Overview
The CM3510 operating controller installed in Desert Aire’s SA dehumidifer is designed for
precise control and monitoring of air temperature and relative humidity (RH) within the
conditioned space. Additionally the control will capture and retain alarm history to aid in
equipment troubleshooting.
1.
Field Installation of CM3510 Control Sensors
The unit supplied for your project will include either a Duct Mount Sensor Assembly or a Wall
Mount Sensor Assembly depending on how the unit was ordered. All sensor installations
should be made in a location that will provide an accurate measurement of the area being
controlled. Effort should be made to prevent influence on the sensors from external sources.
1.1.1 Duct-Mounted Sensor
Install the duct-mount sensor in the return air duct upstream of any outdoor air intakes.
•
Do not mount the sensor in a section of duct where false readings may occur
due to dead air regions, solar heat gain, or thermal losses in winter.
•
Do not mount the sensor where water is likely to drip on it. Liquid moisture
will ruin the humidity sensing element in the sensor.
1.1.2 Wall Mount Humidity and Temperature Sensor
If your dehumidifier was ordered with a wall-mount humidity and temperature sensor,
mount the sensor five feet or higher above the pool deck on an interior wall with
natural air circulation. Avoid the following locations:
•
Do not install in a corrosive or wet environment.
•
Hot spots near concealed heating pipes, warm air ducts, supply register
outlets, or solar radiation.
•
Cold spots due to a cold wall or drafts from stairwells, doors, windows, or
supply register outlets.
•
Dead spots such as behind doors or in corners where room air cannot
circulate freely.
1.1.3 Water Temperature Sensor (Pool Water Heating Option only)
Desert Aire dehumidifiers ordered with the pool water heating option are supplied with
a water temperature sensor and an immersion well.
•
Screw the well into an adapter fitted into the pool water piping. The well is
equipped with a 1/2” MPT connection.
•
Install the sensor upstream from the dehumidifier or the auxiliary pool
water heater.
Desert Aire - CM3510 Manual
Содержание CM3510 Series
Страница 2: ...2 ...
Страница 5: ...5 Product Warning for the State of California Desert Aire CM3510 Manual ...
Страница 6: ...6 Desert Aire CM3510 Manual ...
Страница 12: ...12 Desert Aire CM3510 Manual ...
Страница 67: ...67 Figure 85 Desert Aire CM3510 Manual ...
Страница 68: ...68 Desert Aire CM3510 Manual ...
Страница 79: ...79 Desert Aire CM3510 Manual ...