Error messages
Deutschmann Automation GmbH & Co. KG
46
Instruction manual LOCON 7, LOCON 9 V. 10.4
24.5.04
11.4 Error number 200-299
The following errors occur only on terminals (or if using cam controls of the LOCON 24, 48, 64
series as a terminal)
Error No. Significance
Remarks
201
Self-test error
202
Internal error
206
Error initializing the RS485 interface
207
RS232 error
210
RX overflow error
211
TX overflow error
212
TX change ID error
213
Time-out accessing LCD
Acknowledge the error. If the error occurs again, the unit
must be returned, specifying the information described
in chapter ‘Returning a unit’
214
Undefined field error
215
Get key error
216
LCD XY error
220
Time-out connecting to cam control
221
Incorrect data record on transmission
to cam control
222
Checksum error on reception from
cam control
223
Checksum error on transmission to
cam control
224
Unknown command on transmission
to cam control
230
Incorrect configuration data record or
not possible to configure the cam
control
231
Incorrect initialisation data record
240
DICNET® transmit error
241
DICNET® receive error
242
Duplicate device number in DIC-
NET® or connection problems
Assign a different device number.
Check for cable discontinuity, short circuit, non-twisted
cable....
243
Too many terminals in network (max.
3 allowed)
Reduce to 3 terminals
244
Max. 1 external terminal in the case
of multiple-axis version of the
LOCON 32
251
Internal error
252
CMD UNKNOWN ERROR
253
CMD CHECKSUM ERROR