59
The default Web monitor refresh time is 60 seconds.
Note:
The time units are preset to seconds by default and cannot be changed.
16.
Set the
LCD Delay
time between 1–60 seconds. This timer is used when you have set the LCD to
"Point Mode." This time is how long you want the alarm to be displayed on the front panel LCD
screen. The default is 2 seconds.
17.
Set the
LCD Scroll
speed between 100 to 1000 milliseconds. This timer is used to configure how
much time passes for the LCD to continue scrolling. The default is 600 milliseconds.
Setting the System Date and Time
2.18
Fig. 2.34.
The current date and time can be entered from the Date and Time screen or from an SNMP
manager
The date is entered in the mm/dd/yyyy format and the time is entered in the hh:mm:ss format.
!
Hot Tip!
The date and time can also be set from an SNMP manager.
Use the following steps to manually set the system's time and date:
1. From the
Edit
menu, select
Date and Time
, see Figure 2.34.
2. Enter the appropriate date, the day of the week, and time.
3. Click
Submit Data
to save the data and time settings.
The date and time will need resetting following a power failure or reboot unless your
NetGuardian is equipped with the real-time clock option or network time is enabled. (See the section
2.15.1 for instructions on setting the network time configuration.)