background image

3.3

OPERATING SEQUENCE

3.3.1

Heating mode

1. The thermostat closes the R-W1 circuit (24 VAC),

thereby sending a 24 VAC signal to the blower relay
and the sequencer board.

The board will then

activate all the first stage relays with a delay of 3
seconds between each element. The motor relay
will be activated, which will start the blower on the
first stage heating speed.

2. The thermostat closes the R-W2 circuit (24 VAC),

thereby sending a 24 VAC signal to the blower
relay and the sequencer board.

The board will

then activate all the first and second stage relays
with a delay of 3 seconds between each element.
The motor relay will be activated, which will start
the blower on the second stage maximum heating
speed.

3. The deactivation of either mode will result in the

deactivation of the corresponding relays with a
delay of 0.5 second between each element.

3.3.2

Cooling Mode

1. The thermostat closes the R-G circuit, thereby

activating the 24 VAC relay. The blower starts up
to cooling speed.

2. The thermostat closes the R-Y contact, thereby

activating

the

compressor

relay

of

the

air

conditioner.

3.3.3

Continuous fan speed

Activating the “Fan” switch on the thermostat will engage
only the blower at cooling speed.

3.4

AIRFLOW VERIFICATION

Verify the airflow by taking readings of the following
points, while the elements are in heating mode:

a) Total amperage of all the heating elements;

b) Voltage at the furnace;

c) Supply air temperature. The point of the reading

must not be affected by radiant heat from the
elements;

d) Return air temperature.

From these readings, one can arrive at an approximate
calculation of the average airflow.

To do that, the

following formula should be used:

Liter/s

=

0

.

82

×

amps.

×

volts

Diff. temperature °C

CFM

=

3

.

1

×

amps.

×

volts

Diff. temperature °F

Tables and show estimated airflows for various
temperature rises.

3.4.1

Supply Air Temperature Rise Test

1. Operate the unit at maximum power for at least 10

minutes;

2. Measure the air temperature in the return air

plenum;

3. Measure the air temperature in the largest trunk

coming off the supply air plenum, just outside the
range of radiant heat from the heat exchanger. 0.3
m (12”) from the plenum of the main take-off is
usually sufficient;

4. Calculate the temperature rise by subtracting

the return air temperature from the supply air
temperature.

If the temperature rise exceeds the temperature specified
in Table 2 and Table 3, change to the next higher blower
speed tap, until the temperature rise falls to the target
or below.

If the excessive temperature rise cannot

be reduced by increasing fan speed, investigate for
ductwork obstructions or dirty and improper air filter.

CAUTION

It is important to check the airflow and to
ascertain that the unit does not operate above
the temperatures specified in the Technical
Specifications (Table 2).

This is particularly

important if a cooling coil or a heat pump has been
installed in the ducts.
Hi-Limit thermal protectors should never need
to engage during the normal functioning of the
appliance. They are strictly designed to engage
during the improper functioning of the blower or
when the filter was improperly maintained.

3.4.2

High limit verification

After operating the furnace for at least 15 minutes, restrict
the return air supply by blocking the filters or the return air
register and allow the furnace to shut off on High Limit.
The electric heaters must deactivate themselves before

8

Содержание ADVANTAGE SUPXX-A120D12

Страница 1: ...0 INSTALLER SERVICE TECHNICIAN Attention Do not tamper with the unit or its controls Call a qualified service technician USE THE INFORMATION IN THIS MANUAL FOR THE INSTALLATION AND SERVICING OF THE FU...

Страница 2: ...ATION 9 5 FURNACE INFORMATION 9 6 TECHNICAL SPECIFICATIONS 10 7 NOTES 22 List of figures Figure 1 Upflow Configuration 4 Figure 2 Downflow Configuration 4 Figure 3 Horizontal Configuration 4 Figure 4...

Страница 3: ...d for use by a qualified technician familiar with safety procedures and who is equipped with the proper tools and test instruments Failure to carefully read and follow all instructions in this manual...

Страница 4: ...8 VAC power supply to the control panel thermostat hook up as shown on the wiring diagram 2 1 POSITIONING THE FURNACE WARNING FIRE AND EXPLOSION HAZARD The furnace must be installed in a level positio...

Страница 5: ...and or property damage 2 4 ELECTRICAL SYSTEM The SUPREME furnace is completely pre wired and all field wiring must be connected to the terminal blocks on the unit It requires 2 service wires of 240 20...

Страница 6: ...t be changed to the 208V position 2 5 INSTALLATION OF THE THERMOSTAT A thermostat must be installed to control the temperature of the area to be heated Follow the instructions supplied with the thermo...

Страница 7: ...nd return air connectors to avoid the transmission of vibration To make the unit run even quieter the installer should 1 Use two elbows between each outlet and the supply and return air plenum 2 Cover...

Страница 8: ...structions provided with the thermostat or the Fossil Fuel kit for the proper wiring of the furnace and the heat pump The simultaneous operation of the electric elements and the heat pump will cause o...

Страница 9: ...on of the average airflow To do that the following formula should be used Liter s 0 82 amps volts Diff temperature C CFM 3 1 amps volts Diff temperature F Tables 5 and 6 show estimated airflows for va...

Страница 10: ...rmostat higher than room temperature If the unit does not start up cut the power and call a qualified service technician When calling for service or ordering a replacement part specify the model and s...

Страница 11: ...5 9 9 11 5 9 9 11 5 9 9 11 5 9 9 11 5 9 9 Heating Elements Consumption 240V 208V Amp 41 4 35 9 62 1 53 8 75 8 65 7 82 8 71 8 96 5 83 6 103 5 89 7 82 8 71 8 96 5 83 6 103 5 89 7 113 6 98 5 124 3 107 7...

Страница 12: ...1 5 9 5 1 5 9 5 1 5 9 5 1 Heating Elements Consumption 240V 208V Amp 41 4 35 9 62 1 53 8 75 8 65 7 82 8 71 8 96 5 83 6 103 5 89 7 82 8 71 8 96 5 83 6 103 5 89 7 113 6 98 5 124 3 107 7 Total Consumpti...

Страница 13: ...or Consumption 240V 208V Amp Max 2 6 2 3 5 9 5 1 Heating Elements Consumption 240V 208V Amp 57 8 50 1 72 2 62 6 Total Consumption 240V 208V Amp 60 4 52 3 78 1 67 7 Ampacity 240V 208V Amp 76 66 93 81 S...

Страница 14: ...est 5CFM Data taken with air filter in place Table 6 Airflow CFM SUPREME with 1HP motor Furnace equipped with a 1HP 120 blower motor Blower External static pressure inche of W C Speed 0 2 0 3 0 4 0 5...

Страница 15: ...559mm 22 25mm 1 SUPPLY ALIMENTATION 508mm x 508mm 20 x 20 REVISIONS REV DESCRIPTION A C DATE PAR Figure 12 Advantage Dimensionsi 451mm 17 3 4 451mm 17 3 4 RETURN 483mm x 483mm 19 x 19 RETOUR Identical...

Страница 16: ...Figure 13 lectrical diagram Supreme Comfort PSC 15...

Страница 17: ...Figure 14 lectrical diagram Supreme Advantage PSC 16...

Страница 18: ...Figure 15 lectrical diagram Supreme Advantage PSC 3 phases ELECTRICAL DIAGRAM DIAGRAMME L CTRIQUE ADVANTAGE AVANTAGE PSC 3 PHASES 17...

Страница 19: ...20 23 24 25 28 27 B50147 rev F 7 8 9 10 11 12 13 5 6 REV DESCRIPTION A C DATE PAR B Changement Disjoncteur 22314 2015 05 15 F H C Ajoute support de filtre Change item 1 22388 2015 07 01 F H D TIQUETT...

Страница 20: ...10 15 18 20 kW 20 B01889 Motor support band and legs 21 L06K004 Motor 1hp 120v PSC Supreme 20 kW 22 L06K005 Motor 1hp 240v PSC Supreme 20 kW 23 L06G007 Motor 1 3hp 120v PSC Supreme 10 15 18 20 kW 24...

Страница 21: ...rev F 9 12 13 14 8 6 7 15 16 17 18 19 10 11 REV DESCRIPTION A C DATE PAR B Changement disjoncteur pour CQC 22326 2015 05 19 F H C Ajoute support de filtre Change item 1 22389 2015 07 01 F H D TIQUETT...

Страница 22: ...18 20 23 25 kw 24 B04356 04 Blower assembly 1hp 240V PSC Supreme 20 23 25 27 30 kw 25 Z01I036 Blower 112 9R 1hp Supreme 20 23 25 27 30 kw 26 Z01I035 Blower 112 8R 1 3hp Supr me 10 15 18 20 23 25 kw 27...

Страница 23: ...7 NOTES 22...

Страница 24: ...23...

Отзывы: