background image

CT120G Mini Series Inverter                      Appendix1 Communication Address

 

- 64 - 

Appendix1 Communication Address 

Appendix table 1    485 communication address 

Function 

instruction 

Address 

definition 

Data meaning instruction 

R/W 

characteristics 

Communication 

control 

command 

2000H 

0001H:FWD 

W/R 

0002H:REV 
0003H:RWD JOG 
0004H:REV JOG 
0005H: free stop 
( emergency stop) 
0006H: DEC to stop 
0007H:fault reset 

Number output   
terminal control 

2001H 

BIT0:DO output control 

W/R 

BIT1:reserved 
BIT2:relay 1 output 
control 
BIT3:relay 2 output 
control 
BIT4:HDO output control 

Analog output 
AO1 control 

2002H 

0

7FFF means 0

%~

100

 

Analog output 
AO2 control 

2003H 

0

7FFF means 0

%~

100

 

HDO pulse 
output   

2004H 

0

7FFF means 0

%~

100

 

Inverter state 

3000H 

0001H:FWD running state 

0002H:REV running state 
0003H:inverter stop state 
0004H:inverter fault state 
0005H:inverter ERR03 
state 

Communication 
setting 

value 

address 

1000H 

Communication setting 
frequency

-10000

10000

10000 is 

corresponding to 

W/R 

Содержание CT120G MINI Series

Страница 1: ......

Страница 2: ......

Страница 3: ...anual carefully before using If you find any problem or not understand this manual please contact factory If any problem in using please also contact engineer of factory also We will keep to updated b...

Страница 4: ...CT120G Mini Series Inverter Preface 2...

Страница 5: ...i Series Inverter Content 3 Content 1 Product Infirmation 5 2 Instal and Wire 9 3 Parameter Table 14 Appendix 1 Communication Address 64 Appendix 2 Troubleshooting List 68 Product Certification 75 Gua...

Страница 6: ...CT120G Mini Series Inverter Content 4...

Страница 7: ...B 1 5 5 0 3 7 1 5 CT120G 4T 2 2 B 2 2 5 8 5 3 2 2 Technic table Input and output parameters Input voltage Single phase 220VAC 15 three phase 380VAC 15 Input frequency50 60Hz 5 Output voltage 0 Rated i...

Страница 8: ...quency 0 500Hz DC braking waiting time 0 10s DC braking current 0 0 100 0 DC braking time 0 0 100 0s Auto voltage adjustment Keep a stable voltage automatically when the grid voltage transients Sudden...

Страница 9: ...tion fault current detection fault EEPROM operation fault PID feedback fault factory setting time arrive etc Keypad display LED display Highlight LED digital tube displays the inverter information Oth...

Страница 10: ...Size of inverter and keypad Model Size mm Mounting hole size mm Weight kg W W1 H H1 D CT120G 2S 0 7 B 84 6 67 3 170 2 159 8 131 5 5 1 2 CT120G 2S 1 5 B CT120G 2S 2 2 B CT120G 4T 0 7 B CT120G 4T 1 5 B...

Страница 11: ...CT120G 2S 1 5 B 4 20 16 0 3 150 CT120G 2S 2 2 B 4 32 25 0 3 85 CT120G 4T 0 7 B 2 5 10 10 0 3 320 CT120G 4T 1 5 B 2 5 16 10 0 3 250 CT120G 4T 2 2 B 2 5 16 10 0 3 150 Main terminals Terminal name Funct...

Страница 12: ...ct voltage 0 24V HDO High speed pulse output or collector outputs public termial COM Pulse output frequency range 0 50KHz COM DO HDO public terminal Isolated to GND Analog input 10V 10V output support...

Страница 13: ...mmunication interface Indicator and buttons on keypad Symbol Name meaning Unit LEDs Hz Frequency LED The unit of the current displayed parameter is Hz A Current LED The unit of the current displayed p...

Страница 14: ...he 2nd level menu from the 3rd level menu Multi function key Operate according to multi function selection 2 Run key In the keypad run command reference mode the key is used for start control of the i...

Страница 15: ...stop control of the inverter In other run command reference modes the key is used for stop protection of the inverter 3 At fault or stop state the key is used as a reset key to clear the fault alarm...

Страница 16: ...mmand channel LED flickering 0 F00 02 Main frequency source X 0 Digital setting pre set frequency F00 09 UP DOWN change no power down memory 1 Digital setting pre set frequency F00 09 UP DOWN change w...

Страница 17: ...F00 06 Max frequency 50 00Hz 500 00Hz 50 00 F00 07 Upper limit frequency F00 08 F00 06 Max frequency 50 00 F00 08 Lower limit frequency 0 00Hz F00 07 upper limit of running frequency 0 00 F00 09 Frequ...

Страница 18: ...00 19 Upper limit frequency offset 0 00Hz max frequencyF00 06 0 00 F00 20 Superimposed auxiliary frequency source offset 0 00Hz max frequencyF00 06 0 00 F00 21 Decimal point of frequency instruction 1...

Страница 19: ...uency source selection Hundreds communication command binding frequency source selection F00 26 Serial communication protocol selection 0 Modbus RTU protocol 1 reserved 0 F01 Group Motor 1 parameters...

Страница 20: ...Inductance of asynchronous motor 0 01mH 655 35mH 5 28 F01 10 Mutual inductance of asynchronous motor 0 1mH 6553 5mH 158 6 F01 11 Non load current of asynchronous motor 0 01A F01 03 4 24 F01 12 Motor p...

Страница 21: ...0 invalid 1 valid 0 F02 08 Restart after power off 0 invalid 1 valid 0 F02 09 Waiting time for restart 0 0s 100 0s 0 0 F02 10 Stop mode 0 decelerate to stop 1 coast to stop 0 F02 11 Dead time of FWD R...

Страница 22: ...00 20 F02 22 Speed track KP 0 1000 500 F02 23 Speed track KI 0 1000 800 F02 24 Speed track current 30 200 100 F02 25 Speed track low limit 10 100 30 F02 26 Speed track voltage rise time 5 30 11 F02 27...

Страница 23: ...03 F03 07 0 00 F03 06 V F voltage 2 0 0 100 0 0 0 F03 07 V F frequency 3 F03 05 motor rated voltage F01 03 0 00 F03 08 V F voltage 3 0 0 100 0 0 0 F03 09 Slip compensation gain 0 0 200 0 0 0 F03 10 VF...

Страница 24: ...odel 0 frequency voltage reduce to 0 separately 1 voltage reduce to 0 than frequency reduce 0 F03 18 Over current stall action current 50 200 130 F03 19 Over current stall suppression enable 0 invalid...

Страница 25: ...en place 0 AI2 voltage valid 1 AI2 current valid 00 F04 Group Motor 1 Vector control F04 00 Speed loop proportional gain 1 1 100 30 F04 01 Integral time of speed loop 1 0 01s 10 00s 0 50 F04 02 Switch...

Страница 26: ...etting 6 min AI1 AI2 7 MAX AI1 AI2 1 7 Full scale corresponding to F04 09 0 F04 11 Speed control braking torque max limit source 0 F04 12 set 1 AI1 2 AI2 3 keypad potentiometer setting AI0 4 HDI high...

Страница 27: ...netic 1 direct calculate 2 Automatic adjust 0 F04 19 Over modulation enable selection 0 forbid 1 enable 0 F04 20 Maximum output voltage coefficient 100 110 105 F04 21 Maximum torque coefficient in wea...

Страница 28: ...1 6 5000 1 0000 F05 08 Displayed parameters 1 when running 0000 FFFF BIT0 running frequency Hz BIT1 set frequency Hz BIT2 bus voltage V on BIT3 output voltage V BIT4 output current A BIT5 output power...

Страница 29: ...power on time BIT10 current running time Bit11 high speed pulse input pulse frequency unit 1Hz Bit12 communication set Bit13 encoder feedback speed Bit14 main frequency X diplay Bit15auxiliary freque...

Страница 30: ...laces Unit place B00 14 decimal places 0 0 1 1 2 2 3 3 Ten place B00 19 B00 2 decimal places 1 1 2 2 21 F05 17 Cumulative power on time 0h 65535h 0 F05 18 Cumulative power consumption 0 65535 0 F06Gro...

Страница 31: ...tion 1 17 ACC DEC selection 2 18 frequency source switch 19 UP DOWN setting clear terminal keypad 20 running command switch 21 ACC DEC forbid 22 PID pause 23 PLC reset 24 wobble pause 25 counter input...

Страница 32: ...h terminals 2 switch between terminal control and communication control 38 PID integral pause 39 X setting and pre setting switch 40 Y setting and pre setting switch 41 motor selection terminal 1 42 r...

Страница 33: ...06 15 0 00 F06 14 Curve 1 minimum input corresponding setting 100 0 100 0 0 0 F06 15 Curve 1 maximum input F06 13 10 00V 10 00 F06 16 Curve 1 maximum input corresponding setting 100 0 100 0 100 0 F06...

Страница 34: ...0 F06 29 PULSE minimum input corresponding setting 100 0 100 0 0 0 F06 30 PULSE maximum input F06 28 100 00kHz 50 00 F06 31 PULSE maximum input setting 100 0 100 0 100 0 F06 32 PULSE filt time 0 00s 1...

Страница 35: ...d place keypad potentiometer AI0lower than minimum input setting selection same as AI1 000 F06 35 DI1delay time 0 0s 3600 0s 0 F06 36 DI2delay time 0 0s 3600 0s 0 F06 37 DI3delay time 0 0s 3600 0s 0 F...

Страница 36: ...ode 0 pulse output 1 switch output 0 F07 01 HDOswitch output selection 0 no output 1 running 2 fault output 3 frequency level detection FDT output 4 frequency arrival 5 zero speed running 1 no output...

Страница 37: ...n approach reserved 23 zero speed running 2 output at stop 24 power on time arrive 25 frequency level detection FDT2 output 26 frequency arrive 1 output 27 frequency arrive 2 output 28 current arrive...

Страница 38: ...ower 5 output voltage 6 high speed pulse output 100 0 corresponding to 100 0kHz 7 AI1 8 AI2 9 potentiometerAI0 10 length 11 count value 12 communication set 13 motor speed 14 output current 100 0 corr...

Страница 39: ...17 DO output delay time 0 0s 3600 0s 0 0 F07 18 reserved 0 0s 3600 0s 0 0 F07 19 DO output terminal valid state selection 0 positive logic 1 negative logic unit place HDO ten place relay 1 hundred pla...

Страница 40: ...er detection F08 04 Over voltage stall gain 0 100 1 F08 05 Over voltage stall protection voltage 200 0 2000 0v set according to different models 220V V 380V 760V 0 F08 06 Over current stall gain 0 100...

Страница 41: ...0 1 0 F08 16 First fault type 0 no fault 1 reserved 2 reserved 3 reserved 4 ACC overcurrent E oC1 5 DEC overcurrent E oC2 6 constant speed overcurrent E oC3 7 ACC overvoltage E oU1 8 DEC overvoltage E...

Страница 42: ...22 PID disconnection fault E PIDE 23 braking unit fault E bC 24 run time arrival E ENd 25 electric overload E oL3 26 keypad communication fault E FCE 27 parameter upload fault E UFE 28 parameter downl...

Страница 43: ...at third fault 0 00 F08 21 Bus voltage at third fault 0 0 F08 22 Input terminal status at third fault 0 F08 23 Output terminal status at third fault 0 F08 24 Inverter status at third fault 0 F08 25 Th...

Страница 44: ...cy at first fault 0 00 F08 36 Current at first fault 0 00 F08 37 Bus voltage at first fault 0 0 F08 38 Input terminal status at first fault 0 F08 39 Output terminal status at first fault 0 F08 40 Inve...

Страница 45: ...ce input phase loss E ILF hundred place output phase loss E oLF Thousand external fault E EF Ten thousand communication failure E 485 00000 F08 47 Fault protection act selection 2 Unit place encoder f...

Страница 46: ...and run Automatic back to set frequency if not loss load Ten thousand place PID feedback disconnect fault E PIdE 0 free stop 1 stop as stop mode 2 continue running F08 49 Fault protection act selecti...

