Annex 3 – Instructions for Software update
Test 16: Reduced Pit Safety test (EN 81-21 – ELGO-CP+eSGC)
Test for Reduced Pit and Protection system based on ELGO+eSGC.
Protection intervention is after a shaft access, in the point given by distance TRIPD (Monitor Encoder, pag 8) from the
Lower Reference position (Cabine on the buffer).
During the test ELGO intervention is given also with lift in normal mode, without any shaft access simulation.
Before starts the test put the lift over the intervention point.
During the test elevator car will start in DOWN direction (to the bottom floor). When elevator car reaches the
intervention point, ELGO will open OC contact and switch off the eSGC output stopping the elevator car (Fault ELGO
Cod. 5).
After test it is necessary a fault reset (Menu Fault, Reset) to put the ELGO LIMAX33-CP in normal operating mode.
Test 17: OC Safety contact test (ELGO-CP)
Only for installation with ELGO-CP.
Test checks if the safety contact OC inside the ELGO works porperly: contact opens for 0,5 sec. (you can check the
safety chain open from SE3 point).
Test is automatically executed one time a day.
It is no further operation needed after the test (lift is in normal Service).
Test 18: Door Disable
Test for temporarly disabling door operators.
Test is useful if technician needs to make some test with lift in normal mode but without the risk some user can enter
in the elevator car.
It is possible to program a time of 1/5/10/30/60 minutes.
Time is valid also if Lift will be put in inspection / Normal again.
At the end of timer, lift comes back in normal mode.
Test 19: Black out Simulation
Only for installation with full emergency option. Lift behaviour is the same you have when power supply goes off, so it
make an automatic emergency moving the car to the floor and opens the door.
Test 20: Telephon call for low batteries level simulation
Controller send command to DMCPIT (output ALARM Enable) as if the battery level was wrong for an emergency
call. This signal has to be connected to the telephone’s input for emergency call.
Test and measures (fourth part)
SW update file for PLP is:
FileName.PP2
Insert the USB device into the slot, waiting for the message as in the Figure 1.
PlayPad (PLP) SW update procedure