Operating Instructions 

cod. 1592017410 

 

1592017410  XLH360 GB r1.0  15.04.2005.doc 

XLH360 

3/16 

1.

 

GENERAL WARNING 

1.1

 

PLEASE READ BEFORE USING THIS MANUAL 

 

This manual is part of the product and should be kept near the instrument for easy and quick reference. 

 

The instrument shall not be used for purposes different from those described hereunder. It cannot be used as a safety device. 

 

Check the application limits before proceeding. 

1.2

 

 SAFETY PRECAUTIONS 

 

Check the supply voltage is correct before connecting the instrument. 

 

Do not expose to water or moisture: use the controller only within the operating limits avoiding sudden temperature changes with high 
atmospheric humidity to prevent  formation of condensation 

 

Warning: disconnect all electrical connections before any kind of maintenance. 

 

Fit the probe where it is not accessible by the End User. The instrument must not be opened. 

 

In case of failure or faulty operation send the instrument back to the distributor or to “Dixell s.r.l.” (see address) with a detailed description of 
the fault. 

 

Consider the maximum current which can be applied to each relay (see Technical Data). 

 

Ensure that the wires for probes, loads and the power supply are separated and far enough from each other, without crossing or intertwining. 

 

In case of applications in industrial environments, the use of mains filters (our mod. FT1) in parallel with inductive loads could be useful. 

2.

 

GENERAL DESCRIPTION 

The 

XLH360

 is microprocessor controller, suitable for applications on medium or low temperature refrigerating units. It has 6 output relays to 

control compressor, heating elements, defrost/extractor fan, fan, de-humidifier/light and humidifier. It has 2 NTC inputs one for thermostat the other 
one for defrost. It’s also present a 4÷20mA input for humidity. There is one digital input (free contact) configurable by parameter. An  output allows 
the user to program the parameter list with the 

“Hot Key”.

 

3.

 

TEMPERATURE REGULATION 

The temperature regulation is performed through neutral zone using compressor and heater output relays. 

Set point

OFF

ON

 

• 

Heating

 output: CUT IN is “SET TEMP-dbt”, CUT OUT is when the temperature reaches the set point. 

• 

Compressor

 output CUT IN is “ SET TEMP +dbt”, CUT OUT is when the temperature reaches the set point. 

3.1

 

DEFROST  

During defrost the temperature control is disabled. 

 

If the second relay is configured as defrost: oA2=dEF

 then two defrost modes are available through the “

tdF

” parameter: defrost with electrical 

heater (tdF=rE) or hot gas (tdF= in). The defrost interval is control by means of parameter “

EdF

”: (EdF=in) the defrost is made every “

IdF

” time, 

(EdF=Sd) the interval “IdF” is calculate through Smart Defrost algorithm (only when the compressor is ON). At the end of defrost dripping time is 
started, set by “

Fdt

” parameter. To 

disable 

the defrost set the 

MdF

 parameter to 

zero

 

 

If  oA2 is different from dEF, defrost is made only by stopping compressor  (tdF=rE). 
To disable 

 defrosts set 

MdF=0. 

 

Humidity regulation during defrost depends on the 

Hud 

parameter. 

With  

Hud=no

 humidity regulation is disabled.  

Con 

Hud=yES

 humidity regulation is performed also during defrost. 

 

4.

 

HUMIDITY REGULATION 

The humidity regulation is performed through neutral zone, by humidifying dehumidifying actions. 
Humidity control can be disabled setting the 

SET %RH to “nu”

 value. In this case only the temperature control is perform. 

4.1

 

HUMIDIFYING ACTION 

The humidifying action is done enabling the humidifier relay when the humidity is lower than the “SET %RH-dbH” value. 
The relay is switch off when humidity reaches the set values. 

Содержание COOL MATE XLH360

Страница 1: ...XEL Operating Instructions cod 1592017410 1592017410 XLH360 GB r1 0 15 04 2005 doc XLH360 1 16 Temperature and humidity controller for seasoning maturing cabinets XLH360 COOL MATE Operating Instructio...

Страница 2: ...SPLAY________________________________________________________________ 6 9 PARAMETER LIST ____________________________________________________________ 8 10 DIGITAL INPUT _______________________________...

Страница 3: ...It has 2 NTC inputs one for thermostat the other one for defrost It s also present a 4 20mA input for humidity There is one digital input free contact configurable by parameter An output allows the u...

Страница 4: ...ay By setting the parameter tHu db the de humidifying action is performed by enabling the de humidifier relay when the humidity is higher than SET RH dbH The relay is switch off when humidity comes ba...

Страница 5: ...time and pass to the setting of the stopping phase the oFF message is displayed 7 Push the CLOCK key to see its duration and use the UP and DOWN keys to set it 8 Confirm the value by pushing again th...

Страница 6: ...nd modify target humidity set point SET RH of the running SH1 phase in programming mode it selects a parameter or confirm an operation In programming mode it browses the parameter codes or increases t...

Страница 7: ...con starts flashing 2 To change the Set value push the o or n arrows within 10s 3 To memorise the new set point value push the SET key again or wait 10s 8 3 TO START A MANUAL DEFROST 1 Push the DEF ke...

Страница 8: ...MP dbt value and disabled when the SET TEMP is reached dbH half dead band width for humidity 0 5 25 5RH this band is place below and above the humidity set point SET RH The dehumidifying action is ena...

Страница 9: ...e alarm setting ALC rE 0 50 C or 90 F ALC Ab 50 C or 58 F ALU when this temperature is reached and after the ALd delay time the LA alarm is enabled ALU High temperature alarm setting ALC rE 0 50 C or...

Страница 10: ...dEF defrost relay Adt RS485 serial address for temperature loads 0 247 identifies the instrument within a control or supervising system AdH RS485 serial address for humidity loads 0 247 identifies the...

Страница 11: ...s on the i1P parameters CL the digital input is activated by closing the contact OP the digital input is activated by opening the contact 11 INSTALLATION AND MOUNTING The temperature range allowed for...

Страница 12: ...s or pipepresses using the centres signed in the bottom cover of the Cool Mate Fig 3 H I Then make 3 holes in the wall as indicated in Fig 3 L M N to fix the Cool Mate 4 Fix the cablepresses and the p...

Страница 13: ...supply complies with the instrument s requirements Separate the probe cables from the power supply cables from the outputs and the power connections Do not exceed the maximum current allowed on each r...

Страница 14: ...he probe Temperature alarms HA and LA automatically stop as soon as the thermostat temperature returns to normal values or when the defrost starts Humidity alarms HHA and LHA automatically stop as soo...

Страница 15: ...cF C Pr2 Measurement unit C F rES dE Pr2 Resolution for C in integer dE decimal rEH Hd Pr2 Resolution for RH in integer Hd half digit trC co Pr2 Instrument behaviour at the end of the cycle co start h...

Страница 16: ...o3 0 0 Pr1 Humidity probe calibration 10 10 P2P YES Pr2 Evaporator probe presence no absent YES present P3P YES Pr2 Humidity probe presence no absent YES present Lci 0 0 Pr2 Readout with 4 mA 999 999...

Отзывы: