dIXEL

 

Operating Instructions 

cod. 1592017410 

 

1592017410  XLH360 GB r1.0  15.04.2005.doc 

XLH360 

10/16 

PROBE INPUTS 
Ot 

Thermostat probe calibration: 

(-12.0

÷

12.0°C/ -21

÷

21°F) allows to adjust possible offset of the thermostat probe. 

OE   

Evaporator probe calibration: 

(-12.0

÷

12.0°C/ -21

÷

21°F) allows to adjust possible offsets of the evaporator probe. 

O3   

Humidity probe calibration: 

(-10

÷

10 RH) allows to adjust possible offsets of the humidity probe. 

P2P 

Evaporator probe presence: n

= not present: the defrost stops only by time; 

y=

 present: the defrost stops by temperature and time. 

P3P 

Humidity probe presence: n

= not present; 

y=

 present. 

LCI  

Readout with 4 mA

 : (-999 ÷ 999). Adjustment of  read out corresponding to 4mA signal. 

UCI  

Readout with 20 mA

 : (-999 ÷ 999). Adjustment of  read out corresponding to 20mA signal. 

  

 

DIGITAL INPUTS 
i1P 

Configurable digital input polarity: CL

 : the digital input is activated by closing the contact;  

OP

 : the digital input is activated by 

opening the contact; 

i1P 

Door switch digital input polarity: CL

 : the digital input is activated by closing the contact;  

OP

 : the digital input is activated by 

opening the contact 

i1F 

Digital input operating mode:

 configure the digital input function: 

 EAL 

= generic alarm; 

bAL 

= serious alarm mode; 

PAL 

= Pressure 

switch; 

 Ht 

= heating relay safety; 

dor

 = door switch

 

odc 

Outputs status when open door:

 

on

 = normal; 

Fan

 = Fan OFF; 

oFF

 = all the loads off  

rrd 

Outputs restarting after doA alarm: no = 

outputs not affected by the doA alarm;  

yES = 

outputs restart with the doA alarm;  

did  

Time interval/delay for digital input alarm:

(0

÷

255 min.) Time interval to calculate the number of the pressure switch activation when 

I1F=PAL. If I1F=EAL or bAL (external alarms), “did” parameter defines the time delay between the detection and the successive signalling 
of alarms. 

OTHER 
oA1

 

Light relay configuration

ALr 

= alarm; 

dEH 

= dehumidifier; 

onF 

= on/off relay: close with instrument on, open with instrument off; 

Lig 

light, 

ESt, dEF not select

 

oA2 

Configuration of the defrost / extractor fans relay dEH = not select; onF = 

on/off relay: close with instrument on; open with instrument 

on; 

Lig =Light 

ESt 

= extractor fan

; dEF = 

defrost relay. 

Adt 

RS485 serial address for temperature loads 

(0÷247) identifies the instrument within a control or supervising system.

 

AdH  RS485 serial address for humidity loads 

(0÷247) identifies the instrument within a control or supervising system.

 

Ptb  

Parameter table:

 (read only) it shows the original code of the 

dIXEL

 parameter map. 

rEL  

Software release:

 (read only) Software version of the microprocessor. 

Prd    Probes display: 

(read only) display the temperature values of the evaporator probe Pb2. 

Pr2  

Access to the protected parameter list 

(read only). 

10.

 

DIGITAL INPUT 

One digital input is present configurable by user by means of the i1F parameter according to the following descriptions.  

10.1

 

DOOR SWITCH (I1F = dor) 

It signals the door status and the corresponding relay output status through the “

odc

” parameter: 

no

 = normal (any change); 

Fan

 = Fan OFF; 

oFF

 

= all the loads are switched off. 

 

Since the door is opened, after the delay time set through parameter “

dOA

”, the alarm output is enabled and the display shows the message “

dA

”.  

The status of loads depends on the “

rrd” 

parameter:  

with 

rrd=no 

outputs are not affected by the doA alarm;  

with 

rrd=yES = 

outputs restart with the doA alarm; 

The alarm stops as soon as the external digital input is disabled again. During this time and then for the delay “

dot

” and 

“doH” 

after closing the 

door, the temperature and humidity alarms are disabled. 

10.2

 

GENERIC ALARM (I1F = EAL) 

As soon as the digital input is activated the unit will wait for “

did

” time delay before signalling the “

EAL

” alarm message. The outputs status don’t 

change. The alarm stops just after the digital input is de-activated. 

10.3

 

SERIOUS ALARM MODE (I1F = BAL) 

When the digital input is activated, the unit will wait for “

did

” delay before signalling the “

bAL

” alarm message. The relay outputs are switched OFF. 

The alarm will stop as soon as the digital input is de-activated. 

10.4

 

PRESSURE SWITCH (I1F = PAL) 

If during the interval time set by “

did

” parameter, the pressure switch has reached the number of activation of  the “

nPS

” parameter, the “

PAL

” 

pressure alarm message will be displayed. The compressor and the regulation are stopped. When the digital input is ON the compressor is always 
OFF. 

If the nPS activation in the did time is reached, switch off and on the instrument to restart normal regulation. 

Содержание COOL MATE XLH360

Страница 1: ...XEL Operating Instructions cod 1592017410 1592017410 XLH360 GB r1 0 15 04 2005 doc XLH360 1 16 Temperature and humidity controller for seasoning maturing cabinets XLH360 COOL MATE Operating Instructio...

Страница 2: ...SPLAY________________________________________________________________ 6 9 PARAMETER LIST ____________________________________________________________ 8 10 DIGITAL INPUT _______________________________...

Страница 3: ...It has 2 NTC inputs one for thermostat the other one for defrost It s also present a 4 20mA input for humidity There is one digital input free contact configurable by parameter An output allows the u...

Страница 4: ...ay By setting the parameter tHu db the de humidifying action is performed by enabling the de humidifier relay when the humidity is higher than SET RH dbH The relay is switch off when humidity comes ba...

Страница 5: ...time and pass to the setting of the stopping phase the oFF message is displayed 7 Push the CLOCK key to see its duration and use the UP and DOWN keys to set it 8 Confirm the value by pushing again th...

Страница 6: ...nd modify target humidity set point SET RH of the running SH1 phase in programming mode it selects a parameter or confirm an operation In programming mode it browses the parameter codes or increases t...

Страница 7: ...con starts flashing 2 To change the Set value push the o or n arrows within 10s 3 To memorise the new set point value push the SET key again or wait 10s 8 3 TO START A MANUAL DEFROST 1 Push the DEF ke...

Страница 8: ...MP dbt value and disabled when the SET TEMP is reached dbH half dead band width for humidity 0 5 25 5RH this band is place below and above the humidity set point SET RH The dehumidifying action is ena...

Страница 9: ...e alarm setting ALC rE 0 50 C or 90 F ALC Ab 50 C or 58 F ALU when this temperature is reached and after the ALd delay time the LA alarm is enabled ALU High temperature alarm setting ALC rE 0 50 C or...

Страница 10: ...dEF defrost relay Adt RS485 serial address for temperature loads 0 247 identifies the instrument within a control or supervising system AdH RS485 serial address for humidity loads 0 247 identifies the...

Страница 11: ...s on the i1P parameters CL the digital input is activated by closing the contact OP the digital input is activated by opening the contact 11 INSTALLATION AND MOUNTING The temperature range allowed for...

Страница 12: ...s or pipepresses using the centres signed in the bottom cover of the Cool Mate Fig 3 H I Then make 3 holes in the wall as indicated in Fig 3 L M N to fix the Cool Mate 4 Fix the cablepresses and the p...

Страница 13: ...supply complies with the instrument s requirements Separate the probe cables from the power supply cables from the outputs and the power connections Do not exceed the maximum current allowed on each r...

Страница 14: ...he probe Temperature alarms HA and LA automatically stop as soon as the thermostat temperature returns to normal values or when the defrost starts Humidity alarms HHA and LHA automatically stop as soo...

Страница 15: ...cF C Pr2 Measurement unit C F rES dE Pr2 Resolution for C in integer dE decimal rEH Hd Pr2 Resolution for RH in integer Hd half digit trC co Pr2 Instrument behaviour at the end of the cycle co start h...

Страница 16: ...o3 0 0 Pr1 Humidity probe calibration 10 10 P2P YES Pr2 Evaporator probe presence no absent YES present P3P YES Pr2 Humidity probe presence no absent YES present Lci 0 0 Pr2 Readout with 4 mA 999 999...

Отзывы: