43
Optimized layout for A4 print.
A
D
B
E
C
F
9.94
9.98
10.00
i
Kg
mA / V
Kg
mA / V
Kg
mA / V
Kg
mA / V
USER_MAN_ENG_DGT1SX
LEGEND:
Indicates repeated pressing of
the key.
Parameter visible only
under certain conditions.
Parameter or menu subject
to approval.
Default value of the parameter.
Voltage output
63300
~
10 V
0
~
0 V
Current output
58200
~
20 mA
0
~
0 mA
Example:
Increase
ao 10v
from 63300
to 63550.
CALIBRATION PROCEDURE:
Connect a multimeter to the transmitter.
Enter the parameter to be changed:
ao 0v
/
ao 10v
/
ao 0ma
/
ao.20ma
and set an approximate value.
Increase or decrease the D/A points
value to reach the desired output.
100 D/A points
~
0.015 V - 0.035 mA
1000 D/A points
~
0.15 V - 0.35 mA
Press to update the output value on
the multimeter.
Press to update the output value on
the multimeter.
Repeat the procedure from point “
C
C
”
until the desired value is reached, then
press to save.
Save the changes (press the
C
key
several times until you reach the
message
save?
, then press the
key to confirm).
Positive weight operation
Negative weight operation
ANALOG OUTPUT GRAPHS:
Voltage or current operation is determined by the connection to the transmitter terminals:
Current: 9 (+) and 10 (-).
Voltage: 11 (+) and 12 (-).
Содержание DGT1SX
Страница 1: ...www diniargeo com DGT1SX High speed digital weight transmitter ENGLISH USER MANUAL...
Страница 2: ......
Страница 6: ...6 Optimized layout for A4 print USER_MAN_ENG_DGT1SX...
Страница 57: ...57 Optimized layout for A4 print USER_MAN_ENG_DGT1SX Notes...
Страница 58: ...58 Optimized layout for A4 print USER_MAN_ENG_DGT1SX Notes...
Страница 59: ......