It is possible to wirelessly connect the CXT controller to a higher level controller. For this configuration,
the CXT controller must be supplied with a radio connected to its Modbus slave port. Contact the Detcon
factory for more information on this option.
11.2.7 SetC O M M B a ud R a tes
The Set COMM Baud Rates menu displays the current baud rate settings for COMM1 (master) and
COMM2 (slave).
Upon entering this menu, the LCD will display:
SET C O M M B A U D R A T ES:
C O M M 1B A U D R A T E:9600
C O M M 2B A U D R A T E:9600
N O T E
The value shown is pre-configured to 9600 and should not be altered unless directed to do
so by Detcon factory personnel.
11.2.8 SetM odbus
™
T i
m e outs
The Set Modbus
™
Timeouts menu establishes the response timeout for Modbus
™
communications and the
inter-poll delay. Response timeout is the amount of time in milliseconds the CXT controller will wait for a
sensor to respond to a poll request. Inter-poll delay is the amount of time in milliseconds the CXT will wait
after receiving a poll response from one sensor before it polls the next sensor. Ten missed poll responses
will result in the sensor being declared in COMM ERR. The range of values for the response timeout is
100-1000 milliseconds and 10-255 milliseconds for the inter-poll delay. The recommended value for the
response timeout is 500 and 150 for the inter-poll delay.
1. Upon entering this menu, the LCD will display:
SET M O D B U S T IM EO U T S:
R ESP O N SET IM EO U T :###
IN T ER P O L L D EL A Y :###
2. Values can be changed by swiping the magnet over the markers of the up or down arrows to move
the arrow prompt "
→
" to the desired function. A swipe over:
T he EN T ER m arker w ill select the function indicated by the arrow prom pt "→".
T hem arkersoftheupordow narrow sw illchangethevalue.
T heEN T ER m arkerw illsavetheselectedvalue.
11.2.9 D i
spla y Se tti
ngs
The Display Settings menu customizes the brightness, contrast and backlight duration of the display.
Values for brightness and contrast range between 0 and 100. Available values for the backlight timeout
function (turn off due to inactivity) are OFF, 10 seconds, 30 seconds and 1 to 5 minutes.
1. Upon entering this menu, the LCD will display: