Figure 74
To return to the Airflow Menu, press the
Esc
key.
Pressing the
DOWN
key from this screen will show the next Airflow PID screen.
The WARM EXHAUST DAMPER screen will be shown any time the extended OA
box has been selected in the Factory Configuration. This screen allows the Warm
Air Exhaust Damper PID Gain (or Proportional Band), Reset (or Integral), Rate
(or Derivative) and Set point to be modified for loop tuning. The range of the Gain is
0 to 32767. The range of the Reset is 0 to 999. The range of the Rate is 0 to 999.
The range of the Set point is from 0.0”wc to 1.999”wc. To modify these set points,
press the
ENTER
key and use the arrow keys until the desired setting is shown.
Pressing the
ENTER
key will now change the set point. The actual Exhaust
differential air pressure and the damper position are displayed at the bottom of this
screen for reference.