13
DST
Series
Figure 3.4
•
Heater with Sway Bracing Installation
#3 Gripple
Safety Cabling
Side
Restraints
Longitudinal
Bracing
#3 Gripple
Safety Cabling
#2 Stainless Steel
Bulldog Chain
3.0
Installation
•
Sway Bracing for High Air Movement and Outdoor Applications
Sway Bracing for High Air Movement and Outdoor Applications
For high air movement and outdoor applications, install side restraints (Figure 3.4) to reduce side to side
swaying. Side restraints should be installed so that they are angled at 45° ± 10° and should be placed at
every designated suspension point. It may be necessary to add additional support structures at the ceiling
level for the connection of these side suspensions. Apply longitudinal (forward/backward) bracing at each
end of the heater (field supplied). The desired suspension material shall have a minimum work load rating
of 170 pounds.
Longitudinal
Bracing
(Field Supplied)