21
DC-ITD-CL4andCL8MAN01.A
www.dodtec.com
NOV 2018
815-788-5200
CL4 & CL8 Manual
Figure 3.6
Figure 3.7
Use only AWG22 to AWG18 twisted wire (wire sizes UL1015 and UL1007)
Strip from .2
6” to .31” (6.5mm to 8.0mm) from each wire to insert into
the connector.
1.
To connect the wires to the spring-loaded output connector:
2.
Insert the screwdriver into the square shaped hole which will open the round hole for the wire.
3.
Continue to hold the screwdriver while inserting the wire into the round shaped hole.
4.
While holding the wire in place remove the screwdriver which closes the clamp onto the wire.
5.
IMPORTANT
: Be sure the wire is inserted completely into the hole. Failure to do so could result in
system failure, electrical shock.
6.
To remove a wire, re-insert the screwdriver in the hole as described in step 1 and
gently pull the wire
out while the spring is compressed.
V1 +
V1 -
LOAD
+ 24V -
-
…
OUT 0
OUT 15
LOAD
V2 +
V2 -
LOAD
+ 24V -
-
…
OUT 16
OUT 31
LOAD
DANGER:
Before performing any wiring modifications, be sure that
power to the CL4/CL8 is disconnected and remove the output
connector from the output relay block.