background image

dIXEL

 

Operating Instructions 

cod. 1592017410 

 

1592017410  XLH360 GB r1.0  15.04.2005.doc 

XLH360 

9/16 

 trC=cLE 

at the end of the stopping phase the regulation restarts from the running phase.

 

 

DEFROST 
tdF  

Defrost type: rE

 = electrical heater (Compressor OFF); 

in

 = hot gas (Compressor and defrost relays ON) 

EdF Defrost 

mode:

  

in

 = 

interval mode

. The defrost starts when the time “

Idf

” is expired; 

Sd

=

Smartfrost mode

. The IdF time (interval 

between defrosts) is increased only when the compressor is running (even non consecutively).  

SdF 

Set point for SMARTFROST

: (-30

÷

30 °C/ -22

÷

86 °F) evaporator temperature which allows the IdF counting (interval between defrosts) in 

SMARTFROST mode. 

dtE   Defrost termination temperature:

 (-50,0÷110,0°C; -58÷230°F) (Enabled only when the evaporator probe is present) sets the 

temperature measured by the evaporator probe which causes the end of defrost. 

IdF Interval 

between defrosts: 

(1÷120h) Determines the time interval between the beginning of two defrost cycles. 

MdF   Duration of defrost: 

(0÷255 min) When 

P2P = n

, no evaporator probe, it sets the defrost duration, when 

P2P = y

, defrost end based on 

temperature, it sets the maximum length for defrost. 

dFd   Display during defrost: rt

 = real temperature; 

it

 = temperature reading at the defrost start; 

Set

  

set point; 

dEF

 = “dEF” label; 

 dEG

 = “dEG” label;

 

dAd   Defrost display time out:

 (0

÷

255 min) Sets the maximum time between the end of defrost and the restarting of the real room temperature 

display. 

Fdt  

Drain down time:

 (0÷60 min.) time interval between reaching defrost termination temperature and the restoring of the control’s normal 

operation. This time allows the evaporator to eliminate water drops that might have formed due to defrost.

 

dPO   First defrost after start-up:  y 

= Immediately; 

n

 = after the IdF time 

Hud 

Humidity control during defrost:

 

no

: the humidity control is stopped during the defrost; 

yES

 the humidity control works also during the 

defrost. 

FANS 
FnC 

Fan operating mode: C-n

 = running when a load is on, OFF during the defrost; 

C-y

 = running when a load is on, ON during the defrost; 

O-n

 = continuous mode, OFF during the defrost; 

O-y

 = continuous mode, ON during the defrost; 

EXTRACTOR FANS 
rFi 

Interval between 2 cycles of change of air 

(0÷120 ore; 0 = only manual starting) 

rFd 

Duration of change of air cycle 

(0÷250min; 0 =  only manual stopping) 

 

TEMPERATURE ALARMS 
ALC  Temperature alarm configuration: rE

 = High and Low alarms related to Set Point; 

Ab

 = High and low alarms related to the absolute 

temperature. 

ALL 

Low temperature alarm setting:

 

ALC = rE 

, 0 

÷

 50 °C or 90°F; 

ALC = Ab 

, - 50°C or -58°F 

÷

 ALU;  when  this  temperature  is  reached 

and after the ALd delay time, the LA alarm is enabled,. 

ALU  High temperature alarm setting:

  

ALC= rE

, 0 

÷

 

50°C or 90°F; 

ALC= Ab

, ALL 

÷

 110°C or 230°F; when this temperature is reached and 

after the ALd delay time the HA alarm is enabled. 

 

ALH  Temperature alarm recovery differential: 

(0,1÷25,5°C; 1÷45°F) Intervention differential for recovery of temperature alarm.

 

ALd 

Temperature alarm delay:

 (0÷255 min) time interval between the detection of an alarm condition and the corresponding alarm signalling. 

dAO    Delay of temperature alarm at start-up:

 (0min÷23h 50min) time interval between the detection of the temperature alarm condition after 

the instrument power on and the alarm signalling.

 

EdA   Alarm delay at the end of defrost: 

(0

÷

255 min) Time interval between the detection of the temperature alarm condition at the end of 

defrost and the alarm signalling. 

dot  

Delay of temperature alarm after closing the door : 

(0

÷

255 min) Time delay to signal the temperature alarm condition after closing the 

door. 

HUMIDITY ALARMS 
AHC  Humidity alarm configuration: rE

 = High and Low alarms related to humidity Set Point ; 

Ab= 

High and low alarms related to the 

“absolute” humidity. 

AHL  Low humidity alarm setting: 

(with AHC = rE: 

0 ÷ 50

. With AHC = Ab: 

Lci ÷ AHu)

 

 

when this humidity is reached and after the AHd delay time, the HLA alarm is enabled,. 

