DEHUMIDIFYING ACTION WITHOUT DEHUMIDIFIER RELAY, OA1 DIFFERENT FROM DEH 

In this case the dehumidifying action is performed by setting the following parameters in this way: 

tHu = c-H kind of dehumidifying by means of heating and compressor relays 

oA1 different from dEH:  

The heating and compressor outputs are activated together when humidity is higher than SET %RH+dbH value. Outputs are disabled when 
humidity comes back to the SET %RH value. 

 

4.2.1  Relation between cooling, heating and dehumidifying 

1.

 

If is simultaneously present a request of cooling (temp>SET TEMP+dbt) and dehumidifying (RH > SET %RH+dbH): the cooling action has 
the priority over the dehumidifying action: only the compressor relay is energised till the SET TEMP is reached at this point also the heating 
relay is enabled. 

 

 

2.

 

If is simultaneously present a request of heating (temp< SET TEMP-dbt) and dehumidifying (RH > SET %RH+dbH): the dehumidifying 
action has the priority over the heating action: both the compressor and the heating relays are energised till the humidity set is reached at 
this point only the heating relay is enabled. 

4.3

 

DEHUMIDIFYING ACTION WITH DEHUMIDIFIER RELAY, OA1 = DEH 

The configurable relay is used, setting the parameter 

oA1 =dEH.

 

NOTE: 

the LIGHT button is not more available; Two kinds of de-humidifying are available: 

4.3.1  Dehumidifying action with ONLY de-humidifier relay 

By setting the parameter 

tHu 

db

 the de-humidifying action is performed by enabling the de-humidifier relay when the humidity is higher than SET 

%RH

 

+  dbH. 

The relay is switch off when humidity comes back to the SET %RH value. 

 

4.3.2  Dehumidifying action with de-humidifier and compressor relays 

By setting the parameter 

tHu 

cHu

 the de-humidifying action is performed by enabling the de-humidifier and compressor relays together. when 

the humidity is higher than SET %RH

 

+  dbH. The relays are switched off when humidity comes back to the SET %RH value. 

 

If is simultaneously present a request of cooling (temp>SET TEMP+dbt) and dehumidifying (RH > SET %RH+dbH): the cooling action has the 
priority over the dehumidifying action: only the compressor relay is energised till the SET TEMP is reached at this point also the de-humidifier is 
enabled. 

5.

 

 FA NS 

The fan control mode is selected by means of the “

FnC

” parameter: 

FnC=C-n

   fans will switch ON and OFF with the compressor and

 not run

 during defrost

:

FnC= O-n

 fans will run continuously, but not during defrost  

FnC=C-y

   fans will switch ON and OFF with the compressor and 

run

 during defrost; 

FnC=O-y

   fans will run continuously also during defrost 

6.

 

EXTRACTOR FAN 

6.1

 

EXTRACTOR FAN CYCLES 

The second relay is configured as extractor fan, oA2= ESt, then it is possible to make extraction cycles, both manually and 

automatically. 

 

 
Extraction cycle can be activated both manually by pushing the UP key for 3s, and automatically by the internal time 

rFi. 

Cycle duration is set by 

the 

rFd 

parameter. The cycle can be stopped also by key.  

 
If  

rFI

 = 0 only manual cycle can be activated. 

If  

rFd

 = 0 the cycle is stopped only by pushing the key. 

Содержание COOL MATE XLH360

Страница 1: ...XEL Operating Instructions cod 1592017410 1592017410 XLH360 GB r1 0 15 04 2005 doc XLH360 1 16 Temperature and humidity controller for seasoning maturing cabinets XLH360 COOL MATE Operating Instructio...

Страница 2: ...SPLAY________________________________________________________________ 6 9 PARAMETER LIST ____________________________________________________________ 8 10 DIGITAL INPUT _______________________________...

Страница 3: ...It has 2 NTC inputs one for thermostat the other one for defrost It s also present a 4 20mA input for humidity There is one digital input free contact configurable by parameter An output allows the u...

Страница 4: ...ay By setting the parameter tHu db the de humidifying action is performed by enabling the de humidifier relay when the humidity is higher than SET RH dbH The relay is switch off when humidity comes ba...

Страница 5: ...time and pass to the setting of the stopping phase the oFF message is displayed 7 Push the CLOCK key to see its duration and use the UP and DOWN keys to set it 8 Confirm the value by pushing again th...

Страница 6: ...nd modify target humidity set point SET RH of the running SH1 phase in programming mode it selects a parameter or confirm an operation In programming mode it browses the parameter codes or increases t...

Страница 7: ...con starts flashing 2 To change the Set value push the o or n arrows within 10s 3 To memorise the new set point value push the SET key again or wait 10s 8 3 TO START A MANUAL DEFROST 1 Push the DEF ke...

Страница 8: ...MP dbt value and disabled when the SET TEMP is reached dbH half dead band width for humidity 0 5 25 5RH this band is place below and above the humidity set point SET RH The dehumidifying action is ena...

Страница 9: ...e alarm setting ALC rE 0 50 C or 90 F ALC Ab 50 C or 58 F ALU when this temperature is reached and after the ALd delay time the LA alarm is enabled ALU High temperature alarm setting ALC rE 0 50 C or...

Страница 10: ...dEF defrost relay Adt RS485 serial address for temperature loads 0 247 identifies the instrument within a control or supervising system AdH RS485 serial address for humidity loads 0 247 identifies the...

Страница 11: ...s on the i1P parameters CL the digital input is activated by closing the contact OP the digital input is activated by opening the contact 11 INSTALLATION AND MOUNTING The temperature range allowed for...

Страница 12: ...s or pipepresses using the centres signed in the bottom cover of the Cool Mate Fig 3 H I Then make 3 holes in the wall as indicated in Fig 3 L M N to fix the Cool Mate 4 Fix the cablepresses and the p...

Страница 13: ...supply complies with the instrument s requirements Separate the probe cables from the power supply cables from the outputs and the power connections Do not exceed the maximum current allowed on each r...

Страница 14: ...he probe Temperature alarms HA and LA automatically stop as soon as the thermostat temperature returns to normal values or when the defrost starts Humidity alarms HHA and LHA automatically stop as soo...

Страница 15: ...cF C Pr2 Measurement unit C F rES dE Pr2 Resolution for C in integer dE decimal rEH Hd Pr2 Resolution for RH in integer Hd half digit trC co Pr2 Instrument behaviour at the end of the cycle co start h...

Страница 16: ...o3 0 0 Pr1 Humidity probe calibration 10 10 P2P YES Pr2 Evaporator probe presence no absent YES present P3P YES Pr2 Humidity probe presence no absent YES present Lci 0 0 Pr2 Readout with 4 mA 999 999...

Отзывы: