N.
Fault
Type
Description
Remedy
41 Fault ISO
Problem detected in the operation
monitoring of safety module for advanced
door opening / re-leveling. If activated,
the installation goes into “out of service”
mode at the top floor (electric) or bottom
floor (hydro).
Cod 100: fail on Safety module monitor
during travel
Cod 200: fail on Safety module monitor at
level
Check the alignment of ISO1 and
ISO2.
Reset ISO in the menu Faults (§ 5.3).
42
TOC
Communication
No serial link between controller and car
(in case of car serial link system
configuration)
Check CAN link between controller
and top of car board
43 Inspection
The system is in Inspection mode
(NORM/ISP switch set to Inspection)
EN 81.1/2
Cod 1: REV input open (STD Version)
Cod 2: TOC’s REV1 input open
Cod 3: REV + TOC’s REV1 input open
Cod 5: REV input open (Pitagora version)
Cod 6: REV1 input open
Cod 7: REV + TOC’s REV1 input open
EN 81.20
Cod 11: PME inspection (REV)
Cod 12: TOC inspection (REV1)
Cod 13: PME + TOC inspection (REV +
REV1)
Cod 14: PIT Inspection (REV2)
Cod 15: PME + PIT Inspection (REV +
REV2)
Cod 16: TOC + PIT Inspection (REV1 +
REV2)
Cod 17: PME + TOC + PIT Inspection
(REV + REV1 + REV2)
To exit the inspection mode move the
NORM/ISP switch to Normal and
close the safety chain to trigger the
reset procedure
44
Re-levelling not
completed
Hydraulic lifts: the re-levelling procedure
was not completed within 10 seconds. All
subsequent re-levelling requests at the
same floor are inhibited
Check:
1- the correct operation of the Safety
module and of its sensors ZP1 and
ZP2;
2- Check the FAI/FAS or ENCODER
sensors and the ZP sensor;
3- position of the magnets in the re-
levelling zone;
4- RISO relay.
45 Fault ZP
Door zone contact stays open when the
sensor is in door zone position
Check the correct operation of the
door zone sensor (if present);
See Fault # 33