 10

 

 

 

CAUTION

 

Low flue gas temperature increases the risk of 
condensation. Adjust the total flue gas temperature 
at or higher then 204°C (400°F) in order for the heat 
exchanger warranty to remain in force. 

3.3.5 

 

O

VERFIRE PRESSURE TEST

 

 The overfire draft that is taken through the observation port, 
located above the burner, is a measurement necessary to 
determine if there is a blockage in the heat exchanger or the 
flue pipe. Refer to the Technical Specifications in this manual 
for overfire pressure values. A high pressure condition may be 
caused by excessive combustion air, due to the air band being 
too wide open, or a lack of flue draft (chimney effect) or some 
other blockage, such as soot in the secondary section of the 
heat exchanger or the use of an oversize nozzle input or high 
pressure pump. 

3.3.6 

V

ENT 

T

EMPERATURE 

T

EST 

 

1. 

After having adjusted the burner combustion, insert a 
thermometer into the test hole in the breech pipe; 

2. 

The total vent temperature should be between 204 and 
302°C (400 and 575°F). If not, check for improper air 
temperature rise, pump pressure, nozzle size or a badly 
sooted heat exchanger.  Also refer to section 2.5 for 
proper flue pipe sizing. 

 

3.3.7 

S

UPPLY AIR 

T

EMPERATURE 

R

ISE 

T

EST

 

1.  Operate the burner for at least 10 minutes; 
2.  Measure the air temperature in the return air plenum; 
3.  Measuring the air temperature in the largest trunk coming 

off the supply air plenum, just outside the range of radiant 
heat from the heat exchanger. 0.3 m (12") from the 
plenum of the main take-off is usually sufficient; 

4.  The temperature rise is calculated by subtracting the 

return air temperature from the supply air temperature; 

5.  If the temperature rise is lower or exceeds the 

temperature specified in Table 1, p. 13, change to the next 
lower or higher blower speed tap, until the temperature 
rise falls to the target. If the excessive temperature rise 
cannot be increased or reduced by changing fan speed, 
investigate for ductwork obstructions, dirty or improper air 
filter, improper firing caused by improper pump pressure 
or nozzle sizing. 

3.3.8 

L

IMIT 

C

ONTROL 

C

HECK

 

After operating the furnace for at least 15 minutes, restrict the 
return air supply by blocking the filters or the return air register 
and allow the furnace to shut off on High Limit. The burner will 
shut off but the blower will continue to run. 

 

Remove the obstruction and the burner should restart after a 
few minutes. The time required for the restart also depends on 
the adjustment of the blower “OFF” delay. 

3.3.9 

R

ESTART AFTER BURNER FAILURE

 

1.  Set the thermostat lower than room temperature; 
2.  Press the reset button on the burner primary control 

(relay) 

3.  Set the thermostat higher than room temperature; 
4.  If the burner motor does not start or ignition fails, turn 

off the disconnect switch and CALL A QUALIFIED 
SERVICE TECHNICIAN. 

CAUTION

 

Do not attempt to start the burner when excess oil has 
accumulated, when the furnace is full of vapour or when 
the combustion chamber is hot. 

 

4 MAINTENANCE 

WARNING 

 

Electrical shock hazard. 

 

Turn OFF power and fuel to the furnace before any 
disassembly or servicing. 

 

Failure to do so can result in death, bodily injury 
and/or property damage.

 

 

Preventive maintenance is the best way to avoid 
unnecessary expense and inconvenience. Have your 
heating system and burner inspected by a qualified 
service technician at regular intervals.  

 

To maintain the reliability and optimal performance of the 
furnace, have a complete combustion check done after 
the annual maintenance call. Do not attempt to repair the 
furnace or its controls. Call a qualified service technician. 
 

Before calling for repair service check the following points: 

1.  Check the oil tank gauge and make sure that the 

valve is open; 

2.  Check fuses and the circuit breaker; 

3.  Check if the main disconnect switch is ON ; 

4.  Set the thermostat above room temperature; 

5.  If ignition does not occur, turn off the disconnect 

switch and call a qualified service technician. 

 

When ordering replacement parts, please specify the 
complete furnace model number and serial number. 

Содержание AMT098SD

Страница 1: ...Attention Do not tamper with the unit or its controls Call a qualified service technician INSTALLER SERVICE TECHNICIAN Use the information in this manual for the installation servicing of the furnace...

Страница 2: ...JUSTMENTS HEATING MODE 4 SPEED MOTOR 7 TABLE 2 BLOWER SPEED ADJUSTMENTS A C MODE 4 SPEED MOTOR 7 TABLE 3 HEATING MODE 8 TABLE 4 AIR CONDITIONING MODE 8 TABLE 5 CFM ADJUSTMENT ALL MODES 8 TABLE 6 DELAY...

