Table 3: Technical specifications(240V)
RATING AND
SUPxx-x240D12
SUPxx-x240D20
PERFORMANCE
Motor 1/3 HP / 240V
Motor 1 HP / 240V
Capacity
10
15
18
20
23
25
20
23
25
27
30
Power, total @
240V
/ 208V (Kw)
10
/ 7.5
15
/ 11.3
18
/ 13.5
20
/15
23
/ 17.3
25
/ 18.8
20
/15
23
/ 17.3
25
/ 18.8
27
/ 20.3
30
/ 22.5
Power, first stage @
240V
/ 208V
(Kw)
5
/ 3.8
10
/ 7.5
9
/ 6.8
10
/ 7.5
13
/ 9.8
15
/ 11.3
10
/ 7.5
13
/ 9.8
15
/ 11.3
15
/ 11.3
15
/ 11.3
Net capacity @
240V
(BTU/h) / 208V
34,120
25,628
51,180
38,442
61,420
46,130
68,240
51,256
78,480
58,944
85,300
64,070
68,240
51,256
78,480
58,944
85,300
64,070
92,124
69,195
102,360
76,884
Temperature rise range @ 240V (°F)
1
25-45
45-60
55-75
60-80
60-80
60-80
55-75
50-70
50-70
55-75
60-80
ELECTRICAL SYSTEM
Volts - Hertz - Phase
2 wires 240/208 - 60 - 1
Electrical element #1 @
240V
/ 208V
(Kw)
5
/ 3.7
5
/ 3.7
4
/ 3.1
5
/3.7
4
/ 3.1
5
/ 3.7
5
/ 3.7
4
/ 3.1
5
/ 3.7
5
/ 3.7
5
/ 3.7
Electrical element #2 @
240V
/ 208V
(Kw)
5
/ 3.7
5
/ 3.7
5
/ 3.7
5
/3.7
5
/ 3.7
5
/ 3.7
5
/ 3.7
5
/ 3.7
5
/ 3.7
5
/ 3.7
5
/ 3.7
Electrical element #3 @
240V
/ 208V
(Kw)
5
/ 3.7
4
/ 3.1
5
/3.7
4
/ 3.1
5
/ 3.7
5
/ 3.7
4
/ 3.1
5
/ 3.7
5
/ 3.7
5
/ 3.7
Electrical element #4 @
240V
/ 208V
(Kw)
5
/ 3.7
5
/ 3.7
5
/ 3.7
5
/ 3.7
5
/ 3.7
5
/ 3.7
5
/ 3.7
4
/ 3.1
5
/ 3.7
Electrical element #5 @
240V
/ 208V
(Kw)
5
/ 3.7
5
/ 3.7
5
/ 3.7
5
/ 3.7
4
/ 3.1
5
/ 3.7
Electrical element #6 @
240V
/ 208V
(Kw)
4
/ 3.1
5
/ 3.7
Blower motor Consumption @
240V
/ 208V (Amp. Max.)
2.6
/ 2.3
2.6
/ 2.3
2.6
/ 2.3
2.6
/ 2.3
2.6
/ 2.3
2.6
/ 2.3
5.9
/ 5.1
5.9
/ 5.1
5.9
/ 5.1
5.9
/ 5.1
5.9
/ 5.1
Heating Elements Consumption @
240V
/ 208V (Amp)
41.4
/
35.9
62.1
/
53.8
75.8
/
65.7
82.8
/
71.8
96.5
/
83.6
103.5
/
89.7
82.8
/
71.8
96.5
/
83.6
103.5
/
89.7
113.6
/
98.5
124.3
/
107.7
Total Consumption @
240V
/ 208V
(Amp)
44.0
/
35.9
64.7
/
56.1
78.4
/
68.0
85.4
/
74.1
99.1
/
85.9
106.1
/
92.0
88.7
/
76.9
102.4
/
88.7
109.4
/
94.8
119.5
/
103.6
130.2
/
112.8
Ampacity - Terminal block #1 @
240V
/ 208V (Amp)
2
54.3
/
47.3
78.9
/
68.6
95.1
/
82.7
103.5
/
90.0
119.7
/
104.0
128.1
/
111.3
107.4
/
93.3
123.5
/
107.3
132.0
/
114.6
54.0
/
47.0
58.2
/
50.7
Ampacity - Terminal block #2 @
240V
/ 208V (Amp)
2
-
-
-
-
-
-
-
-
-
90.0
/
78.0
98.4
/
85.2
Breaker size - Terminal block #1 @
240V
/ 208V (Amp)
2
60
/ 50
80
/ 70
100
/
90
125
/
90
125
/
125
150
/
125
125
/
100
125
/
125
150
/
125
60
/ 50
60
/ 60
Breaker size - Terminal block #2 @
240V
/ 208V (Amp)
2
-
-
-
-
-
-
-
-
-
90
/ 80
100
/
90
BLOWER DATA (factory adjusted for a static pressure of 0.5" W.C.)
Blower speed at 1
st
stage
LOW
LOW
LOW
LOW
LOW
MED-LOW
LOW
LOW
LOW
LOW
LOW
Blower speed at 0.50” W.C. stat.
LOW
MED-LOW MED-LOW MED-HIGH MED-HIGH MED-HIGH
LOW
LOW
MED-LOW MED-LOW MED-LOW
Blower speed at 0.20” W.C. stat.
LOW
MED-LOW MED-LOW MED-LOW MED-HIGH MED-HIGH
LOW
LOW
MED-LOW MED-LOW MED-LOW
Motor (HP) / number of speeds
1/3 HP / 3 speeds
1 HP / 4 speeds
Nominal blower size (diam. X width)
12 x 8
12 x 9
GENERAL INFORMATION
Overall dim. (width x depth x height)
22" x 22" x 36.5"
Supply
20” x 20”
Return
18” x 18”
Filter quantity and size
(1) 20" x 20"
Shipping weight
48 Kg / 105 lbs
Maximum cooling capacity
3 tons
5 tons
1) Select a blower speed that will generate the specified temperature rise.
2) Calculated on the basis of standardC22.2-236.
11