background image

IMPORTANT

:

All

local

and

national

code

requirements governing the installation of central
electric heating equipment, wiring and the flue
connection MUST be followed. Some of the codes
that may apply are:

ANSI/NFPA 70

:

National Electrical Code

CSA

C22.1 or CSA C22.10

: Canadian Electrical Code

Only the latest issues of these codes may be used,
and are available from either:

The National Fire Protection Agency

1 Batterymarch Park

Quincy, MA 02269

or

The Canadian Standards Association

178 Rexdale Blvd.

Rexdale, Ontario M9W 1R3

1.3

DANGER OF FREEZING

CAUTION

If your furnace is shut down during the cold
weather season, water pipes may freeze, burst and
cause serious water damage. Turn off the water
supply and bleed the pipes.

If the heater is left unattended during the cold weather
season, take the following precautions:

a) Close the main water valve in the house and purge

the pipes if possible. Open all the faucets in the
house;

b) Ask someone to frequently check the house during

the cold weather season to make sure that there is
sufficient heat to prevent the pipes from freezing.
Tell this person to call an emergency number if
required.

2

INSTALLATION

This furnace is a true multi-position unit, in that
it will function in an upflow, downflow or horizontal
configuration to the left or the right.

Only a few

modifications are required during installation to change
from one position to another. The unit is shipped in the
upflow configuration and instructions as to how to change
to the other positions are included in this manual.
The unit requires a 120/240 - 208 VAC power supply to
the control panel, thermostat hook-up as shown on the
wiring diagram.

2.1

POSITIONING THE FURNACE

WARNING

FIRE AND EXPLOSION HAZARD
The furnace must be installed in a level position,
never where it will slope toward the front.
Do not store or use gasoline or any other
flammable substances near the furnace.
Non-observance

of

these

instructions

will

potentially result in death, bodily injury and/or
property damage.

WARNING

This furnace is not watertight and is not designed
for outdoor installation.

It must be installed

in such a manner as to protect its electrical
components from water. Outdoor installation will
lead to a hazardous electrical condition and to
premature failure of the equipment.

If the furnace is installed in a basement or on a dirt floor,
in a crawl space for example, it is recommended to install
the unit on a cement base 2.5 cm to 5.0 cm (1” to 2”)
thick.
In addition, the heater should also be located close to the
center of the air distribution system.

2.2

CLEARANCES TO
COMBUSTIBLE MATERIAL

2.2.1

Heating unit

The

furnace

is

approved

for

zero

clearance

to

combustible material regardless of the heating capacity.

2.2.2

Supply air ducts

Ducts can be installed with a zero clearance to
combustible material.

2.3

CONFIGURATIONS

This furnace requires suitable ductwork.

2.3.1

Upflow installation

The return duct may be installed to the back, to the
bottom, on the left side or on the right side of the unit. The
supply duct shall be installed on the top of the unit. Care
should be taken not to damage the wires inside, while
cutting the opening. Instal the filter rack that is supplied
with the unit. It is also recommended to install the blower
door before handling or moving the unit. Refer to Figure
1 for additional details.

3

Содержание ADVANTAGE SUPXX-A120D12

Страница 1: ...0 INSTALLER SERVICE TECHNICIAN Attention Do not tamper with the unit or its controls Call a qualified service technician USE THE INFORMATION IN THIS MANUAL FOR THE INSTALLATION AND SERVICING OF THE FU...

Страница 2: ...ATION 9 5 FURNACE INFORMATION 9 6 TECHNICAL SPECIFICATIONS 10 7 NOTES 22 List of figures Figure 1 Upflow Configuration 4 Figure 2 Downflow Configuration 4 Figure 3 Horizontal Configuration 4 Figure 4...

Страница 3: ...d for use by a qualified technician familiar with safety procedures and who is equipped with the proper tools and test instruments Failure to carefully read and follow all instructions in this manual...

Страница 4: ...8 VAC power supply to the control panel thermostat hook up as shown on the wiring diagram 2 1 POSITIONING THE FURNACE WARNING FIRE AND EXPLOSION HAZARD The furnace must be installed in a level positio...

Страница 5: ...and or property damage 2 4 ELECTRICAL SYSTEM The SUPREME furnace is completely pre wired and all field wiring must be connected to the terminal blocks on the unit It requires 2 service wires of 240 20...

Страница 6: ...t be changed to the 208V position 2 5 INSTALLATION OF THE THERMOSTAT A thermostat must be installed to control the temperature of the area to be heated Follow the instructions supplied with the thermo...

Страница 7: ...nd return air connectors to avoid the transmission of vibration To make the unit run even quieter the installer should 1 Use two elbows between each outlet and the supply and return air plenum 2 Cover...

Страница 8: ...structions provided with the thermostat or the Fossil Fuel kit for the proper wiring of the furnace and the heat pump The simultaneous operation of the electric elements and the heat pump will cause o...

Страница 9: ...on of the average airflow To do that the following formula should be used Liter s 0 82 amps volts Diff temperature C CFM 3 1 amps volts Diff temperature F Tables 5 and 6 show estimated airflows for va...

Страница 10: ...rmostat higher than room temperature If the unit does not start up cut the power and call a qualified service technician When calling for service or ordering a replacement part specify the model and s...

Страница 11: ...5 9 9 11 5 9 9 11 5 9 9 11 5 9 9 11 5 9 9 Heating Elements Consumption 240V 208V Amp 41 4 35 9 62 1 53 8 75 8 65 7 82 8 71 8 96 5 83 6 103 5 89 7 82 8 71 8 96 5 83 6 103 5 89 7 113 6 98 5 124 3 107 7...

Страница 12: ...1 5 9 5 1 5 9 5 1 5 9 5 1 Heating Elements Consumption 240V 208V Amp 41 4 35 9 62 1 53 8 75 8 65 7 82 8 71 8 96 5 83 6 103 5 89 7 82 8 71 8 96 5 83 6 103 5 89 7 113 6 98 5 124 3 107 7 Total Consumpti...

Страница 13: ...or Consumption 240V 208V Amp Max 2 6 2 3 5 9 5 1 Heating Elements Consumption 240V 208V Amp 57 8 50 1 72 2 62 6 Total Consumption 240V 208V Amp 60 4 52 3 78 1 67 7 Ampacity 240V 208V Amp 76 66 93 81 S...

Страница 14: ...est 5CFM Data taken with air filter in place Table 6 Airflow CFM SUPREME with 1HP motor Furnace equipped with a 1HP 120 blower motor Blower External static pressure inche of W C Speed 0 2 0 3 0 4 0 5...

Страница 15: ...559mm 22 25mm 1 SUPPLY ALIMENTATION 508mm x 508mm 20 x 20 REVISIONS REV DESCRIPTION A C DATE PAR Figure 12 Advantage Dimensionsi 451mm 17 3 4 451mm 17 3 4 RETURN 483mm x 483mm 19 x 19 RETOUR Identical...

Страница 16: ...Figure 13 lectrical diagram Supreme Comfort PSC 15...

Страница 17: ...Figure 14 lectrical diagram Supreme Advantage PSC 16...

Страница 18: ...Figure 15 lectrical diagram Supreme Advantage PSC 3 phases ELECTRICAL DIAGRAM DIAGRAMME L CTRIQUE ADVANTAGE AVANTAGE PSC 3 PHASES 17...

Страница 19: ...20 23 24 25 28 27 B50147 rev F 7 8 9 10 11 12 13 5 6 REV DESCRIPTION A C DATE PAR B Changement Disjoncteur 22314 2015 05 15 F H C Ajoute support de filtre Change item 1 22388 2015 07 01 F H D TIQUETT...

Страница 20: ...10 15 18 20 kW 20 B01889 Motor support band and legs 21 L06K004 Motor 1hp 120v PSC Supreme 20 kW 22 L06K005 Motor 1hp 240v PSC Supreme 20 kW 23 L06G007 Motor 1 3hp 120v PSC Supreme 10 15 18 20 kW 24...

Страница 21: ...rev F 9 12 13 14 8 6 7 15 16 17 18 19 10 11 REV DESCRIPTION A C DATE PAR B Changement disjoncteur pour CQC 22326 2015 05 19 F H C Ajoute support de filtre Change item 1 22389 2015 07 01 F H D TIQUETT...

Страница 22: ...18 20 23 25 kw 24 B04356 04 Blower assembly 1hp 240V PSC Supreme 20 23 25 27 30 kw 25 Z01I036 Blower 112 9R 1hp Supreme 20 23 25 27 30 kw 26 Z01I035 Blower 112 8R 1 3hp Supr me 10 15 18 20 23 25 kw 27...

Страница 23: ...7 NOTES 22...

Страница 24: ...23...

Отзывы: