5 Settings and Operation
5.1 Testing
1.
If not already done, connect the AC power adapter and/or turn on the AC current.
2.
Verify the Power Status LED on the access door is ON.
3.
If equipped, verify the Battery Status LED on the access door is ON.
NOTE:
Battery status LED may be off if the battery is completely discharged or if the connections are
reversed. A properly connected battery may take up to 12 hours to charge and the LED to turn on.
4.
Verify that the Func1 (D45) and Func2 (D46) LEDs on the controller board (B) blink continuously and D48
and D37 are on (if 2 readers are used).
5.
Activate the bypass switches SW3 and SW5 on the controller board (B).
6.
Verify the locking device is activated. If it is now activated, verify the Fire Alarm input is properly
connected or that a jumper wire is connected to J18 pins 3, 4 and 5.
7.
De-activate the bypass switches SW3 and SW5 on the controller board (B).
8.
If a Request to Exit (REX) button is connected, press it and verify that the door unlocks. Verify the door
unlocks for 5 seconds (delay is configurable) and then relocks afterwards.
9.
If a Remote Unlock button is connected, press it and verify that the door unlocks for as long as the button
is pressed, and then relocks when the button is released.
10.
If a Motion Detector is connected, pass in front of it to verify the door unlocks.
11.
If the RAC5 XT is connected to a Fire Panel and the electromagnetic lock powered by the 12 VDC output of
the RAC5 XT, verify that the electromagnetic lock or a fail-safe electric strike is deactivated when the Fire
Alarm is active (open input).
12.
If a battery back-up is equipped, when fully charged, remove the main AC power adapter and verify the
proper RAC5 XT operation.
5.2 Programming and Auditing
The RAC5 XT can be programmed from Ambiance or Community via the M-Unit. Once programmed, the Zone 1
key card will no longer work. Refer to the M-Unit manual for more details.