background image

 

 

6

 

 

 

2.6.1 

M

ASONRY CHIMNEY

 

This furnace can be vented into an existing masonry chimney. 
However, the unit must not be vented into a chimney into 
which a solid fuel burning furnace is already being vented. 

 

Before venting this furnace into a chimney, its condition must 
be checked and repairs made, if necessary. Also, the chimney 
lining and dimensions must conform to local and national 
codes. 

 

2.6.2 

F

ACTORY 

B

UILT 

C

HIMNEYS

 

Oil fired furnaces are approved for use with “L” type vents. The 
unit may also be used with an approved chimney of proper 
dimensions and temperature ratings as specified in the 
installation code. Refer to chimney manufacturer’s instructions 
for proper installation. 

2.6.3 

D

RAFT 

R

EGULATOR

 

This unit may be installed with or without a draft 
regulator. However, it is recommended that a draft 
regulator be installed in cases where the draft is 
either high or variable due to external conditions. 
Follow the instructions provided with the regulator. 

2.6.4 

S

IDE

-W

ALL 

V

ENTING

 

The heating unit is approved for side-wall venting. This system 
is comprised of a model VTK-098/KLAVT0101DET side-wall 
venter and a 4” insulated vent pipe, model IFV098-
10/KLAFV0101DET, IFV098-20/KLAFV0201DET. Refer to the 
installation instructions provided with the venting system. 
 

2.7 

BLOCKED VENT SHUT-OFF DEVICE 
(BVSO) FOR CHIMNEY VENTING 

CAUTION 

It is imperative that this device be installed by a qualified service 
technician. 

 

A positive pressure venting system (Sealed Combustion System 
or Direct Vent) 

MUST NOT

 use the BVSO. Follow the 

instructions supplied with the venting system. 

 

This device is designed to detect the insufficient evacuation of 
combustion gases in the event of a vent blockage. In such a 
case the thermal switch will shut down the oil burner. The 
device will then need to be re-armed MANUALLY.

 

R

efer to the detailed instructions and wiring diagrams supplied 

with the BVSO for the installation and wiring procedures. The 
length of wires supplied with the unit is such that the safety 
device must be installed between the flue outlet of the 
appliance and the draft regulator, as indicated in the 
instructions. 

 

It is also essential that the BVSO be maintained annually. For 
more details refer to the instructions supplied with the device 
itself, as well as Section 3 of this Manual. 

2.7.1 

BVSO

 

P

ERFORMANCE 

T

EST

 

 

The purpose of the following test is to check that the electrical 
outlet on the furnace, designated to the BVSO, is functional. 

 

1.  Start up the burner; 
2.  Remove the three-pole plug from the BVSO outlet on the 

furnace; 

3.  The burner must shut-off immediately, while the 

blower continues to run to the end of the cool-down 
cycle.

 

If the test is not in line with the above, call a QUALIFIED 
SERVICE TECHNICIAN.

 

2.8 

COMBUSTION AIR SUPPLY 
AND VENTILATION

 

WARNING

 

 

Poisonous carbon monoxide gas hazard. 

 

Comply with NFPA 31 (U.S.) and CSA B139 (Canada) 
standards for the installation of Oil Burning 
Equipment and applicable provisions of local building 
codes to provide combustion and ventilation air. 

 

Failure to provide adequate combustion and 
ventilation air can result in death, bodily injury and/or 
property damage. 

 

Oil furnaces must have an adequate supply of combustion 
air. It is common practice to assume that older homes 
have sufficient infiltration to accommodate the combustion 
air requirement for the furnace. However, home 
improvements such as new windows, doors, and weather 
stripping have drastically reduced the volume of air 
infiltration into the home.

 

 

Refer to oil furnace installation codes relative to 
combustion and ventilation air requirements. Consult 
Section 2.1 in this manual, specifically for units installed in 
an enclosed space.  

 

Home air exhausters are common. Bathroom and kitchen 
fans, power vented clothes dryers and water heaters all 
tend to create a negative pressure condition in the home. 
Should this occur the chimney becomes less and less 
effective and can easily downdraft. In certain cases, 
mechanically supplied air, by way of a blower, interlocked 
with the unit, is necessary. It is the installer’s responsibility 
to check that. 

2.8.1 

C

ONTAMINATED 

C

OMBUSTION 

A

IR 

 

Installations in certain areas or types of structures will 
increase the exposure to chemicals or halogens that may 
harm the furnace. These conditions will require that only 
outside air be used for combustion. 

 

The following areas or types of structures may contain or 
be exposed to certain substances, potentially requiring 
outside air for combustion: 

 

a. Commercial 

buildings; 

b.  Buildings with indoor pools; 

c. 

Furnaces installed near chemical storage areas.

 

Exposure to the following substances: 
a.  Permanent wave chemicals for hair; 
b.  Chlorinated waxes and cleaners; 
c. 

Chlorine based swimming pool chemicals; 

d.  Water softening chemicals; 
e.  De-icing salts or chemicals; 
f. Carbon 

tetrachloride; 

g.  Halogen type refrigerants; 
h.  Cleaning solvents (such as perchloroethylene); 
i. 

Printing inks, paint removers, varnishes, etc. ; 

j. Hydrochloric 

acid; 

Содержание AMT098SD

Страница 1: ...Attention Do not tamper with the unit or its controls Call a qualified service technician INSTALLER SERVICE TECHNICIAN Use the information in this manual for the installation servicing of the furnace...

Страница 2: ...JUSTMENTS HEATING MODE 4 SPEED MOTOR 7 TABLE 2 BLOWER SPEED ADJUSTMENTS A C MODE 4 SPEED MOTOR 7 TABLE 3 HEATING MODE 8 TABLE 4 AIR CONDITIONING MODE 8 TABLE 5 CFM ADJUSTMENT ALL MODES 8 TABLE 6 DELAY...

Страница 3: ...formation such as the model and serial numbers of the furnace WARNING Installations and repairs performed by unqualified persons can result in hazards to them and to others Installations must conform...

Страница 4: ...so be located close to the centre of the air distribution system 2 1 1 INSTALLATION IN AN ENCLOSURE The unit can be installed in an enclosure such as a closet However 2 ventilation openings are requir...

Страница 5: ...nozzle sizes by working back from the desired flow rate at operating pressure and not the nozzle marking 2 5 2 AIR AND TURBULATOR SETTINGS Before starting the burner for the first time adjust the air...

Страница 6: ...k that the electrical outlet on the furnace designated to the BVSO is functional 1 Start up the burner 2 Remove the three pole plug from the BVSO outlet on the furnace 3 The burner must shut off immed...

Страница 7: ...led to the furnace casing Failure to properly seal ducts can result in death bodily injury and or property damage The ducting must be designed and installed according to approved methods local and nat...

Страница 8: ...24 VAC signal can also be supplied from the W and C terminals on the blower electronic board to activate a switching relay Also refer to the instructions supplied with the accessory 2 12 2 ELECTRONIC...

Страница 9: ...of the oil piping and pump Slowly close and tighten the bleed screw Once closed the flame will light up 3 3 2 PRESSURE ADJUSTMENT The oil pressure must be adjusted according to the Technical Specifica...

Страница 10: ...ed investigate for ductwork obstructions dirty or improper air filter improper firing caused by improper pump pressure or nozzle sizing 3 3 8 LIMIT CONTROL CHECK After operating the furnace for at lea...

Страница 11: ...bly cover 3 Remove the cover 4 Remove the two screws holding the control box to the heat transfer tube assembly Sliding the control box in the appropriate direction will unlock it from the heat transf...

Страница 12: ...vice telephone Day Night Dealer name and address START UP RESULTS Nozzle Pressure lb po 2 Burner adjustments Primary air Fine air Drawer Assembly CO2 Smoke scale Bacharach Gross stack temperature F Am...

Страница 13: ...stion air adjustment turbulator damper 0 3 5 1 5 25 0 3 5 1 5 25 Minimum and Maximum pump pressure PSIG 125 to 180 135 to 170 125 to 180 135 to 170 AFUE From CSA B212 standard and Canadian regulation...

Страница 14: ...c 13 60 sec 38 3 min D 1 ON 2 ON All 13 30 sec 100 0 sec 100 2 min No adjustment required A C size PreRun On Delay CFM Level Time ShortRun On Delay CFM Level Time Off Delay CFM Level Time All No Delay...

Страница 15: ...E XTE RNAL STATIC P RE SSURE WITH AIR FILTE R Table 10 Minimum clearances from combustible material LOCATION APP LICATION CLEARANCE S combustible ma terials RECOMMANDED ACCES S FO R SERVICE FURNACE 1...

Страница 16: ...16 Figure 7 Furnace Dimensions...

Страница 17: ...17 Figure 8 Wiring Diagram 4 Speed Motor PSC...

Страница 18: ...18 Figure 9 Wiring Diagram Variable Speed Motor ECM...

Страница 19: ...19 COMPONENTS AND REPLACEMENT PARTS...

Страница 20: ...20 Figure 10 Parts List With 4 Speed motor PSC B50082E...

Страница 21: ...B03589 01 SIDE PANEL INSULATION 26 B03559 01 SIDE BAFFLE 27 B03553 ELECTRICAL BOX SPACER 28 B03549 ELECTRICAL BOX 29 R02R008 HIGH LIMIT CTL205 30F 7 in 30 B03550 ELECTRICAL BOX COVER Panel only 31 B0...

Страница 22: ...22 Figure 11 Parts List With variable speed motor ECM B50083E...

Страница 23: ...03589 01 SIDE PANEL INSULATION 26 B03559 01 SIDE BAFFLE 27 B03553 ELECTRICAL BOX SPACER 28 B03534 ELECTRICAL BOX 29 R02R008 HIGH LIMIT CTL205 30F 7 in 30 B03550 ELECTRICAL BOX COVER Panel only 31 B031...

Страница 24: ...Ne pas alt rer votre unit ou ses contr les Appeler un technicien qualifi INSTALLATEUR TECHNICIEN Utiliser les renseignements dans ce manuel pour l installation et l entretien de l appareil et garder...

Страница 25: ...ALISATION OUVERTURE DE VENTILATION DANS LA PORTE DU PLACARD 4 FIGURE 2 BRANCHEMENT DU THERMOSTAT CHAUFFAGE ET CLIMATISATION UNIT AVEC MOTEUR 4 VITESSES 5 FIGURE 3 BRANCHEMENT DU THERMOSTAT CHAUFFAGE E...

Страница 26: ...onduit comment le changer une fois par ann e iv Le filtre air comment le changer v rifier mensuellement et nettoyer ou changer si n cessaire g Avant d appeler pour le service prendre en note les rense...

Страница 27: ...s doit tre utilis e 2 1 EMPLACEMENT MISE EN GARDE Risque d incendie ou d explosion L appareil doit tre install au niveau Ne jamais installer avec une inclinaison vers l avant Ne pas ranger ou utiliser...

Страница 28: ...d origine de l appareil de chauffage central utilisez seulement du fil de cuivre r sistant la m me temp rature que les fils d origine 2 3 INSTALLATION DU THERMOSTAT L installation d un thermostat de...

Страница 29: ...s avec le volet motoris Si cette fournaise ou d autres appareils ne sont pas ad quatement vacu s cela peut entra ner la mort ou des dommages corporels et ou mat riels Pour assurer un fonctionnement s...

Страница 30: ...ner une flamme malpropre des odeurs dans la maison le refoulement des appareils de combustion et peut entra ner des naus es l asphyxie et ou la mort des occupants L appareil de chauffage central n ces...

Страница 31: ...stribution d air conform ment aux m thodes approuv es et conforme aux codes locaux et nationaux Lorsque les conduits d alimentation d air transportent l air dans un autre espace que celui o la fournai...

Страница 32: ...C 10 10 ON ON D N A 0 Table 6 Ajustement des d lais en mode chauffage SW4 Delay D lai Position interrupteurs DIP 1 2 POSITION Puissance USGPH OFF OFF A 0 70 ON OFF B 0 55 OFF ON C 0 55 ON ON D ALL Po...

Страница 33: ...s et selon les sp cifications de ce manuel 8 Les d lais de d part et d arr t du ventilateur sont r gl s de fa on satisfaisante 9 Le thermostat de la pi ce est en mode chauffage et est r gl une temp ra...

Страница 34: ...age central installer le r gulateur de tirage barom trique fourni avec l appareil Pour que ce r gulateur fonctionne correctement monter les goupilles pins l horizontale et le devant du r gulateur la v...

Страница 35: ...e de l unit effectuer une v rification compl te de la combustion apr s chaque entretien annuel Ne pas tenter de r parer l unit ou les contr les de l appareil Appeler un technicien qualifi Avant d appe...

Страница 36: ...et fixer le bo tier de commande l aide des 2 vis qui avait t enlev es l tape 4 8 Remettre en place le couvercle de l ensemble avec les vis enlev es l tape 2 9 Remettre l alimentation lectrique 4 3 NE...

Страница 37: ...se du technicien de service R SULTAT DU TEST DE MISE EN MARCHE Gicleur Pression lb po 2 Ajustements du br leur Bande principale Bande fine Position de la t te CO2 Indice de fum e Bacharach Temp rature...

Страница 38: ...partir du standard CSA B212 et des lois canadiennes 86 1 85 0 86 1 85 0 AFUE partir du standard ASHRAE 103 et des lois am ricaines 85 7 85 0 85 7 85 0 Volts Hertz Phase Consommation Amp Amp minimum p...

Страница 39: ...19 60 sec 38 3 min C 1 OFF 2 ON 0 55 13 60 sec 13 60 sec 38 3 min D 1 ON 2 ON All 13 30 sec 100 0 sec 100 2 min Pas d ajustement requis Capacit climatisation PreRun D lai On Niveau PCM Temps ShortRun...

Страница 40: ...SSE AMT098 PRESS ION STATIQ UE EXTERNE AVE C FILTRE AIR Table 10 D gagement minimum mat riaux combustibles EMPLACEMENT APPLICATION D G AGEMENTS m at riaux combustibles ACC S RE COMMAND P OUR L ENTRETI...

Страница 41: ...18 Figure 7 Dimensions de la fournaise...

Страница 42: ...____________________________________________________________________________________ 19 Figure 8 Diagramme lectrique Moteur 4 vitesses PSC...

Страница 43: ...20 Figure 9 Diagramme lectrique Moteur vitesse variable ECM...

Страница 44: ...____________________________________________________________________________________ 21 COMPOSANTES ET PI CES DE REMPLACEMENT...

Страница 45: ...22 Figure 10 Liste de pi ces Avec moteur 4 vitesses PSC B50082E...

Страница 46: ...olation et d flecteur 25 B03589 01 ISOLATION PANNEAU DE COTE 26 B03559 01 DEFLECTEUR LATERAL 27 B03553 ESPACEUR DE BOITE ELECTRIQUE 28 B03549 BOITE ELECTRIQUE 29 R02R008 CONTR LE HAUTE LIMITE L205 30...

Страница 47: ...24 Figure 11 Liste de pi ces Avec moteur vitesse variable ECM B50083E...

Страница 48: ...rend panneau et isolation et d flecteur 25 B03589 01 ISOLATION PANNEAU DE COTE 26 B03559 01 DEFLECTEUR LATERAL 27 B03553 ESPACEUR DE BOITE ELECTRIQUE 28 B03534 BOITE ELECTRIQUE 29 R02R008 CONTR LE HAU...

Отзывы: