48
Pressing the
DOWN
key will now display the screen shown in Figure 57. Figure 57 allows the
Keypad to set the position of the Movable Roof or Wall. Press the
ENTER
key and the
UP
or
DOWN
key until the correct position of the Roof or Walls is shown. This screen also shows
the state of the Roof/Wall Switch as well as the BMS point. If any of these three settings are
open, the action defined in the next section will be active. The last line of this screen will
show the state that the Roof/Wall is in.
Figure 57
Pressing the
DOWN
key will now display the screen shown in Figure 58. Figure 58 defines
the action taken if the Roof/Wall switch is set. All five of the selections can be set to Enable
or Disable. If the Supply Fan is set to Disable, the supply fan will be forced off when the
Roof/Wall switch is closed and the next four selections will be removed from the screen. If the
Supply Fan is set to Enable, the next four selections can be modified. If the Compressor is
set to disable, the compressor will not be active when the Roof/Wall switch is closed. If the
Air Heating is set to disable, then the air heating will not be active when the Roof/Wall switch
is closed. If the Ventilation is set to disable, then the outside air damper will be closed when
the Roof/Wall switch is closed. If the Exhaust Fan is set to disable, then the exhaust fan
output will set to 0% when the Roof/Wall switch is closed.
To return to the SERVICE MENU, press the
Esc
key.
Desert Aire - CM3510 Manual
Содержание CM3510 Series
Страница 2: ...2 ...
Страница 5: ...5 Product Warning for the State of California Desert Aire CM3510 Manual ...
Страница 6: ...6 Desert Aire CM3510 Manual ...
Страница 12: ...12 Desert Aire CM3510 Manual ...
Страница 67: ...67 Figure 85 Desert Aire CM3510 Manual ...
Страница 68: ...68 Desert Aire CM3510 Manual ...
Страница 79: ...79 Desert Aire CM3510 Manual ...