EN-4 452235.66.09 · FD 9209
www.dimplex.de
English
WI 10TU - WI 22TU
4 Accessories
4.1 Remote control
A remote control adds convenience and is available as a special
accessory. Operation and menu navigation are identical to those
of the heat pump manager. Connection is made using a 6-core
telephone cable (special accessory) with modular plugs.
NOTE
In the case of heating controllers with a removable operating element,
this can also be used directly as a remote control.
4.2 Building management
technology
The heat pump manager can be connected to a building man-
agement system network via supplementation of the relevant in-
terface plug-in card. The supplementary installation instructions
of the interface card must be consulted regarding the exact con-
nection and parameterisation of the interface.
The following network connections can be made on the heat
pump manager:
Modbus
EIB, KNX
Ethernet
ATTENTION!
If the heat pump or circulating pumps are controlled externally, an
additional flow rate switch is required to prevent the compressor from
being switched on when there is no volume flow.
5 Transport
A lift truck is suited for transporting the unit on a level surface.
Carrying straps may be used if the heat pump needs to be trans-
ported on an uneven surface or carried up or down stairs. These
straps can be passed directly underneath the pallet.
ATTENTION!
The heat pump is not fixed to the pallet.
ATTENTION!
The heat pump must not be tilted more than 45° (in any direction).
Use the holes provided in the sides of the frame to lift the unit
without the pallet. The side panel assemblies must be removed
for this purpose. Any commercially available length of pipe can
be used as a carrying aid.
ATTENTION!
Do not use the holes in the panel assemblies for lifting the device!
After the transport, the transport securing device is to be re-
moved.
ATTENTION!
The transport securing device is to be removed prior to commissioning.
6 Set-up
6.1 General Information
The compact water-to-water heat pump must be installed in a
frost-free, dry room on an even, smooth and horizontal surface.
The entire base of the frame should lie directly on the floor to en-
sure an adequate soundproof seal. If supporting feet are used,
the heat pump must be installed horizontally. In this case, the
specified sound level can be up to
3 dB(A) higher, and additional sound insulation measures may
be necessary..
The heat pump must be installed so that maintenance work can
be carried out without hindrance. This can be ensured by main-
taining a clearance of approx. 1 m in front of and on each side of
the heat pump.
Neither frost nor temperatures higher than 35 °C must occur in
the installation location at any time of the year.
6.2 Acoustic Emissions
The heat pump operates silently due to efficient sound insulation.
Internal insulation measures should be carried out to prevent vi-
brations from being transmitted to the foundation or to the heat-
ing system.
5HPRYH
WUDQVSRUWORFN
Содержание I 22TU
Страница 2: ......
Страница 14: ...DE 12 452235 66 09 FD 9209 www dimplex de Deutsch WI 10TU WI 22TU...
Страница 36: ...FR 12 452235 66 09 FD 9209 www dimplex de Fran ais WI 10TU WI 22TU...
Страница 47: ...www dimplex de 452235 66 09 FD 9209 A XI Anhang Appendix Annexes WI 10TU WI 22TU 3 2 Steuerung Control Commande...
Страница 48: ...A XII 452235 66 09 FD 9209 www dimplex de Anhang Appendix Annexes WI 10TU WI 22TU 3 3 Last Load Charge...
Страница 57: ...www dimplex de 452235 66 09 FD 9209 A XXI Anhang Appendix Annexes WI 10TU WI 22TU...
Страница 58: ...A XXII 452235 66 09 FD 9209 www dimplex de Anhang Appendix Annexes WI 10TU WI 22TU...
Страница 59: ...www dimplex de 452235 66 09 FD 9209 A XXIII Anhang Appendix Annexes WI 10TU WI 22TU...