Se nti
nel C X T
Sentinel CXT Instruction Manual
Rev. 1.7
Page 22 of 49
Figure 20 Magnetic Programming Tool
5.2.2 Front P a nel U se r Inte rfa ce
The front panel user interface (Figure 21) contains four switches necessary to configure the CXT controller.
S m a r t W i r e l e s s A l a r m & C o n t r o l S y s t e m
Figure 21 Front Panel User Interface
P R O G Swi
tch
From the Main Display, the PROG switch enters into the Main Menu. Once inside the Main Menu, the
PROG switch acts as an "Escape" switch that moves backwards in the menu flow chart.
N O T E
While in Main Menu mode there are no updates to gas readings and hence no alarms will
take place.
U p A rrow Swi
tch
This switch moves the user up the Main Menu flow chart. It is also used to change selected entries in
the menu selections in the upward direction.
D ownA rrow Swi
tch
This switch moves the user down the Main Menu flow chart. It is also used to change selected entries
in the menu selections in the downward direction.
EN T ER a nd R ESET /
A C K Swi
tch
This switch has multi-purpose use:
T heEN T ER functionisused to acceptselectionsinallm enu screensand toexecutetheR eset
andAcknow ledgefunctions.
T heR esetfunctionreleasesalllatchedrelaysoncethealarm /faultconditionhascleared.
T he Acknow ledge function w illdisengage any silenceable relaysthat are in an active state.
T hisisusedtosilencealarm soncetheend-userhasassessedthealarm condition.
T he R ES ET /ACKN O W L EDGE function ofthe sw itch isonly applicable from the M ain Display
andnotw hileinM ainM enu m ode.
Содержание SmartWireless CXT
Страница 6: ......
Страница 44: ...Sen ti n el C X T Sentinel CXT Instruction Manual Rev 1 7 Page 38 of 49...