12.Diagnostic and maintenance

48

49

12.Diagnostic and maintenance

EN

Message

Possible cause

Action

Heat Sink NTC2 

Fail

1. Actual utility 

voltage is under the 

UVR setting
2. Incorrect country 

or Grid setting
3. Wrong connec

-

tion in AC plug
4. One or more 

internal fuses are 

broken
5. Detection circuit 

malfunction

1. Check the utility 

voltage connection 

to the inverter ter-

minal.
2. Check country & 

Grid setting
3. Check the con

-

nection in AC plug
4. Replace fuses 

and check all 

switching devices 

in boost & inverter 

stages
5. Check the detec

-

tion circuit inside 

the inverter

DSP ADC Vgrid/

Iout fail

1. Actual utility 

voltage is over the 

OVR setting
2. Utility voltage 

is over the Slow 

OVR setting during 

operation

3. Incorrect country 

or Grid setting
4. Detection circuit 

malfunction

1-2. Check the 

utility voltage on the 

inverter terminal

3. Check country & 

Grid setting
4. Check the detec

-

tion circuit inside 

the inverter

DSP ADC Vin/Vbus 

Fail

1. Actual Solar1 

voltage is over 

1000Vdc

2. Detection circuit 

malfunction

1. Modify the solar 

array setting, and 

make the Voc less 

than 1000Vdc

2. Check the detec

-

tion circuit inside 

the inverter

DSP ADC Iin/Iboost 

Fail

1. Auxiliary power 

circuitry malfunction
2. Detection circuit 

malfunction

1. Check the auxil

-

iary circuitry inside 

the inverter

2. Check the detec

-

tion circuit inside 

the inverter

Red. ADC Vgrid Fail 1. Auxiliary power 

circuitry malfunction
2. Detection circuit 

malfunction

1. Check the auxil

-

iary circuitry inside 

the inverter

2. Check the detec

-

tion circuit inside 

the inverter

RED. ADC Iout_dc 

Fail

1. Auxiliary power 

circuitry malfunction
2. Detection circuit 

malfunction

1. Check the auxil

-

iary circuitry inside 

the inverter

2. Check the detec

-

tion circuit inside 

the inverter

Efficiency Incon

-

sistent

1. The calibration is 

incorrect

2. Current feedback 

circuit is defective

1. Check the accu

-

racy of current and 

power
2. Check the cur

-

rent feedback circuit 

inside the inverter

Message

Possible cause

Action

Internal Comm 

Fault_R

1. Red. CPU is 

idleing
2. The communica

-

tion connection is 

disconnected

1. Check reset and 

crystal in Red. CPU
2. Check the con

-

nection between 

Red. CPU and DSp

Internal Comm 

Fault_D

1. DSP is idleing
2. The communica

-

tion connection is 

disconnected

3. The communica

-

tion circuit malfunc

-

tion

1. Check reset and 

crystal in DSP
2. Check the con

-

nection between 

DSP and COMM
3. Check the com

-

munication circuit

Residual  Current 

Over Rating

1. PV array insula

-

tion fault
2. Large PV array 

capacitance 

between Plus to 

Ground or Minus to 

Ground
3. Either side of 

boost driver or 

boost choke mal

-

function
4. Detection circuit 

malfunction

1. Check the insula

-

tion of Solar inputs
2. Check the capac

-

itance (+ <-> GND 

& - <-> GND), must 

< 2.5uF. Install a 

external transformer 

if necessary
3. Check boost 

driver & boost 

choke
4. Check the detec

-

tion circuit inside 

the inverter

Ground Fault

1. PV array insula

-

tion fault
2. Large PV array 

capacitance 

between Plus to 

Ground or Minus to 

Ground or both.
3. Detection circuit 

malfunction

1. Check the insula

-

tion of Solar inputs
2. Check the capac

-

itance, dry PV panel 

if necessary
3. Check the detec

-

tion circuit inside 

the inverter

RCMU Circuit Fail

1. RCMU is discon

-

nected

2. Detection circuit 

malfunction

1. Check the RCMU 

connection inside 

the inverter

2. Check the detec

-

tion circuit inside 

the inverter

Relay  Short

1. One or more 

relays are sticking
2. The driver circuit 

for the relay mal

-

function

1. Replace the 

defective relay(s)
2. Check the driver 

circuit inside the 

inverter

Relay  Open

1. One or more 

relays are abnormal
2. The driver circuit 

for the relay mal

-

