85
57
NetGuardian DX 2 fail
8697
9697
58
NetGuardian DX 3 fail
8698
9698
59
GLD/BSU 1 fail
8699
9699
60
GLD/BSU 2 fail
8700
9700
61
GLD/BSU 3+ fail
8701
9701
62
Chan. Port Timeout
8702
9702
63
Craft Timeout
8703
9703
64
Event Que Full
8704
9704
Table A.2
Display 11 System Alarms point descriptions
4.1.1
System Alarms Display Map
See Table A.3 for detailed descriptions of the NetGuardian's system alarms.
Displa
y
Points
Alarm Point
Description
Solution
11
1-16
Control
Relays
Reserved by system for control
relays.
Reserved by system for control
relays.
17
Timed Tick
Toggles state at constant rate as
configured by the Timed Tick timer
variable. Useful in testing integrity
of SNMP trap alarm reporting.
To turn the feature off, set the
Timed Tick timer to 0.
18
Exp. Module
Callout
Alarm is triggered whenever an
alarm point from an Entry Control
Unit (ECU) is collected. A
notification event may be
associated with the alarm to force
a call out or trap.
Disable Building Access Control
(BAC) by setting the BAC Unit ID to
0. If Building Access is being used,
then investigate the ECU alarm
source or don’t associate
notification with the alarm event.
19
Network Time
Server
Communication with Network Time
Server has failed.
Try pinging the Network Time
Server’s IP Address as it is
configured. If the ping test is
successful, then check the port
setting and verify the port is not
being blocked on your network.
20
Accumulation
Event
An alarm has been standing for the
time configured under Accum.
Timer. The Accumulation timer
enables you to monitor how long an
alarm has been standing despite
system reboots. Only the user
may reset the accumulated time, a
reboot will not.
To turn off the feature, under
Accum.Timer, set the display and
point reference to 0.
21
Duplicate IP
Address
The unit has detected another node
with the same IP Address.
Unplug the LAN cable and contact
your network administrator. Your
network and the unit will most likely
behave incorrectly. After assigning