Страница 47: ...alid 1 DEC 2 DEC to stop 0 F08 57 Judging voltage for suspended stop instant stop act 80 0 100 0 85 0 F08 58 Judging time for instant stop not stop voltage rise 0 0s 100 0s 0 5 F08 59 Judging voltage...

Страница 48: ...AI1 2 AI2 3 Keypad potentiometerAI0 4 High speed pulse set DI5 5 communication set 6 multi step speed set 0 F09 01 PID 0 0 100 0 50 0 F09 02 PID feedback channel 0 AI1 1 AI2 2 keypad potentiometer AI...

Страница 49: ...00 650 00s 0 00 F09 15 PID reference filter time 0 00 60 00s 0 00 F09 16 PID output filter time 0 00 60 00s 0 00 F09 17 Proportional gain P2 0 0 100 0 20 0 F09 18 Integral time I2 0 01s 10 00s 2 00 F0...

Страница 50: ...ount value F10 00 Wobble set mode 0 Corresponding to centre frequency 1 Corresponding to maximum frequency 0 F10 01 Wobble range 0 0 100 0 0 0 F10 02 Saltation frequency amplitude 0 0 50 0 0 0 F10 03...

Страница 51: ...100 0 of max frequency F00 06 0 F11 04 Multi step speed command 4 100 0 100 0 100 0 of max frequency F00 06 0 F11 05 Multi step speed command 5 100 0 100 0 100 0 of max frequency F00 06 0 F11 06 Mult...

Страница 52: ...ed command 12 100 0 100 0 100 0 of max frequency F00 06 0 F11 13 Multi step speed command 13 100 0 100 0 100 0 of max frequency F00 06 0 F11 14 Multi step speed command 14 100 0 100 0 100 0 of max fre...

Страница 53: ...0 3 0 F11 22 Step 2 running time 0 0s h 6553 5s h 0 F11 23 PLC step 2 ACC DEC time selection 0 3 0 F11 24 Step 3 running time 0 0s h 6553 5s h 0 F11 25 PLC step 3 ACC DEC time selection 0 3 0 F11 26 S...

Страница 54: ...38 Step 10 running time 0 0s h 6553 5s h 0 F11 39 PLC step 10 ACC DEC time selection 0 3 0 F11 40 Step 11 running time 0 0s h 6553 5s h 0 F11 41 PLC step 11 ACC DEC time selection 0 3 0 F11 42 Step 1...

Страница 55: ...1 2 AI2 3 potentiometer AI0 4 high speed pulse 5 PID 6 F00 09 give UP DOWNmodify 0 F12 Group 485 communication F12 00 Local address 1 247 0 broadcast address 1 F12 01 Baud rate 0 300BPS 1 600BPS 2 120...

Страница 56: ...0 Jogging frequency 0 00Hz max frequencyF00 06 2 00 F13 01 Jogging running ACC time 0 0s 6500 0s 20 0 F13 02 Jogging running DEC time 0 0s 6500 0s 20 0 F13 03 ACC time 2 0 0s 6500 0s 20 0 F13 04 DEC t...

Страница 57: ...8 Frequency detection delay value FDT1 0 0 100 0 FDT1 level 5 0 F13 19 Frequency arrival detection amplitude 0 0 100 0 Max frequency 0 0 F13 20 Jump frequency valid or not while ACC DEC 0 invalid 1 va...

Страница 58: ...arrival detection frequency range 2 0 0 100 0 Max frequency 0 0 F13 32 0 current detection level 0 0 300 0 100 0 corresponding motor rated current no outout at stop 5 0 F13 33 0 current detection del...

Страница 59: ...0 00V F13 44 3 10 F13 44 AI1input voltage protection value low limit F13 43 11 00V 6 80 F13 45 Module temperature arrive 0 100 75 F13 46 Radiate fan control 0 fan runs while inverter running 1 fan alw...

Страница 60: ...en place user change parameter group display selection 0 not display 1 display 11 F16 02 Function parameter modify control 0 can modify 1 can not modify 0 A00 00Speed troque control mode A00 00 Speed...

Страница 61: ...rque ACC time 0 00s 650 00s 0 00 A00 08 Torque DEC time 0 00s 650 00s 0 00 A03 Group Reserved A04 Group Reserved A05 Group Control Optimization Parameters A05 00 DPWM switch high limit frequency 5 00H...

Страница 62: ...6 02 0 00 A06 01 curve4min input set 100 0 100 0 0 0 A06 02 curve4inflection point 1input A06 00 A06 04 3 00 A06 03 curve4inflection point 1input set 100 0 100 0 30 0 A06 04 curve4inflection point 2in...

Страница 63: ...t jump point 100 0 100 0 0 0 A06 27 AI2set jump range 0 0 100 0 0 5 A06 28 keypad potentiometerAI0se t jump point 100 0 100 0 0 0 A06 29 keypad potentiometerAI0se t jump range 0 0 100 0 0 5 A07 Group...

Страница 64: ...kHz 0 01 B00 19 Feedback speed unit Hz 0 01 B00 20 Remaining running time unit min 0 1 B00 21 AI1 before correction voltage unit V 0 001 B00 22 AI2 before correction voltage current unit V mA 0 001 B...

Страница 65: ...sition unit 0 1 B00 34 reserved 1 B00 35 Aim torque unit 0 1 B00 36 reserved 1 B00 37 Power factor angle unit 0 1 B00 38 reserved 1 B00 39 VF separation aim voltage unit V 1 B00 40 VF separation outpu...

Страница 66: ...t Number output terminal control 2001H BIT0 DO output control W R BIT1 reserved BIT2 relay 1 output control BIT3 relay 2 output control BIT4 HDO output control Analog output AO1 control 2002H 0 7FFF m...

Страница 67: ...ltage 0 2000 0 unit0 1V R 1003H Output voltage 0 1200V unit1V R 1004H Output current 0 0 3000 0 unit0 1A R 1005H Output power 300 0 300 0 unit0 1 100 corresponding to motor rated power R 1006H Output...

Страница 68: ...00 corresponding to 100 0 R 1011H PID feedback value 0 1000 1000 corresponding to 100 0 R 1012H PLC and multi steps speed current step 0 0xFFFF R 1013H High speed pulse HDI value 0 00 50 00kHz unit0 0...

Страница 69: ...ource display R Note in the Data meaning instruction in the table above the number values such as 10000 1000 are decimal numbers which need to be converted to hexadecimal in actual use Read and write...

Страница 70: ...he inverter of larger power E oC3 Constant speed running overcurrent 1 Load sudden change or abnormal 2 The grid voltage is too low 3 The inverter power is too small 1 Check load or decrease load sudd...

Страница 71: ...te motor E oL2 Inverter overload 1 The acceleration is too fast 2 Restart the rotating motor 3 The grid voltage is too low 4 The load is too large 1 Reduce the acceleration speed 2 Avoid restart at st...

Страница 72: ...nnect 6 Ask for service 7 Ask for service 8 Ask for service E EF External fault SI external fault input terminal operation 1 Check the external device input E 485 Communicati on fault 1 Incorrect baud...

Страница 73: ...s according to the motor name plate 3 Make the motor at no load and re identification 4 Check the motor wiring and parameters setting E EEP EEPROM read and write fault 1 Control parameters read and wr...

Страница 74: ...sk for service E UFE Parameter up load wrongly 4 Keypad wire not good 5 Keypad wire too long or broken 6 Communication part of keypad or main board have electric problem 4 Check keypad wire 5 Check if...

Страница 75: ...1 Load is abnormal or inverter not connect motor 2 Synchronous motor control parameters not right Self start not right 1 Check load Check control parameters add stall detection time E LL Under load f...

Страница 76: ...CT120G Mini Series Inverter Appendix2 Troubleshooting List 74...

Страница 77: ...CT120G Mini Series Inverter Product Certification 75 Product Certification Product Name Product standard Product number Release date Inspector...

Страница 78: ...76 Guarantee User File User Name Contact person Address Telephone Product File Model number Post code Dealer Company Fault information Application of environment Maintenance situation describe Mainten...