Operating Instructions 

cod. 1592017410 

 

1592017410  XLH360 GB r1.0  15.04.2005.doc 

XLH360 

2/16 

 

C

OOL

M

ATE 

 

XLH360 

 
 

INDICE 

 

1.

 

GENERAL WARNING__________________________________________________________ 3

 

2.

 

GENERAL DESCRIPTION ______________________________________________________ 3

 

3.

 

TEMPERATURE REGULATION__________________________________________________ 3

 

4.

 

HUMIDITY REGULATION ______________________________________________________ 3

 

5.

 

FA NS ______________________________________________________________________ 4

 

6.

 

EXTRACTOR FAN ____________________________________________________________ 4

 

7.

 

MATURING CYCLE WITH DRIPPING, RUNNING AND STOPPING PHASE. ______________ 5

 

8.

 

THE DISPLAY________________________________________________________________ 6

 

9.

 

PARAMETER LIST ____________________________________________________________ 8

 

10.

 

DIGITAL INPUT _____________________________________________________________ 10

 

11.

 

INSTALLATION AND MOUNTING _______________________________________________ 11

 

12.

 

DIMENSIONS _______________________________________________________________ 13

 

13.

 

ELECTRICAL CONNECTIONS _________________________________________________ 13

 

14.

 

HOW TO USE THE HOT KEY __________________________________________________ 13

 

15.

 

ALARM SIGNALLING _________________________________________________________ 14

 

10.

 

TECHNICAL DATA ___________________________________________________________ 14

 

16.

 

XLH360 WIRING CONNECTIONS _______________________________________________ 15

 

17.

 

DEFAULT SETTING VALUES __________________________________________________ 15

 

 

Содержание COOL MATE XLH360

Страница 1: ...XEL Operating Instructions cod 1592017410 1592017410 XLH360 GB r1 0 15 04 2005 doc XLH360 1 16 Temperature and humidity controller for seasoning maturing cabinets XLH360 COOL MATE Operating Instructio...

Страница 2: ...SPLAY________________________________________________________________ 6 9 PARAMETER LIST ____________________________________________________________ 8 10 DIGITAL INPUT _______________________________...

Страница 3: ...It has 2 NTC inputs one for thermostat the other one for defrost It s also present a 4 20mA input for humidity There is one digital input free contact configurable by parameter An output allows the u...

Страница 4: ...ay By setting the parameter tHu db the de humidifying action is performed by enabling the de humidifier relay when the humidity is higher than SET RH dbH The relay is switch off when humidity comes ba...

Страница 5: ...time and pass to the setting of the stopping phase the oFF message is displayed 7 Push the CLOCK key to see its duration and use the UP and DOWN keys to set it 8 Confirm the value by pushing again th...

Страница 6: ...nd modify target humidity set point SET RH of the running SH1 phase in programming mode it selects a parameter or confirm an operation In programming mode it browses the parameter codes or increases t...

Страница 7: ...con starts flashing 2 To change the Set value push the o or n arrows within 10s 3 To memorise the new set point value push the SET key again or wait 10s 8 3 TO START A MANUAL DEFROST 1 Push the DEF ke...

Страница 8: ...MP dbt value and disabled when the SET TEMP is reached dbH half dead band width for humidity 0 5 25 5RH this band is place below and above the humidity set point SET RH The dehumidifying action is ena...

Страница 9: ...e alarm setting ALC rE 0 50 C or 90 F ALC Ab 50 C or 58 F ALU when this temperature is reached and after the ALd delay time the LA alarm is enabled ALU High temperature alarm setting ALC rE 0 50 C or...

Страница 10: ...dEF defrost relay Adt RS485 serial address for temperature loads 0 247 identifies the instrument within a control or supervising system AdH RS485 serial address for humidity loads 0 247 identifies the...

Страница 11: ...s on the i1P parameters CL the digital input is activated by closing the contact OP the digital input is activated by opening the contact 11 INSTALLATION AND MOUNTING The temperature range allowed for...

Страница 12: ...s or pipepresses using the centres signed in the bottom cover of the Cool Mate Fig 3 H I Then make 3 holes in the wall as indicated in Fig 3 L M N to fix the Cool Mate 4 Fix the cablepresses and the p...

Страница 13: ...supply complies with the instrument s requirements Separate the probe cables from the power supply cables from the outputs and the power connections Do not exceed the maximum current allowed on each r...

Страница 14: ...he probe Temperature alarms HA and LA automatically stop as soon as the thermostat temperature returns to normal values or when the defrost starts Humidity alarms HHA and LHA automatically stop as soo...

Страница 15: ...cF C Pr2 Measurement unit C F rES dE Pr2 Resolution for C in integer dE decimal rEH Hd Pr2 Resolution for RH in integer Hd half digit trC co Pr2 Instrument behaviour at the end of the cycle co start h...

Страница 16: ...o3 0 0 Pr1 Humidity probe calibration 10 10 P2P YES Pr2 Evaporator probe presence no absent YES present P3P YES Pr2 Humidity probe presence no absent YES present Lci 0 0 Pr2 Readout with 4 mA 999 999...

Отзывы: