2.2.4.5.1 Airflow Setup
Selecting the Airflow Setup will display the screen shown in Figure 62. This screen
displays a means to override the unit into an un-occupied mode to check the airflow
settings, the pressure drop across the reheat condenser and the minimum setting
used for the low airflow condition.
Figure 62
To return to the Airflow Menu, press the
Esc
key.
Pressing the
DOWN
key from this screen will continue the Airflow Setup. The
DAMPER SETTINGS screen will be shown if “No Exhaust” has been selected in the
Factory Configuration. The outside air damper position is set based upon the settings
shown in Figure 63. The Event, Max O/A and Purge positions will be shown on this
screen if these options have been selected in the Factory Configuration of the
dehumidifier. All settings can be modified from 0.0% to 100.0%. To modify these
set points, press the
ENTER
key and use the arrow keys until the desired setting is
shown. Pressing the
ENTER
key will now change the set point. The Unit Override can
be set to “Auto”, “Unocc”, “Occ”, “Event”, “Max OA” or “Purge”. This will allow testing
of the damper position in all applicable modes.
Desert Aire - CM3510 Manual