9
Add-on PID controller
Controller options
On/Off controller with adjustable hysteresis
P/PI/PID controller as Pulse-Pause, Pulse-Frequency, or
continuous controller
3-point controller
Set points
2 set points with adjustable acting direction (except 3-point
controller)
Relays
2 potential-free contacts 6A, 250 V, max. 550 VA
Hysteresis
Adjustable within the measuring range
Proportional range (X
P
)
Adjustable within the measuring range
Integral time (T
N
)
0…2000 seconds
Derivative time (T
V
)
0
… 2000 seconds
Min. pulse
0.2
… 9.9 seconds
Pulse+Pause time
2
…99 seconds
Max. frequency
1
…7200 pulses/h
Start delay
0
…200 seconds
Dosage monitoring
0
… 99 minutes
Add-on Volume-based dosing
Dosing
0.000
…9.999 l reagent per l of water
Flow measurement
0.000
…9.999 l/pulse
Dosing rate
0.0
…999.9l/h
Min. pulse
0.2
…9.9 seconds
Pulse+Pause time
2
…99 seconds
Max. frequency
1…7200 pulses/h
Relays
2 potential-free contacts 6A, 250 V, max. 550 VA
Relay 1
– control variable
Relay 2
– circulation pump
Содержание Neon pR