function
3. The detection 

accuracy is not cor

-

rect for Vgrid and 

Vout

1. Replace the 

defective relay(s)
2. Check the driver 

circuit inside the 

inverter

3. Check the Vgrid 

and Vout voltage 

detection accuracy

Message

Possible cause

Action

Bus Unbalance

1. Not totally inde

-

pendent or parallel 

between inputs
2. PV Array short to 

Ground
3. Driver for boost is 

defective or discon-

nected

4. Detection circuit 

malfunction

1. Check the inputs 

connections

2. Check the PV 

Array insulation
3. Check the driver 

curcuit for boost 

inside the inverter

4. Check the detec

-

tion circuit inside 

the inverter

Bus_P Over Volt 

Rating

1. Driver for boost is 

defective

2. Voc of PV array 

is over 1000Vdc

3. Surge occurs 

during operation
4. Detection circuit 

malfunction

1. Check the driver 

curcuit for boost 

inside the inverter

2. Modify the solar 

array setting, and 

make the Voc less 

than 1000Vdc

3. N/A
4. Check the detec

-

tion circuit inside 

the inverter

Bus_N Over Volta 

Rating

1. Driver for boost is 

defective

2. Voc of PV array 

is over 1000Vdc

3. Surge occurs 

during operation
4. Detection circuit 

malfunction

1. Check the driver 

curcuit for boost 

inside the inverter

2. Modify the solar 

array setting, and 

make the Voc less 

than 1000Vdc

3. N/A
4. Check the detec

-

tion circuit inside 

the inverter

Bus Volt Over Rat

-

ing

1. Driver for boost is 

defective

2. Voc of PV array 

is over 1000Vdc

3. Surge occurs 

during operation
4. Detection circuit 

malfunction

1. Check the driver 

curcuit for boost 

inside the inverter

2. Modify the solar 

array setting, and 

make the Voc less 

than 1000Vdc

3. N/A
4. Check the detec

-

tion circuit inside 

the inverter

Output Current 

Transient Over

1. Surge occurs 

during operation
2. Driver for inverter 

stage is defective
3. Switching device 

is defective

4. Detection circuit 

malfunction

1. N/A
2. Check the driver 

circuit in inverter 

stage
3. Check all switch

-

ing devices in 

inverter stage
4. Check the detect 

circuit inside the 

inverter

AC curr Over rating Detection circuit 

malfunction

Check the detect 

circuit inside the 

inverter

Message

Possible cause

Action

CT Current Sensor 

Fail

1.Inverter choke 

Fail

2.Output Filter Fail
3. Detection circuit 

malfunction

1. Check Inverter 

choke inductance.
2. Check output 

filter capacitance.
3. Check the detec

-

tion circuit inside 

the inverter

HW OOCP

1. WB1 WB2 mis

-

connection.
2. Detection circuit 

malfunction

1. Check the con

-

nection of WB1 and 

WB2.
2. Check the detec

-

tion circuit inside 

the inverter

Zero Cross Circuit 

Fail

The detection circuit 

for synchronal sig

-

nal malfunction

Check the detection 

circuit for synchro

-

nal signal inside the 

inverter

Incompatibility

Firmware version 

incorrect

Update the firm

-

ware

DC Curr Over 

 

Rating

1. Switching device 

in boost is defective
2. Driver for boost is 

defective

3. Input current 

detection circuit 

malfunction

1. Check all switch

-

ing device in boost
2. Check the driver 

curcuit for boost 

inside the inverter

3. Check input cur

-

rent detection circuit

DC Curr Transient 

Over

1. Switching device 

in boost is defective
2. Driver for boost is 

defective

3. Input current 

detection circuit 

malfunction

1. Check all switch

-

ing device in boost
2. Check the driver 

curcuit for boost 

inside the inverter

3. Check input cur

-

rent detection circuit

11.3  Maintenance

DANGER

Danger from hazardous voltage

Hazardous voltage is applied to the solar 

power inverter during operation. Hazardous 

voltage is still present 5 minutes after all 

power sources have been disconnected.

 

► Never open the solar power inverter. 

The solar power inverter contains no 

components that are to be maintained 

or repaired by the operator or installer. 

Opening the cover will void the war

-

ranty.

Ensure that the solar power inverter is not covered during 

operation. 
Regularly clean the solar power inverter to prevent soiling of 

the housing.
If there are any damaged parts, please contact a qualified 

technician to repair or replace the spare part.
Please clean the air outlets.

Содержание SOLIVIA 30 EU T4 TL

Страница 1: ...Operation and installation manual SOLIVIA 3 0 EU T4 TL SOLIVIA 5 0 EU T4 TL preliminary...

Страница 2: ...the device All information and specifications can be modified without prior notice Within this manual there may be symbols used that indicate that ETHERNET or WIRELESS function is required to utilize...

Страница 3: ...n features ETHERNET 19 5 7 Electrical connections 20 5 7 1 Overview 20 5 7 2 DC connections and DC switch 21 5 7 3 AC connection 21 5 7 4 Communications Module RS485 ETHERNET WiFi 21 5 7 4 1 RS485 int...

Страница 4: ...unication module ETHERNET WIRELESS 36 8 4 Next steps 37 9 Production information 38 9 1 Overview Menu Structure Display Interface 38 9 1 1 Startup Menu 38 9 1 2 Main Menu Loop 38 9 1 3 Measurement Loo...

Страница 5: ...ionality must be present to access the web interface 1 3 Warnings and symbols The following section explains the warnings and symbols used in this manual DANGER Indicates a dangerous situation An acci...

Страница 6: ...lar inverter during operation This potentially fatal voltage is still present for five minutes after all power sources have been discon nected Never open the solar inverter Always disconnect the solar...

Страница 7: ...sse ausreichend abgedichtet werden Nicht genutzte Anschl sse m ssen mit den am Solar Wech selrichter angebrachten Abdeckkappen verschlossen werden Italiano Indicazioni di sicurezza generali PERICOLO P...

Страница 8: ...este manual Antes de realizar trabajos en el inversor solar se debe separar el inversor solar de la red y de los m dulos FV El inversor solar presenta un valor de corriente de fuga elevado El conducto...

Страница 9: ...en m Najprv odpojte sie aby sol rny invertor nemohol dod va iadnu al iu energiu Potom rozpojte odpojova DC Zabezpe te DC pr pojky pred dotykmi Sol rny invertor mo no bezpe ne a norm lne prev dzkova i...

Страница 10: ...st te prevenci proti z sahu bleskem a to dodr ov n m ustanoven platn ch ve va zemi Povrch sol rn ho st da e m e b t velmi hork Sol rn st da je t k Sol rn st da je nutno zvedat a p en et v dy ve dvou K...

Страница 11: ...njury due to heavy weight The solar power inverter is heavy see Chapter 13 Technical Data Incorrect han dling can lead to injuries The solar power inverter must always be lifted by at least two people...

Страница 12: ...d in the following table SOLIVIA 3 0 TL and 5 0 TL inverter packing list Object Qty Description PV Inverter 1 3 kVA or 5 kVA solar inverter User Manual 1 The Instruction to provide the information of...

Страница 13: ...on Module Communication modules are available in three configurations depending on which inverter is ordered Type 1 is the stan dard default module that has the RS485 communication only Type 2 is a mo...

Страница 14: ...tion Hazardous voltage is still present 5 minutes after all power sources have been disconnected Never open the solar power inverter The solar power inverter contains no components that are to be main...

Страница 15: ...terface ETHERNET interface and WiFi module depends on the communications module type See the following section for further details 5 7 4 1 RS485 interface EIA485 The two RS485 interfaces are used to c...

Страница 16: ...s comes in multiple languages Accessible by Ethernet or WiFi connection IP address Ethernet 169 254 1 100 or WiFi 169 254 2 100 3 level of users are available Guest pwd guest Owner pwd owner Installer...

Страница 17: ...assumed temperature More exact information on tempera ture dependency is provided in the PV module data sheet The feed in voltage range of the solar power inverter defines the range of input voltages...

Страница 18: ...inte grated internal web interface Production information ETHERNET Production information is available for the actual day week month etc The production information is saved each month Warning and fai...

Страница 19: ...degree of pro tection and can be installed indoors and in protected outdoor areas Note the Operating temperature range at full power without derating and the maximum operating tem perature range When...

Страница 20: ...Mounting plate WARNING Danger of injury due to heavy weight The solar power inverter is heavy Incorrect handling can lead to injuries The solar power inverter must always be lifted by at least two peo...

Страница 21: ...ting nuts and washers for fastening the solar power inverter to the mounting plate The following items are also required Screws 5 mm dowels for fastening the mount ing plate to the wall 12 pcs M5 scre...

Страница 22: ...s kit allow you to meet the DC protection and signal requirements specified in UTE C 15 712 1 Multi Contact UTE Kit Delta Part Num ber Multi Contact UTE kit for SOLIVIA EU G4 TR EOE90000341 7 3 3 Esta...

Страница 23: ...dule kit is supplied in the scope of delivery Ethernet RS485 1 RS485 2 Antenna Rubber Seal Plug Claw Nut Fig 7 10 Assembly of the communications module The three openings for the cable feed through ar...

Страница 24: ...VDE 126A1 Germany VDE 0126 1 1 A1 x FR UTE France UTE 15 712 1 x NL Netherlands x PL Poland SPAIN RD 1699 Spain RD 1699 2011 x SPAIN Spain RD 1663 2000 x UK G83 1 United Kingdom UK G59 2 United Kingdo...

Страница 25: ...Guest Owner Installer Each level will have varied functions with Guest hav ing access to basic information and Installer with more advanced user rights For more info please see Chapter 9 Production I...

Страница 26: ...x xx Hz xxxx W DC xxx V xx x A xxxx W Today DC xxxxx Wh Today AC xxxxx Wh DC Life Energy xxxxxx KWh AC Life Energy xxxxxx KWh cos phi x xx PR xxx ENT or After 2 sec Measurement Information Section Sys...

Страница 27: ...r is master of Guest and Installer is the master of Owner and Guest User Levels Guest Owner Installer Example of the log in page Three user levels are avail able Guest Owner or Installer The user leve...

Страница 28: ...responds to a power gradient of 83 3 Hz User can set all necessary settings to meet the require ments from network operator P 0 Gradient 40 Pm Hz Pm Fstart 50 2Hz Power vs frequency curve for VDE AR N...

Страница 29: ...EC62109 2 Minimum Value R VMAX PV 30 mA 33K VDE0126 The array insulation resistance to ground shall be not less than 1 k V with respect to the maximum dc input voltage as specified by the manufacturer...

Страница 30: ...n AC plug and make sure it connects to inverter 3 Replace fuses and check all switching devices in boost inverter stages Grid Volt Under Rating 1 Actual utility voltage is under the UVR setting 2 Inco...

Страница 31: ...ace the defective relay s 2 Check the driver circuit inside the inverter 3 Check the Vgrid and Vout voltage detection accuracy Message Possible cause Action Bus Unbalance 1 Not totally inde pendent or...

Страница 32: ...Incorrect han dling can lead to injuries The solar power inverter must be lifted and carried by at least two people Or use an appropriate lifting device such as a crane 12 1 Decommissioning 1 Switch...

Страница 33: ...ass I Configurable trip parameters Yes 3 Isolation monitoring Yes Overload behavior Current limiting power limiting ENS Grid connection guidelines DIN VDE 0126 1 1 RD 1699 2011 RD1633 2000 UTE C15 712...

Страница 34: ...ating elevation 2 000 m above sea level 1 Cos Phi 1 VA W 2 AC voltage and frequency range will be programmed according to the individual country requirements 3 Ethernet communication module required t...

Страница 35: ...UR 4 6 10 3 6 32 0014P0001 UR 5 5 9 32 0016P0001 UR DC Plug 1 5 2 5 14 3 6 32 0011P0001 UR 5 5 9 32 0013P0001 UR 4 6 10 3 6 32 0015P0001 UR 5 5 9 32 0017P0001 UR MultiContact UTE kit The Multi Contact...

Страница 36: ...r Rating R Phase F42 CT current sensor Fail A F45 HW OOCP Circuit F50 Zero Cross Circuit Fail F56 Hardware Incompatibility F60 PV1 Current Over Rating F70 PV1 Current Transient Over Rating Error E01 O...

Страница 37: ...55 Certificates EN 15 Certificates Please visit the web site at www solar inverter com to find all applicable certificates for the SOLIVIA 3 0 TL 5 0 TL solar inverters...

Страница 38: ...upport greece solar inverter com 49 7641 455 549 Israel support israel solar inverter com 49 7641 455 549 Italy supporto italia solar inverter com 800 787 920 Free Call The Netherlands ondersteuning n...

Отзывы: