Sentinel CXT Instruction Manual
Rev. 1.7
Page 29 of 49
3. If there is more than one channel, a swipe of the down arrow marker while the flashing cursor is on
ALM3 ASCENDING will scroll the display to the next channel allowing for its configuration. To
return to the previous channel, a swipe of the up arrow marker should be performed while the
flashing cursor is on ALM1 LEVEL.
4. Ensure that the gas alarm relay (if not being used) has a setting of 0 to make it inactive.
N O T E
For prope r com pli
a nce wi
thIEC 61010Sa fe ty Sta nda rd,
i
t i
sre qui
re d tha t a ny da nge rousle ve l
a la rm s (those tha t re qui
re possi
ble use r a cti
on/
i
nte rve nti
on)sha ll only be a ssi
gned tothe R e d
L ED i
ndi
ca tor (A la rm L e ve l 3). It i
s a lso re qui
re d for the ca se i
nwhi
ch i
f only 1 of the 3
possi
ble a la rm s i
s chose nto be se t,tha t i
t sha ll se t to A la rm L e ve l 3 whi
ch i
s the R e d L ED
i
ndi
ca tor.
N O T E
Any channels that are in alarm or fault will not display the device tag on the main display.
N O T E
If the channel range is changed, then the alarm set points must be re-entered.
5.4.4 SetR ela y (A la rm )Functi
ons
1. Upon entering this menu, the LCD will display:
FA U L T R EL A Y SET U P :B A N K 1
L A T C H IN G :X
EN ER G IZ ED :X
SIL EN C EA B L E:X
N O T E
Relays are displayed in the following order:
•
FAU L T
•
AL AR M 1
•
AL AR M 2
•
AL AR M 3
2. A flashing cursor will appear on LATCHING for Bank1. Swiping the magnet over:
T hem arkersoftheupordow narrow sw illm ovetheflashingcursortothedesiredfunction.
T heEN T ER m arkerw illselectthefunctionindicatedby theflashingcursor.
T hem arkersoftheupordow narrow sw illchangethevalue.
T heEN T ER m arkerw illsavetheselectedvalueandreturntotheflashingcursor.
T he dow n arrow m arkerw hile the flashing cursorison S ILEN CEABL E forBank1 w illscrollthe
display tothenextrelay allow ingforitsconfiguration.
T heuparrow m arkertoreturntothepreviousrelay w hiletheflashingcursorisonL AT CHIN G
forBank1.
3. Repeat Step 2 for the remaining banks containing three alarms and a fault.
4. Ensure that all four relay outputs in all eight banks are set-up to account for the following three
settings (Section 1.3). The values selected can be either Y (Yes) or N (No).