48
DC-ITD-CL4andCL8MAN01.A
www.dodtec.com
NOV 2018
815-788-5200
CL4 & CL8 Manual
B.2.1 4 to 20mA Module (4 Points per Module) (PN: 2-500-011)
TR+
SLD
+24V
AG1
V2+
I2+
V3+
I3+
AG4
FG*
TR-
0V
V1+
I1+
AG2
FG*
AG3
V4+
I4+
GND
Labeled connector on each 4 to 20ma Module. *Each ‘FG’ terminal may be used for 2 points.
4-20 ma Output Circuit Wiring.
Description
Module
Connection
Symbol
Point 1 4 to 20 ma
1
I1+
I+
1
AG1
AG
1
FG*
FG
Point 2 4 to 20 ma
1
I2+
I+
1
AG2
AG
1
FG*
FG
Point 3 4 to 20 ma
1
I3+
I+
1
AG3
AG
1
FG*
FG
Point 4 4 to 20 ma
1
I4+
I+
1
AG4
AG
1
FG*
FG
Point 5 4 to 20 ma
2
I1+
I+
2
AG1
AG
2
FG*
FG
Point 6 4 to 20 ma
2
I2+
I+
2
AG2
AG
2
FG*
FG
Point 7 4 to 20 ma
2
I3+
I+
2
AG3
AG
2
FG*
FG
Point 8 4 to 20 ma
2
I4+
I+
2
AG4
AG
2
FG*
FG
Module
Address
Module 1
9
Module 2
D
IMPORTANT:
Use only connections above shown in grey. Other connections are
pre-wired in the CL4/CL8.