WARNING

R

ISK OF FIRE

When using one terminal block on models of 25kW
and higher, the installation must be performed
with copper wire ONLY in order to comply with
the Canadian electrical code.

The usage of an

aluminum or copper wire is acceptable on models
25kW and lower.

Move all wires from the two pole terminal to the three pole

terminal following the corresponding colors as shown in
Figure 4.
The breaker and the supply conductors must be sized by
adding the ampacities of the two terminals indicated on
the nameplate. Refer to the electrical diagram Figure 12.

Figure 4: Conversion from two to one supply wires

2.4.2

208V Power Supply

If a 208VAC Power Supply is used, the connector at the
primary of the transformer must be changed to the 208V
position.

2.5

INSTALLATION OF THE
THERMOSTAT

A thermostat must be installed to control the temperature
of the area to be heated.

Follow the instructions

supplied with the thermostat. Some thermostats need to
connect the C terminal on the furnace and thermostat.
Install the thermostat on an interior wall in a location
where it will not be subject to direct sunlight, lamps,
air diffusers, fireplaces, etc. Seal openings in walls to
avoid air currents that may influence the operation of the
thermostat. Also refer to the wiring diagrams provided
with the heating/air conditioning unit. The connections
must be made as indicated on Figure 5 to Figure 9. Refer
to the electrical diagrams (Figure 12 and Figure 13).

Figure 5: 1-stage thermostat, electric heating only

Figure 6: 2-stage thermostat, electric heating only

Figure 7: 1-stage thermostat with outdoor control for
2-stage function, electric heating only

5

Содержание ADVANTAGE SUPXX-A120D12

Страница 1: ...0 INSTALLER SERVICE TECHNICIAN Attention Do not tamper with the unit or its controls Call a qualified service technician USE THE INFORMATION IN THIS MANUAL FOR THE INSTALLATION AND SERVICING OF THE FU...

Страница 2: ...ATION 9 5 FURNACE INFORMATION 9 6 TECHNICAL SPECIFICATIONS 10 7 NOTES 22 List of figures Figure 1 Upflow Configuration 4 Figure 2 Downflow Configuration 4 Figure 3 Horizontal Configuration 4 Figure 4...

Страница 3: ...d for use by a qualified technician familiar with safety procedures and who is equipped with the proper tools and test instruments Failure to carefully read and follow all instructions in this manual...

Страница 4: ...8 VAC power supply to the control panel thermostat hook up as shown on the wiring diagram 2 1 POSITIONING THE FURNACE WARNING FIRE AND EXPLOSION HAZARD The furnace must be installed in a level positio...

Страница 5: ...and or property damage 2 4 ELECTRICAL SYSTEM The SUPREME furnace is completely pre wired and all field wiring must be connected to the terminal blocks on the unit It requires 2 service wires of 240 20...

Страница 6: ...t be changed to the 208V position 2 5 INSTALLATION OF THE THERMOSTAT A thermostat must be installed to control the temperature of the area to be heated Follow the instructions supplied with the thermo...

Страница 7: ...nd return air connectors to avoid the transmission of vibration To make the unit run even quieter the installer should 1 Use two elbows between each outlet and the supply and return air plenum 2 Cover...

Страница 8: ...structions provided with the thermostat or the Fossil Fuel kit for the proper wiring of the furnace and the heat pump The simultaneous operation of the electric elements and the heat pump will cause o...

Страница 9: ...on of the average airflow To do that the following formula should be used Liter s 0 82 amps volts Diff temperature C CFM 3 1 amps volts Diff temperature F Tables 5 and 6 show estimated airflows for va...

Страница 10: ...rmostat higher than room temperature If the unit does not start up cut the power and call a qualified service technician When calling for service or ordering a replacement part specify the model and s...

Страница 11: ...5 9 9 11 5 9 9 11 5 9 9 11 5 9 9 11 5 9 9 Heating Elements Consumption 240V 208V Amp 41 4 35 9 62 1 53 8 75 8 65 7 82 8 71 8 96 5 83 6 103 5 89 7 82 8 71 8 96 5 83 6 103 5 89 7 113 6 98 5 124 3 107 7...

Страница 12: ...1 5 9 5 1 5 9 5 1 5 9 5 1 Heating Elements Consumption 240V 208V Amp 41 4 35 9 62 1 53 8 75 8 65 7 82 8 71 8 96 5 83 6 103 5 89 7 82 8 71 8 96 5 83 6 103 5 89 7 113 6 98 5 124 3 107 7 Total Consumpti...

Страница 13: ...or Consumption 240V 208V Amp Max 2 6 2 3 5 9 5 1 Heating Elements Consumption 240V 208V Amp 57 8 50 1 72 2 62 6 Total Consumption 240V 208V Amp 60 4 52 3 78 1 67 7 Ampacity 240V 208V Amp 76 66 93 81 S...

Страница 14: ...est 5CFM Data taken with air filter in place Table 6 Airflow CFM SUPREME with 1HP motor Furnace equipped with a 1HP 120 blower motor Blower External static pressure inche of W C Speed 0 2 0 3 0 4 0 5...

Страница 15: ...559mm 22 25mm 1 SUPPLY ALIMENTATION 508mm x 508mm 20 x 20 REVISIONS REV DESCRIPTION A C DATE PAR Figure 12 Advantage Dimensionsi 451mm 17 3 4 451mm 17 3 4 RETURN 483mm x 483mm 19 x 19 RETOUR Identical...

Страница 16: ...Figure 13 lectrical diagram Supreme Comfort PSC 15...

Страница 17: ...Figure 14 lectrical diagram Supreme Advantage PSC 16...

Страница 18: ...Figure 15 lectrical diagram Supreme Advantage PSC 3 phases ELECTRICAL DIAGRAM DIAGRAMME L CTRIQUE ADVANTAGE AVANTAGE PSC 3 PHASES 17...

Страница 19: ...20 23 24 25 28 27 B50147 rev F 7 8 9 10 11 12 13 5 6 REV DESCRIPTION A C DATE PAR B Changement Disjoncteur 22314 2015 05 15 F H C Ajoute support de filtre Change item 1 22388 2015 07 01 F H D TIQUETT...

Страница 20: ...10 15 18 20 kW 20 B01889 Motor support band and legs 21 L06K004 Motor 1hp 120v PSC Supreme 20 kW 22 L06K005 Motor 1hp 240v PSC Supreme 20 kW 23 L06G007 Motor 1 3hp 120v PSC Supreme 10 15 18 20 kW 24...

Страница 21: ...rev F 9 12 13 14 8 6 7 15 16 17 18 19 10 11 REV DESCRIPTION A C DATE PAR B Changement disjoncteur pour CQC 22326 2015 05 19 F H C Ajoute support de filtre Change item 1 22389 2015 07 01 F H D TIQUETT...

Страница 22: ...18 20 23 25 kw 24 B04356 04 Blower assembly 1hp 240V PSC Supreme 20 23 25 27 30 kw 25 Z01I036 Blower 112 9R 1hp Supreme 20 23 25 27 30 kw 26 Z01I035 Blower 112 8R 1 3hp Supr me 10 15 18 20 23 25 kw 27...

Страница 23: ...7 NOTES 22...

Страница 24: ...23...

Отзывы: