14
1100T Wireless Translator Installation and Programming Guide | Digital Monitoring Products, Inc.
COMPLIANCE LISTING SPECIFICATIONS
Commercial Fire
Power Supply
When using the Model 372-500-W plug-in
power supply for Commercial Fire installations,
mount the 1100T on a UL-listed gangbox and
connect by conduit to a listed transformer
enclosure such as the ES501 or ES502.
Install the enclosure by removing the two
screws from the outlet and inserting them
through the back of the enclosure. Install
conduit fittings, connect wiring, and install the
power supply. Secure the enclosure cover with
two screws. See Figure 3.
Conduit
ES501
372-500-W
1100TF installed on backbox
Figure 3: Power Supply
with Enclosure Wiring
Battery
The 9800BAT2400 provides 24-hour standby operation for Commercial Fire installations.
Install the 1100TF in accordance with NFPA 70 and NFPA 72 Chapter 29.
Supervision Time
1100T and Non-DMP Sensor supervision time must be set to 4 hours or less.