XLH360 

8/16 

Another possibility

 is the following: after switching ON the instrument the user can push 

SET %RH

 + 

n

 keys within 30 seconds. 

 

NOTE

: each parameter in “Pr2” can be removed or put into “Pr1” (user level) by pressing 

SET %RH

 + 

n

. When a parameter is present in “Pr1” 

 icon is on. 

8.7

 

TO CHANGE PARAMETER VALUES 

1.

 

Enter the Programming mode. 

2.

 

Select the required parameter with 

o

 or 

n

3.

 

Press the “

 SET %RH

 ” key to display its value (°C or °F icon start blinking). 

4.

 

Use 

o

 or 

n

 to change its value. 

5.

 

Press “

 SET %RH

 ” to store the new value and move to the following parameter. 

To exit

: Press 

SET %RH

 

+ UP 

or wait 15s without pressing a key. 

NOTE

: the new programming is stored even when the procedure is exited by waiting the time-out. 

8.8

 

HOW TO LOCK THE KEYBOARD 

 
 

 

 

1.  

Keep the 

o

 and 

n

 keys pressed together for more than 3 s the 

o

 and 

n

 keys. 

2.  

The “

POF

” message will be displayed and the keyboard is locked. At this point it is 

only possible the viewing of the set point or the MAX o Min temperature stored and 
to switch ON and OFF the light, the auxiliary output and the instrument. 

 

TO UNLOCK THE KEYBOARD 

Keep the 

o

 and 

n

 keys pressed together for more than 3s. 

 

8.9

 

ON/OFF FUNCTION 

 

By pushing the 

ON/OFF

 key, the instrument shows “OFF” for 5 sec. and the ON/OFF 

LED 
 is switched ON. 
During the OFF status, all the relays are switched OFF and the regulations are stopped;  

N.B. During the OFF status the 

  icon is lighted. 

 

9.

 

PARAMETER LIST 

REGULATION 

dbt

  half dead band width for temperature:

 (0,1÷25,5°C; 1÷45°F) this band is place below and above the temperature set point (SET 

TEMP). The compressor is enabled when the temperature increases and reaches the SET TEMP + dbt value. It is turned off when it 
comes back to the SET TEMP. The heating output is enabled when temperature is less than SET TEMP -dbt value and disabled when the 
SET TEMP is reached.

 

dbH

  half dead band width for humidity:

 (0,5÷25,5RH) this band is place below and above the humidity set point (SET %RH). The 

dehumidifying action is enabled when the humidity increases and reaches the SET %RH + dbH value. It is stopped when it comes back to 
the SET %RH. The humidifying  output is enabled when humidity is less than SET %RH -dbH value and disabled when the SET %RH is 
reached.

 

LS 

Minimum temperature set point limit: 

(-50,0°C

÷

SET; -58°F÷SET) Sets the minimum acceptable value for the set point. 

US 

Maximum temperature set point limit: 

(SET

÷

110°C; SET÷230°F) Set the maximum acceptable value for set point. 

OdS  Outputs activation delay at start up:

 (0÷255 min) This function is enabled at the initial start up of the instrument and inhibits any output 

activation for the period of time set in the parameter. (Light can work) 

AC 

Anti-short cycle delay: 

(0÷30 min) interval between the compressor stop and the following restart. 

tHu 

Kind of de-humidifying: db

: only with de-humidifier relay (oA1= dEH); 

cHu

 with de-humidifier and compressor relay (oA1= dEH); 

c-H: 

without de-humidifier relay, by means of compressor and heating relays

 

(oA1

 dEH)

LSH 

Minimum humidity set point limit: 

(

Lci ÷ Set H

) Sets the minimum acceptable value for the humidity set point. 

uSH 

Maximum humidity set point limit: 

(

Set H ÷ uci

) Set the maximum acceptable value for humidity set point. 

 

DISPLAY AND KIND OF REGULATION 
CF 

Measurement unit: °C

= Celsius; 

°F

= Fahrenheit 

rES 

Resolution (for °C)

: allows decimal point display. 

dE

 = 0,1°C; 

in

 = 1 °C  

rEH 

Resolution for RH%:

 in = integer; Hd= half digit. 

trC 

Kind of behaviour after the end of the cycle 

 trC=co 

the controller goes on working, and maintains the temperature and humidity of the running phase, till the controller is stopped. 

 trC=in 

at the end of the stopping phase the controller gives the “End” message, the buzzer is turned on, and the regulation is stopped. 

 trC=cL 

at the end of the stopping phase the controller gives the “End” message, the buzzer is turned on, and the regulation restarts from 

the running phase 

Содержание COOL MATE XLH360

Страница 1: ...XEL Operating Instructions cod 1592017410 1592017410 XLH360 GB r1 0 15 04 2005 doc XLH360 1 16 Temperature and humidity controller for seasoning maturing cabinets XLH360 COOL MATE Operating Instructio...

Страница 2: ...SPLAY________________________________________________________________ 6 9 PARAMETER LIST ____________________________________________________________ 8 10 DIGITAL INPUT _______________________________...

Страница 3: ...It has 2 NTC inputs one for thermostat the other one for defrost It s also present a 4 20mA input for humidity There is one digital input free contact configurable by parameter An output allows the u...

Страница 4: ...ay By setting the parameter tHu db the de humidifying action is performed by enabling the de humidifier relay when the humidity is higher than SET RH dbH The relay is switch off when humidity comes ba...

Страница 5: ...time and pass to the setting of the stopping phase the oFF message is displayed 7 Push the CLOCK key to see its duration and use the UP and DOWN keys to set it 8 Confirm the value by pushing again th...

Страница 6: ...nd modify target humidity set point SET RH of the running SH1 phase in programming mode it selects a parameter or confirm an operation In programming mode it browses the parameter codes or increases t...

Страница 7: ...con starts flashing 2 To change the Set value push the o or n arrows within 10s 3 To memorise the new set point value push the SET key again or wait 10s 8 3 TO START A MANUAL DEFROST 1 Push the DEF ke...

Страница 8: ...MP dbt value and disabled when the SET TEMP is reached dbH half dead band width for humidity 0 5 25 5RH this band is place below and above the humidity set point SET RH The dehumidifying action is ena...

Страница 9: ...e alarm setting ALC rE 0 50 C or 90 F ALC Ab 50 C or 58 F ALU when this temperature is reached and after the ALd delay time the LA alarm is enabled ALU High temperature alarm setting ALC rE 0 50 C or...

Страница 10: ...dEF defrost relay Adt RS485 serial address for temperature loads 0 247 identifies the instrument within a control or supervising system AdH RS485 serial address for humidity loads 0 247 identifies the...

Страница 11: ...s on the i1P parameters CL the digital input is activated by closing the contact OP the digital input is activated by opening the contact 11 INSTALLATION AND MOUNTING The temperature range allowed for...

Страница 12: ...s or pipepresses using the centres signed in the bottom cover of the Cool Mate Fig 3 H I Then make 3 holes in the wall as indicated in Fig 3 L M N to fix the Cool Mate 4 Fix the cablepresses and the p...

Страница 13: ...supply complies with the instrument s requirements Separate the probe cables from the power supply cables from the outputs and the power connections Do not exceed the maximum current allowed on each r...

Страница 14: ...he probe Temperature alarms HA and LA automatically stop as soon as the thermostat temperature returns to normal values or when the defrost starts Humidity alarms HHA and LHA automatically stop as soo...

Страница 15: ...cF C Pr2 Measurement unit C F rES dE Pr2 Resolution for C in integer dE decimal rEH Hd Pr2 Resolution for RH in integer Hd half digit trC co Pr2 Instrument behaviour at the end of the cycle co start h...

Страница 16: ...o3 0 0 Pr1 Humidity probe calibration 10 10 P2P YES Pr2 Evaporator probe presence no absent YES present P3P YES Pr2 Humidity probe presence no absent YES present Lci 0 0 Pr2 Readout with 4 mA 999 999...

Отзывы: