Se nsor C O M M Error
Verify all devices are set to the same RF Channel.
Verify all SmartWireless® CXT devices have a unique Modbus ID number.
Verify the Sensor Input PCA and Relay PCA Modbus address are set correctly
Verify the Radio Module Modbus address is set correctly
Se nsor Fa ult
Verify if sensor displays any fault. If so, follow sensor trouble shooting notes.
Verify if sensor cell needs replacement.
L ow B a tte ry
Attach external battery charger (this can only be done in an indoor non-hazardous area)
P oor L i
nk Q uali
ty
Verify antenna is securely attached to all devices.
Verify obstructions are eliminated or minimized between SmartWireless CXT devices and
controller or other CXT devices.
Slow G a s R e spon
se
Some delay in gas response is normal if the network update rate is greater than zero. To increase
response time, reduce the update rate. Reducing the update rate will reduce the battery life for
devices.
Sm a rtW i
rele ss C X T notfound duri
ng controller A utoC on
fi
gure
Verify CXT device set to correct RF Channel
Verify Radio Module has correct Modbus address
Verify the Sensor Input PCA and Relay PCA Modbus address are set correctly
Verify a proper mA load is present on sensor input. Sensor inputs are not detected unless the mA
input is greater than 1.9mA.
Contact the Detcon Service Department for further troubleshooting assistance at 713-559-9200