DPC Touch User Manual
18
Screen 3 of 4: Management of fastening time
Min fastening
time limit, %
Lower limit of fastening time control in percentage of
actual fastening time detected during programming.
NOTE: changes will be applied only to new jobs, existing
jobs won’t be affected.
0 - 100
25
Max fastening
time limit, %
Upper limit of fastening time control in percentage of
actual fastening time detected during programming.
NOTE: changes will be applied only to new jobs, existing
jobs won’t be affected.
0 - 100
25
Start trigger
release time
limit, ms
Fastening time threshold after which trigger release will be
considered as NG tightening. Error message “Trigger
released before Torque Up” will appear.
0 - 9999
0
Temporary
position loss
time, ms
If fastening is started (Motor Run signal is received), then it
is allowed to exit position OK zone (green) into
approaching area (orange) for the specified time without
locking the tool. If this time limit is passed the tool will be
instantly locked. If position NOK zone (red) is entered the
tool will be instantly locked.
NOTE: this parameter is used to avoid interruptions of
fastening process when position is lost for short time due
to vibrations.
0 - 3000
50
Judging time,
ms
Judging time is used if Fastening OK signal is delayed after
the fall of Motor run signal.
0 - 500
100
Screen 4 of 4: Management of NG tightenings
Number of
retightenings
on a position
Maximum number of attempts to rework a NG fastening. If
the maximum number of attempts is reached the current
position can be skipped or Job/Step can be reset according
to parameters selected.
NOTE: this parameter is not effective in non-sequential
assembly mode.
0 - 10
1
Skip NG
tightening
Allows to skip automatically a NG tightening if rework is
not allowed or if
rework wasn’t successful.
ON/OFF
OFF
Fastening NG
signal if
position
skipped
If turned ON, Fastening NG signal will be provided when a
position is skipped automatically, by Skip button on the
operating screen or by external input. If turned OFF,
Fastening OK signal will be provided.
ON/OFF
ON
Auto reset
delay, ms
Alarm can be reset automatically after the specified delay.
If delay is equal to 0 than reset has to be done manually or
by external input.
0 - 9999
3000
Содержание DPC Touch
Страница 1: ... DPC Touch INSTRUCTIONS MANUAL ...
Страница 24: ...DPC Touch User Manual 25 9 3 Inputs wiring scheme ...
Страница 36: ...Doc 60290 12 17 ...