Sentinel CXT Instruction Manual
Rev. 1.7
Page 27 of 49
2. A flashing cursor will appear on SLAVE ID. Swipe the magnet over the markers of the up or down
arrows to move the flashing cursor to the desired function. A swipe over:
T heEN T ER m arkerw illselectthefunctionindicatedby theflashingcursor.
T hem arkersoftheupordow narrow sw illchangethevalue.
T heEN T ER m arkerw illsavetheselectedvalueandreturntotheflashingcursor.
N O T E
The SLAVE ID is the Modbus
™
address in hex of the sensor or device being assigned to a
specific channel. This will be a Modbus
™
slave device to the CXT controller.
D e vi
ce T ype V a lue
The Device Type values available are 100, 700, 600C, 600D (Detcon serial sensor models), DA4/DI4
(analog sensors), CXT-320, BM25 (wireless devices) or RXT-320 (when analog inputs are in use). Ensure
that the appropriate value corresponding to the sensor or device is assigned to the indicated channel.
A nalog InputV a lue
The Analog Input is only available for DA4/DI4, CXT-320, BM25, and RXT-320 devices. For analog
sensors (DA4/DI4), the available value is 1, 2, 3, or 4 corresponding to the input position on the DA4/DI4
module. For a BM25, the available values are 1, 2, 3, 4, or 5 corresponding to the cell number. For an
RXT-320 wireless radio module, the available value is 1 or 2 corresponding to the input position of the
connected sensor.
D e ci
m a l P oi
n
tV a lue
The Decimal Point value is set to 0, 1 or 2. This value can be edited if the device is a DA4, DI4, or RXT-
320. The number of digits displayed to the right of the decimal point of the gas concentration value is as
follows:
S ensorrangeislessthan10,thisvaluew illbe2.
S ensorrangeisbetw een10 and25,thisvaluew illusually be1.
S ensorrangeisgreaterthan25,thevalueshouldbe0.
R a nge V a lue
The Range value is 1-9,999 and corresponds to the gas range value of the sensor. This value can be edited
if the device is a DA4, DI4, or RXT-320.
N O T E
If the range is changed, the alarm levels will have to be reset.
CAUTION
The range value must match the range on the sensor for proper operation.
T ype V a lue
The Type value is an alphanumeric string of ten characters and corresponds to the tag that is displayed with
the gas concentration value. This field is used to define the gas concentration units and the gas type.
1. Swipe the magnet over the markers of the up or down arrows to modify the first alphanumeric
character indicated by an underscore.
2. A swipe over the ENTER marker will select the displayed value and the next character to be
changed will be indicated by an underscore.
3. Repeat Steps 1 and 2 to update all ten characters.