5
SYSTEM CONFIGURATION
5.1
Local configuration interface
LED zone controller based on TCM 330 can provide a simple local configuration interface
based on two buttons (LRN and DIM) and two LED (red and green). Their functions are de-
scribed in the subsequent chapters.
If the LED is not in a specific mode as described here then its output state will indicate the
relay output state. The green LED output will blink if the relay is in active state while the
red LED output will blink if the relay is in inactive state (output state = OFF). The blinking
period is chosen to minimize energy consumption.
Note that all TCM 330 parameters can be configured using remote commissioning as dis-
cussed in chapter 5.3. Having a dedicated local configuration interface is therefore optional.
5.1.1
Linking
The LRN and DIM button of the local interface can be used for linking to transmitters or
transceivers as outlined in chapter 5.1.4.
5.1.2
Device reset
The LRN button of the local interface can be used to reset all TCM 330 device parameters
(including PIN code) to factory state similar to a factory reset.
This functionality can be particularly useful if remote configuration access to the device is
secured with a custom PIN code and this PIN code is lost.
In order to reset TCM 330 to factory state, press and hold the LRN button for 10 seconds.
After that the red LED output will be set to active for 10 seconds.