AHu  High humidity alarm setting:

 (with AHC = rE: 0÷50°C. with AHC = Ab: 

AHL ÷ uci

 

 

when this humidity is reached and after the AHd delay time the HHA alarm is enabled. 

AHH  Humidity alarm recovery differential: 

(0.5÷20.0) Intervention differential for recovery of humidity alarm.

 

AHd  Humidity alarm delay:

 (0÷255 min) time interval between the detection of an alarm condition and the corresponding alarm signalling. 

dHo    Delay of humidity alarm at start-up:

 (0min÷23h 50min) time interval between the detection of the humidity alarm condition after the 

instrument power on and the alarm signalling.

 

doH   Alarm delay at the end of defrost: 

(0

÷

255 min) Time interval between the detection of the humidity alarm condition at the end of defrost 

and the alarm signalling. 

doA   Open door alarm delay:

(0÷255 min) delay between the detection of the open door condition and its alarm signalling: the flashing 

message “

dA

” is displayed. 

tbA 

Alarm relay status after pushing a key: on= 

the relay remains on

; off= 

the relay is switched off. 

nPS   Pressure switch number:

 (0 

÷

15) Number of activation of the pressure switch, during the “

did

” interval, before signalling the alarm event 

(I1F= PAL). 

If the nPS activation in the “did” time is reached, switch off and on the instrument to restart normal regulation. 

 

Содержание COOL MATE XLH360

Страница 1: ...XEL Operating Instructions cod 1592017410 1592017410 XLH360 GB r1 0 15 04 2005 doc XLH360 1 16 Temperature and humidity controller for seasoning maturing cabinets XLH360 COOL MATE Operating Instructio...

Страница 2: ...SPLAY________________________________________________________________ 6 9 PARAMETER LIST ____________________________________________________________ 8 10 DIGITAL INPUT _______________________________...

Страница 3: ...It has 2 NTC inputs one for thermostat the other one for defrost It s also present a 4 20mA input for humidity There is one digital input free contact configurable by parameter An output allows the u...

Страница 4: ...ay By setting the parameter tHu db the de humidifying action is performed by enabling the de humidifier relay when the humidity is higher than SET RH dbH The relay is switch off when humidity comes ba...

Страница 5: ...time and pass to the setting of the stopping phase the oFF message is displayed 7 Push the CLOCK key to see its duration and use the UP and DOWN keys to set it 8 Confirm the value by pushing again th...

Страница 6: ...nd modify target humidity set point SET RH of the running SH1 phase in programming mode it selects a parameter or confirm an operation In programming mode it browses the parameter codes or increases t...

Страница 7: ...con starts flashing 2 To change the Set value push the o or n arrows within 10s 3 To memorise the new set point value push the SET key again or wait 10s 8 3 TO START A MANUAL DEFROST 1 Push the DEF ke...

Страница 8: ...MP dbt value and disabled when the SET TEMP is reached dbH half dead band width for humidity 0 5 25 5RH this band is place below and above the humidity set point SET RH The dehumidifying action is ena...

Страница 9: ...e alarm setting ALC rE 0 50 C or 90 F ALC Ab 50 C or 58 F ALU when this temperature is reached and after the ALd delay time the LA alarm is enabled ALU High temperature alarm setting ALC rE 0 50 C or...

Страница 10: ...dEF defrost relay Adt RS485 serial address for temperature loads 0 247 identifies the instrument within a control or supervising system AdH RS485 serial address for humidity loads 0 247 identifies the...

Страница 11: ...s on the i1P parameters CL the digital input is activated by closing the contact OP the digital input is activated by opening the contact 11 INSTALLATION AND MOUNTING The temperature range allowed for...

Страница 12: ...s or pipepresses using the centres signed in the bottom cover of the Cool Mate Fig 3 H I Then make 3 holes in the wall as indicated in Fig 3 L M N to fix the Cool Mate 4 Fix the cablepresses and the p...

Страница 13: ...supply complies with the instrument s requirements Separate the probe cables from the power supply cables from the outputs and the power connections Do not exceed the maximum current allowed on each r...

Страница 14: ...he probe Temperature alarms HA and LA automatically stop as soon as the thermostat temperature returns to normal values or when the defrost starts Humidity alarms HHA and LHA automatically stop as soo...

Страница 15: ...cF C Pr2 Measurement unit C F rES dE Pr2 Resolution for C in integer dE decimal rEH Hd Pr2 Resolution for RH in integer Hd half digit trC co Pr2 Instrument behaviour at the end of the cycle co start h...

Страница 16: ...o3 0 0 Pr1 Humidity probe calibration 10 10 P2P YES Pr2 Evaporator probe presence no absent YES present P3P YES Pr2 Humidity probe presence no absent YES present Lci 0 0 Pr2 Readout with 4 mA 999 999...

Отзывы: