background image

 

 

4

 

 

 

2 INSTALLATION

 

The unit is shipped with a burner and its controls. It requires a 
115VAC power supply to the control panel and thermostat 
hook-up as shown on the wiring diagram, one or more oil line 
connections, suitable ductwork and connection to a properly 
sized vent.  

 

All local and national code requirements governing the 
installation of oil burning equipment, wiring and the flue 
connection MUST be followed. Some of the codes that may 
apply are: 

CSA B139:

  

Installation code for oil burning equipment. 

ANSI/NFPA 31:

   Installation of oil burning equipment. 

ANSI/NFPA 90B:

 Warm air heating and air conditioning 

systems. 

ANSI/NFPA 211:

  Chimneys, Fireplaces, Vents and solid fuel 

burning appliances.

 

ANSI/NFPA 70:

   National Electrical Code.  

CSA C22.1 or CSA C22.10

: Canadian Electrical Code. 

Only the latest issues of these codes may be used. 

2.1 

POSITIONING THE FURNACE 

WARNING 

 

Fire and explosion hazard. 

 

The furnace must be installed in a level position, never 
where it will slope toward the front. 

 

Do not store or use gasoline or any other flammable 
substances near the furnace. 

 

Non-observance of these instructions will potentially result 
in death, bodily injury and/or property damage. 

 

CAUTION 

This furnace is not watertight and is not designed for outdoor 
installation. It must be installed in such a manner as to protect 
its electrical components from water. Outdoor installation will 
lead to a hazardous electrical condition and to premature 
failure of the equipment. 

 

 

The minimum clearances from combustible material for 
each of the positions are specified in Table 4. 

 

If the furnace is installed in a basement or on a dirt floor, in a 
crawl space for example, it is recommended to install the unit 
on a cement base 2.5 cm to 5.0 cm (1" to 2") thick. 

 

The unit must be installed in an area where the ambient and 
return air temperatures are above 15°C (60°F). In addition, the 
furnace should be installed as closely as possible to the vent, 
so that the connections are direct and kept to a minimum. The 
heater should also be located close to the centre of the air 
distribution system. 

2.1.1 

I

NSTALLATION IN AN ENCLOSURE

 

The unit can be installed in an enclosure such as a closet. 
However, 2 ventilation openings are required for combustion 
air. The openings should be located in front of the furnace 
approximately 15 cm (6") above the floor and 15 cm (6") below 
the ceiling. Figure 1 indicates the minimum dimensions 
required and the location of the openings.  

Figure 1: Location and dimensions of ventilation air 

openings in a closet door 

 

2.2 ELECTRICAL 

SYSTEM 

CAUTION 

The exterior of the unit must have an uninterrupted ground 
to minimize the risk of bodily harm, if ever an electrical 
problem develops. A green ground screw is supplied with 
the control box for that purpose.

  

 

The appliance must be installed in accordance with the 
current ANSI/NFPA 70 National Electrical Code, CSA 
C22.1 Canadian Electrical Code Part 1 and/or local codes.

 

The control system depends on the correct polarity of the 
power supply. Connect “HOT” wire (H) and “NEUTRAL” 
wire (N) as shown in Figures 3 and 4.

 

A separate line voltage supply should be used, with fused 
disconnect switch or circuit breaker, between the main 
power panel and the unit.

 

Only copper wire may be used for the 115V circuit on this 
unit. If wires need to be changed, the replacements must 
have the same temperature resistance as the originals. 

2.3 ELECTRICAL 

SYSTEM 

CAUTION 

The exterior of the unit must have an uninterrupted ground 
to minimize the risk of bodily harm, if ever an electrical 
problem develops. A green ground screw is supplied with 
the control box for that purpose.

  

The appliance must be installed in accordance with the 
current ANSI/NFPA 70 National Electrical Code, CSA 
C22.1 Canadian Electrical Code Part 1 and/or local codes. 

 

The control system depends on the correct polarity of the 
power supply. Connect “HOT” wire (H) and “NEUTRAL” 
wire (N) as shown in Figures 3 and 4. 

 

A separate line voltage supply should be used, with fused 
disconnect switch or circuit breaker, between the main 
power panel and the unit. 

 

Only copper wire may be used for the 115V circuit on this 
unit. If wires need to be changed, the replacements must 
have the same temperature resistance as the originals. 

Содержание AMT098SD

Страница 1: ...Attention Do not tamper with the unit or its controls Call a qualified service technician INSTALLER SERVICE TECHNICIAN Use the information in this manual for the installation servicing of the furnace...

Страница 2: ...JUSTMENTS HEATING MODE 4 SPEED MOTOR 7 TABLE 2 BLOWER SPEED ADJUSTMENTS A C MODE 4 SPEED MOTOR 7 TABLE 3 HEATING MODE 8 TABLE 4 AIR CONDITIONING MODE 8 TABLE 5 CFM ADJUSTMENT ALL MODES 8 TABLE 6 DELAY...

Страница 3: ...formation such as the model and serial numbers of the furnace WARNING Installations and repairs performed by unqualified persons can result in hazards to them and to others Installations must conform...

Страница 4: ...so be located close to the centre of the air distribution system 2 1 1 INSTALLATION IN AN ENCLOSURE The unit can be installed in an enclosure such as a closet However 2 ventilation openings are requir...

Страница 5: ...nozzle sizes by working back from the desired flow rate at operating pressure and not the nozzle marking 2 5 2 AIR AND TURBULATOR SETTINGS Before starting the burner for the first time adjust the air...

Страница 6: ...k that the electrical outlet on the furnace designated to the BVSO is functional 1 Start up the burner 2 Remove the three pole plug from the BVSO outlet on the furnace 3 The burner must shut off immed...

Страница 7: ...led to the furnace casing Failure to properly seal ducts can result in death bodily injury and or property damage The ducting must be designed and installed according to approved methods local and nat...

Страница 8: ...24 VAC signal can also be supplied from the W and C terminals on the blower electronic board to activate a switching relay Also refer to the instructions supplied with the accessory 2 12 2 ELECTRONIC...

Страница 9: ...of the oil piping and pump Slowly close and tighten the bleed screw Once closed the flame will light up 3 3 2 PRESSURE ADJUSTMENT The oil pressure must be adjusted according to the Technical Specifica...

Страница 10: ...ed investigate for ductwork obstructions dirty or improper air filter improper firing caused by improper pump pressure or nozzle sizing 3 3 8 LIMIT CONTROL CHECK After operating the furnace for at lea...

Страница 11: ...bly cover 3 Remove the cover 4 Remove the two screws holding the control box to the heat transfer tube assembly Sliding the control box in the appropriate direction will unlock it from the heat transf...

Страница 12: ...vice telephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure lb po 2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Am...

Страница 13: ...stion air adjustment turbulator damper 0 3 5 1 5 25 0 3 5 1 5 25 Minimum and Maximum pump pressure PSIG 125 to 180 135 to 170 125 to 180 135 to 170 AFUE From CSA B212 standard and Canadian regulation...

Страница 14: ...c 13 60 sec 38 3 min D 1 ON 2 ON All 13 30 sec 100 0 sec 100 2 min No adjustment required A C size PreRun On Delay CFM Level Time ShortRun On Delay CFM Level Time Off Delay CFM Level Time All No Delay...

Страница 15: ...E XTE RNAL STATIC P RE SSURE WITH AIR FILTE R Table 10 Minimum clearances from combustible material LOCATION APP LICATION CLEARANCE S combustible ma terials RECOMMANDED ACCES S FO R SERVICE FURNACE 1...

Страница 16: ...16 Figure 7 Furnace Dimensions...

Страница 17: ...17 Figure 8 Wiring Diagram 4 Speed Motor PSC...

Страница 18: ...18 Figure 9 Wiring Diagram Variable Speed Motor ECM...

Страница 19: ...19 COMPONENTS AND REPLACEMENT PARTS...

Страница 20: ...20 Figure 10 Parts List With 4 Speed motor PSC B50082E...

Страница 21: ...B03589 01 SIDE PANEL INSULATION 26 B03559 01 SIDE BAFFLE 27 B03553 ELECTRICAL BOX SPACER 28 B03549 ELECTRICAL BOX 29 R02R008 HIGH LIMIT CTL205 30F 7 in 30 B03550 ELECTRICAL BOX COVER Panel only 31 B0...

Страница 22: ...22 Figure 11 Parts List With variable speed motor ECM B50083E...

Страница 23: ...03589 01 SIDE PANEL INSULATION 26 B03559 01 SIDE BAFFLE 27 B03553 ELECTRICAL BOX SPACER 28 B03534 ELECTRICAL BOX 29 R02R008 HIGH LIMIT CTL205 30F 7 in 30 B03550 ELECTRICAL BOX COVER Panel only 31 B031...

Страница 24: ...Ne pas alt rer votre unit ou ses contr les Appeler un technicien qualifi INSTALLATEUR TECHNICIEN Utiliser les renseignements dans ce manuel pour l installation et l entretien de l appareil et garder...

Страница 25: ...ALISATION OUVERTURE DE VENTILATION DANS LA PORTE DU PLACARD 4 FIGURE 2 BRANCHEMENT DU THERMOSTAT CHAUFFAGE ET CLIMATISATION UNIT AVEC MOTEUR 4 VITESSES 5 FIGURE 3 BRANCHEMENT DU THERMOSTAT CHAUFFAGE E...

Страница 26: ...onduit comment le changer une fois par ann e iv Le filtre air comment le changer v rifier mensuellement et nettoyer ou changer si n cessaire g Avant d appeler pour le service prendre en note les rense...