Страница 3: ...formation such as the model and serial numbers of the furnace WARNING Installations and repairs performed by unqualified persons can result in hazards to them and to others Installations must conform...

Страница 4: ...so be located close to the centre of the air distribution system 2 1 1 INSTALLATION IN AN ENCLOSURE The unit can be installed in an enclosure such as a closet However 2 ventilation openings are requir...

Страница 5: ...nozzle sizes by working back from the desired flow rate at operating pressure and not the nozzle marking 2 5 2 AIR AND TURBULATOR SETTINGS Before starting the burner for the first time adjust the air...

Страница 6: ...k that the electrical outlet on the furnace designated to the BVSO is functional 1 Start up the burner 2 Remove the three pole plug from the BVSO outlet on the furnace 3 The burner must shut off immed...

Страница 7: ...led to the furnace casing Failure to properly seal ducts can result in death bodily injury and or property damage The ducting must be designed and installed according to approved methods local and nat...

Страница 8: ...24 VAC signal can also be supplied from the W and C terminals on the blower electronic board to activate a switching relay Also refer to the instructions supplied with the accessory 2 12 2 ELECTRONIC...

Страница 9: ...of the oil piping and pump Slowly close and tighten the bleed screw Once closed the flame will light up 3 3 2 PRESSURE ADJUSTMENT The oil pressure must be adjusted according to the Technical Specifica...

Страница 10: ...ed investigate for ductwork obstructions dirty or improper air filter improper firing caused by improper pump pressure or nozzle sizing 3 3 8 LIMIT CONTROL CHECK After operating the furnace for at lea...

Страница 11: ...bly cover 3 Remove the cover 4 Remove the two screws holding the control box to the heat transfer tube assembly Sliding the control box in the appropriate direction will unlock it from the heat transf...

Страница 12: ...vice telephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure lb po 2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Am...

Страница 13: ...stion air adjustment turbulator damper 0 3 5 1 5 25 0 3 5 1 5 25 Minimum and Maximum pump pressure PSIG 125 to 180 135 to 170 125 to 180 135 to 170 AFUE From CSA B212 standard and Canadian regulation...

Страница 14: ...c 13 60 sec 38 3 min D 1 ON 2 ON All 13 30 sec 100 0 sec 100 2 min No adjustment required A C size PreRun On Delay CFM Level Time ShortRun On Delay CFM Level Time Off Delay CFM Level Time All No Delay...

Страница 15: ...E XTE RNAL STATIC P RE SSURE WITH AIR FILTE R Table 10 Minimum clearances from combustible material LOCATION APP LICATION CLEARANCE S combustible ma terials RECOMMANDED ACCES S FO R SERVICE FURNACE 1...

Страница 16: ...16 Figure 7 Furnace Dimensions...

Страница 17: ...17 Figure 8 Wiring Diagram 4 Speed Motor PSC...

Страница 18: ...18 Figure 9 Wiring Diagram Variable Speed Motor ECM...

Страница 19: ...19 COMPONENTS AND REPLACEMENT PARTS...

Страница 20: ...20 Figure 10 Parts List With 4 Speed motor PSC B50082E...

Страница 21: ...B03589 01 SIDE PANEL INSULATION 26 B03559 01 SIDE BAFFLE 27 B03553 ELECTRICAL BOX SPACER 28 B03549 ELECTRICAL BOX 29 R02R008 HIGH LIMIT CTL205 30F 7 in 30 B03550 ELECTRICAL BOX COVER Panel only 31 B0...

Страница 22: ...22 Figure 11 Parts List With variable speed motor ECM B50083E...

Страница 23: ...03589 01 SIDE PANEL INSULATION 26 B03559 01 SIDE BAFFLE 27 B03553 ELECTRICAL BOX SPACER 28 B03534 ELECTRICAL BOX 29 R02R008 HIGH LIMIT CTL205 30F 7 in 30 B03550 ELECTRICAL BOX COVER Panel only 31 B031...

Страница 24: ...Ne pas alt rer votre unit ou ses contr les Appeler un technicien qualifi INSTALLATEUR TECHNICIEN Utiliser les renseignements dans ce manuel pour l installation et l entretien de l appareil et garder...

Страница 25: ...ALISATION OUVERTURE DE VENTILATION DANS LA PORTE DU PLACARD 4 FIGURE 2 BRANCHEMENT DU THERMOSTAT CHAUFFAGE ET CLIMATISATION UNIT AVEC MOTEUR 4 VITESSES 5 FIGURE 3 BRANCHEMENT DU THERMOSTAT CHAUFFAGE E...

Страница 26: ...onduit comment le changer une fois par ann e iv Le filtre air comment le changer v rifier mensuellement et nettoyer ou changer si n cessaire g Avant d appeler pour le service prendre en note les rense...

Страница 27: ...s doit tre utilis e 2 1 EMPLACEMENT MISE EN GARDE Risque d incendie ou d explosion L appareil doit tre install au niveau Ne jamais installer avec une inclinaison vers l avant Ne pas ranger ou utiliser...

Страница 28: ...d origine de l appareil de chauffage central utilisez seulement du fil de cuivre r sistant la m me temp rature que les fils d origine 2 3 INSTALLATION DU THERMOSTAT L installation d un thermostat de...

Страница 29: ...s avec le volet motoris Si cette fournaise ou d autres appareils ne sont pas ad quatement vacu s cela peut entra ner la mort ou des dommages corporels et ou mat riels Pour assurer un fonctionnement s...

Страница 30: ...ner une flamme malpropre des odeurs dans la maison le refoulement des appareils de combustion et peut entra ner des naus es l asphyxie et ou la mort des occupants L appareil de chauffage central n ces...

Страница 31: ...stribution d air conform ment aux m thodes approuv es et conforme aux codes locaux et nationaux Lorsque les conduits d alimentation d air transportent l air dans un autre espace que celui o la fournai...

Страница 32: ...C 10 10 ON ON D N A 0 Table 6 Ajustement des d lais en mode chauffage SW4 Delay D lai Position interrupteurs DIP 1 2 POSITION Puissance USGPH OFF OFF A 0 70 ON OFF B 0 55 OFF ON C 0 55 ON ON D ALL Po...

Страница 33: ...s et selon les sp cifications de ce manuel 8 Les d lais de d part et d arr t du ventilateur sont r gl s de fa on satisfaisante 9 Le thermostat de la pi ce est en mode chauffage et est r gl une temp ra...

Страница 34: ...age central installer le r gulateur de tirage barom trique fourni avec l appareil Pour que ce r gulateur fonctionne correctement monter les goupilles pins l horizontale et le devant du r gulateur la v...

Страница 35: ...e de l unit effectuer une v rification compl te de la combustion apr s chaque entretien annuel Ne pas tenter de r parer l unit ou les contr les de l appareil Appeler un technicien qualifi Avant d appe...

Страница 36: ...et fixer le bo tier de commande l aide des 2 vis qui avait t enlev es l tape 4 8 Remettre en place le couvercle de l ensemble avec les vis enlev es l tape 2 9 Remettre l alimentation lectrique 4 3 NE...

Страница 37: ...se du technicien de service R SULTAT DU TEST DE MISE EN MARCHE Gicleur Pression lb po 2 Ajustements du br leur Bande principale Bande fine Position de la t te CO2 Indice de fum e Bacharach Temp rature...

Страница 38: ...partir du standard CSA B212 et des lois canadiennes 86 1 85 0 86 1 85 0 AFUE partir du standard ASHRAE 103 et des lois am ricaines 85 7 85 0 85 7 85 0 Volts Hertz Phase Consommation Amp Amp minimum p...

Страница 39: ...19 60 sec 38 3 min C 1 OFF 2 ON 0 55 13 60 sec 13 60 sec 38 3 min D 1 ON 2 ON All 13 30 sec 100 0 sec 100 2 min Pas d ajustement requis Capacit climatisation PreRun D lai On Niveau PCM Temps ShortRun...

Страница 40: ...SSE AMT098 PRESS ION STATIQ UE EXTERNE AVE C FILTRE AIR Table 10 D gagement minimum mat riaux combustibles EMPLACEMENT APPLICATION D G AGEMENTS m at riaux combustibles ACC S RE COMMAND P OUR L ENTRETI...

Страница 41: ...18 Figure 7 Dimensions de la fournaise...

Страница 42: ...____________________________________________________________________________________ 19 Figure 8 Diagramme lectrique Moteur 4 vitesses PSC...

Страница 43: ...20 Figure 9 Diagramme lectrique Moteur vitesse variable ECM...

Страница 44: ...____________________________________________________________________________________ 21 COMPOSANTES ET PI CES DE REMPLACEMENT...

Страница 45: ...22 Figure 10 Liste de pi ces Avec moteur 4 vitesses PSC B50082E...

Страница 46: ...olation et d flecteur 25 B03589 01 ISOLATION PANNEAU DE COTE 26 B03559 01 DEFLECTEUR LATERAL 27 B03553 ESPACEUR DE BOITE ELECTRIQUE 28 B03549 BOITE ELECTRIQUE 29 R02R008 CONTR LE HAUTE LIMITE L205 30...

Страница 47: ...24 Figure 11 Liste de pi ces Avec moteur vitesse variable ECM B50083E...

Страница 48: ...rend panneau et isolation et d flecteur 25 B03589 01 ISOLATION PANNEAU DE COTE 26 B03559 01 DEFLECTEUR LATERAL 27 B03553 ESPACEUR DE BOITE ELECTRIQUE 28 B03534 BOITE ELECTRIQUE 29 R02R008 CONTR LE HAU...

Отзывы: