SIDE VIEW
End
End
WARNING
!
Failure to comply with the stated clearances to combustibles may result in
personal injury, property damage, and/or death.
END VIEW - 30° MOUNTING ANGLE
END VIEW - 0° MOUNTING ANGLE
Behind
Top
(to ceiling)
Front
Below**
Side
Side
Top (to ceiling)
Below**
Max.
30˚ Angle
9
DST
Series
In locations used for the storage of combustible materials, signs must be posted to specify the maximum
permissible stacking height to maintain the required clearances from the heater to the combustibles.
Signs must either be posted adjacent to the heater’s thermostat or in a conspicuous location.
The stated clearance to combustibles represents a surface temperature of 90°F (50°C) above room
temperature. Building materials with a low heat tolerance (such as plastics, vinyl siding, canvas, tri-ply,
etc.) may be subject to degradation at lower temperatures. It is the installer’s responsibility to assure that
adjacent materials are protected from degradation.
Chart 2.1
•
Clearances to Combustible Materials in Inches
(see Figure 2.1)
Model
Number
Mounting
Angle*
Top
Sides
Ends
Below**
Front
Behind
DST-60
0°
12
19
19
16
66
30°
14
45
24
16
45
DST-80
0°
15
26
26
16
77
30°
16
74
31
16
74
2.0
Safety
•
Clearances to Combustibles
* Heaters mounted on an angle between 1° to 30° must maintain clearances posted for 0° or 30°;
whichever is greater.
** The minimum mounting height is 79” above floor level.
Figure 2.1
•
Mounting Angles