Страница 27: ...s doit tre utilis e 2 1 EMPLACEMENT MISE EN GARDE Risque d incendie ou d explosion L appareil doit tre install au niveau Ne jamais installer avec une inclinaison vers l avant Ne pas ranger ou utiliser...

Страница 28: ...d origine de l appareil de chauffage central utilisez seulement du fil de cuivre r sistant la m me temp rature que les fils d origine 2 3 INSTALLATION DU THERMOSTAT L installation d un thermostat de...

Страница 29: ...s avec le volet motoris Si cette fournaise ou d autres appareils ne sont pas ad quatement vacu s cela peut entra ner la mort ou des dommages corporels et ou mat riels Pour assurer un fonctionnement s...

Страница 30: ...ner une flamme malpropre des odeurs dans la maison le refoulement des appareils de combustion et peut entra ner des naus es l asphyxie et ou la mort des occupants L appareil de chauffage central n ces...

Страница 31: ...stribution d air conform ment aux m thodes approuv es et conforme aux codes locaux et nationaux Lorsque les conduits d alimentation d air transportent l air dans un autre espace que celui o la fournai...

Страница 32: ...C 10 10 ON ON D N A 0 Table 6 Ajustement des d lais en mode chauffage SW4 Delay D lai Position interrupteurs DIP 1 2 POSITION Puissance USGPH OFF OFF A 0 70 ON OFF B 0 55 OFF ON C 0 55 ON ON D ALL Po...

Страница 33: ...s et selon les sp cifications de ce manuel 8 Les d lais de d part et d arr t du ventilateur sont r gl s de fa on satisfaisante 9 Le thermostat de la pi ce est en mode chauffage et est r gl une temp ra...

Страница 34: ...age central installer le r gulateur de tirage barom trique fourni avec l appareil Pour que ce r gulateur fonctionne correctement monter les goupilles pins l horizontale et le devant du r gulateur la v...

Страница 35: ...e de l unit effectuer une v rification compl te de la combustion apr s chaque entretien annuel Ne pas tenter de r parer l unit ou les contr les de l appareil Appeler un technicien qualifi Avant d appe...

Страница 36: ...et fixer le bo tier de commande l aide des 2 vis qui avait t enlev es l tape 4 8 Remettre en place le couvercle de l ensemble avec les vis enlev es l tape 2 9 Remettre l alimentation lectrique 4 3 NE...

Страница 37: ...se du technicien de service R SULTAT DU TEST DE MISE EN MARCHE Gicleur Pression lb po 2 Ajustements du br leur Bande principale Bande fine Position de la t te CO2 Indice de fum e Bacharach Temp rature...

Страница 38: ...partir du standard CSA B212 et des lois canadiennes 86 1 85 0 86 1 85 0 AFUE partir du standard ASHRAE 103 et des lois am ricaines 85 7 85 0 85 7 85 0 Volts Hertz Phase Consommation Amp Amp minimum p...

Страница 39: ...19 60 sec 38 3 min C 1 OFF 2 ON 0 55 13 60 sec 13 60 sec 38 3 min D 1 ON 2 ON All 13 30 sec 100 0 sec 100 2 min Pas d ajustement requis Capacit climatisation PreRun D lai On Niveau PCM Temps ShortRun...

Страница 40: ...SSE AMT098 PRESS ION STATIQ UE EXTERNE AVE C FILTRE AIR Table 10 D gagement minimum mat riaux combustibles EMPLACEMENT APPLICATION D G AGEMENTS m at riaux combustibles ACC S RE COMMAND P OUR L ENTRETI...

Страница 41: ...18 Figure 7 Dimensions de la fournaise...

Страница 42: ...____________________________________________________________________________________ 19 Figure 8 Diagramme lectrique Moteur 4 vitesses PSC...

Страница 43: ...20 Figure 9 Diagramme lectrique Moteur vitesse variable ECM...

Страница 44: ...____________________________________________________________________________________ 21 COMPOSANTES ET PI CES DE REMPLACEMENT...

Страница 45: ...22 Figure 10 Liste de pi ces Avec moteur 4 vitesses PSC B50082E...

Страница 46: ...olation et d flecteur 25 B03589 01 ISOLATION PANNEAU DE COTE 26 B03559 01 DEFLECTEUR LATERAL 27 B03553 ESPACEUR DE BOITE ELECTRIQUE 28 B03549 BOITE ELECTRIQUE 29 R02R008 CONTR LE HAUTE LIMITE L205 30...

Страница 47: ...24 Figure 11 Liste de pi ces Avec moteur vitesse variable ECM B50083E...

Страница 48: ...rend panneau et isolation et d flecteur 25 B03589 01 ISOLATION PANNEAU DE COTE 26 B03559 01 DEFLECTEUR LATERAL 27 B03553 ESPACEUR DE BOITE ELECTRIQUE 28 B03534 BOITE ELECTRIQUE 29 R02R008 CONTR LE HAU...

Отзывы: