8. Commissioning

34

35

8. Commissioning

EN

8. 

Commissioning

8.1 

Before you start

The solar power inverter must be correctly installed, see 

Chapter 7 - Installation.
Information on operating the display is provided in 

Chapter 

5 - System description. 

After starting for the first time and completion of the auto

-

matic self-test you are guided step-by-step through the ini-
tial commissioning procedure. 

8.2 

Initial commissioning procedure

An overview of available grids for 3.0 TL and 5.0 TL is 

shown on table 9.1 in section 8.3.2.2.  The basic commis-

sioning process can be accomplished quickly via the display 

interface.  For fine tuning grid settings the web interface is 

recommended if your inverter has the ETHERNET option.  

More information is given regarding this in Chapter 10 Set-

tings.

8.3 

Basic commissioning

8.3.1  Brief overview of the commissioning steps

 

Set the display language

 

Set the country (grid)

 

Insulation (default is enabled)

 

Set the power limitation (optional)

1)

 

Set the date and time

1)

 Power limitation is required for some country grids.  Due 

to the simple software set up you can quickly set the power 

output installation parameters.  Please check with the grid 

authority and standard for required power limitations.

8.3.2  Detailed description of the commissioning 

steps via the display interface

Check all connections and cables for damage and correct 

seating. Correct the installation if necessary. 
1.  Switch on the DC switch.
2.  The startup process of the solar power inverter begins. 
3.  After the startup process and the automatic self-test 

the initial commissioning procedure of the solar power 

inverter starts and the 

Language

 menu is displayed.

8.3.2.1  Select a language for the display.

 

In the language setting page, press 

S

elect

 button to 

select the country.  Press 

S

elect

 multiple times to ad-

vance through the possible language list. 

 

After the appropriate language is shown, press 

e

nter

  

button to go to the confirm page.

 

Press 

e

nter

 on the confirm page to finalize your selec

-

tion or 

S

elect

 to redo the language selection.

Next / Enter

 

 
 
 
 
 
 

XXX

N / Y

 

 
 
 
 
 
 

XXX

XXX

 

 
 
 
 
 
 

Language

Configurable parameters

Display text

Designation Description

Language

Language

The display language XXX:
English | Italian | French | 

Spanish | German | Dutch | 

Polish

8.3.2.2  Select a country (grid).

 

In the country setting page, press 

S

elect

 button to 

select the country.  Pressing 

S

elect

 multiple times will 

advance through the possible grid country list. 

 

After the appropriate country is shown, press 

e

nter

  

button to go to the confirm page.

 

Press 

e

nter

 on the confirm page to finalize your selec

-

tion or 

S

elect

 to redo the country selection.

Next / Enter

 

 
 
 
 
 
 

XXX

N / Y

 

 
 
 
 
 
 

XXX

XXX

 

 
 
 
 
 
 

Country

Grids available for commissioning (XXX)

Display text

Description

3.0 

TL

5.0 

TL

BE C10/11

Belgium C10/C11 2012

x

DE VDE 126

Germany VDE 0126-1-1

x

DE VDE 126A1

Germany VDE 0126-1-1 / A1

x

FR UTE

France UTE 15-712-1

x

NL

Netherlands

x

PL

Poland

SPAIN RD 1699

Spain RD 1699 / 2011

x

SPAIN

Spain RD 1663 / 2000

x

UK G83-1

United Kingdom

UK G59-2

United Kingdom

x

Grids requiring

 

ETHERNET

 

for setup

DE LVD

Germany VDE AR N 4105

x

DK LVD

Denmark per VDE AR N 4105

x

Table 9.1.: 

Available grids for 3.0 TL and 5.0 TL

8.3.2.3  Set up Limited Power Start  (Optional)

 

In the Limited Power setting page, press 

S

elect

 button 

to select the limited power setting  Pressing 

S

elect

 

multiple times will advance through the possible limited 

power settings list. 

 

After the appropriate limited power is shown, press 

e

nter

 button to go to the confirm page.

 

Press 

e

nter

 on the confirm page to finalize your selec

-

tion or 

S

elect

 to redo the limited power selection.

Next / Enter

 

 
 
 
 
 
 

XXX

N / Y

 

 
 
 
 
 
 

XXX

x.x KW

 

 
 
 
 
 
 

Limited Power

Limited power setting available (XXX)

Display text

Description

5.0 KW

Default setting except for DE LVD

4.6 KW (only 

DE)

default for DE LVD

4.5 KW
4.0 KW
3.5 KW
3.0 KW

Fig. 9.1.: 

Power Limitation Label

NOTE

 

If you set a power limit then you 

must also fill out the label shown 

above stating "The power of the 

product has been power limited 

..." and apply this label to the front 

of the solar power inverter. Use a 

waterproof pen for filling out this 

information

 

► The power limitation is fixed after 

setting.  To adjust will require that 

you get a PIN from Delta techni-

cal support team.  See Chapter 10 

Settings for more detail on making 

changes.

The power limit will show on the display during start up 

phase (boot).  Please see display mesage below.  For the 

complete Start Up messages information, please see Chap-

ter 9.1.1 Start Up Messages.  You can restart the inverter to 

make the Start Up messages appear when you require this 

information.

Limited Power

4.6 / 5.0 KW

Please note that under limited power are two power settings 

shown.  The first is the Max. Power that the installer can set 

when needed.  The second setting is the Power Limitation 

described in this section.  

8.3.2.4  Insulation

The default insulation setting is enabled.  This will allow 

ground monitoring.  We recommend for safety reasons that 

you do not adjust this setting.  Press the Select button at 

this step to accept the default and move into the date and 

time setting.

8.3.2.5  Set the date and time

 
 
 
 

 
 
 
 
 
 

23:58

  31/12/2012

Configurable parameters

Display text

Designation

Description

31/12/2012

Date format

DD/MM/YYYY 

23:58

Time format

hh:mm (24h)

Main Menu Start

31/12/2012

23:58

31/12/2012

23:58

Blink

01/12/2012

23:58

Blink

SEL

xx/12/2012

23:58

Blink

xx/01/2012

23:58

Blink

SEL

ENT

ENT

ENT

xx/xx/xxxx

xx:58

Blink

xx/xx/xxxx

xx:59

Blink

SEL

ENT

ENT

ENT

ENT

SEL

SEL

SEL

Figure 9.2.: 

Setting the date and time on the display interface

Although the date and time can be set in the display inter-

face, it can also be adjusted at a later time in the Web Inter-

face if you have ETHERNET.  More details can be found in 

Chapter 10 - Settings.

 

Press the 

e

nter

 button to finish commissioning.

 

þ

Commissioning is now finished.

Содержание SOLIVIA 30 EU T4 TL

Страница 1: ...Operation and installation manual SOLIVIA 3 0 EU T4 TL SOLIVIA 5 0 EU T4 TL preliminary...

Страница 2: ...the device All information and specifications can be modified without prior notice Within this manual there may be symbols used that indicate that ETHERNET or WIRELESS function is required to utilize...

Страница 3: ...n features ETHERNET 19 5 7 Electrical connections 20 5 7 1 Overview 20 5 7 2 DC connections and DC switch 21 5 7 3 AC connection 21 5 7 4 Communications Module RS485 ETHERNET WiFi 21 5 7 4 1 RS485 int...

Страница 4: ...unication module ETHERNET WIRELESS 36 8 4 Next steps 37 9 Production information 38 9 1 Overview Menu Structure Display Interface 38 9 1 1 Startup Menu 38 9 1 2 Main Menu Loop 38 9 1 3 Measurement Loo...

Страница 5: ...ionality must be present to access the web interface 1 3 Warnings and symbols The following section explains the warnings and symbols used in this manual DANGER Indicates a dangerous situation An acci...

Страница 6: ...lar inverter during operation This potentially fatal voltage is still present for five minutes after all power sources have been discon nected Never open the solar inverter Always disconnect the solar...

Страница 7: ...sse ausreichend abgedichtet werden Nicht genutzte Anschl sse m ssen mit den am Solar Wech selrichter angebrachten Abdeckkappen verschlossen werden Italiano Indicazioni di sicurezza generali PERICOLO P...

Страница 8: ...este manual Antes de realizar trabajos en el inversor solar se debe separar el inversor solar de la red y de los m dulos FV El inversor solar presenta un valor de corriente de fuga elevado El conducto...

Страница 9: ...en m Najprv odpojte sie aby sol rny invertor nemohol dod va iadnu al iu energiu Potom rozpojte odpojova DC Zabezpe te DC pr pojky pred dotykmi Sol rny invertor mo no bezpe ne a norm lne prev dzkova i...

Страница 10: ...st te prevenci proti z sahu bleskem a to dodr ov n m ustanoven platn ch ve va zemi Povrch sol rn ho st da e m e b t velmi hork Sol rn st da je t k Sol rn st da je nutno zvedat a p en et v dy ve dvou K...

Страница 11: ...njury due to heavy weight The solar power inverter is heavy see Chapter 13 Technical Data Incorrect han dling can lead to injuries The solar power inverter must always be lifted by at least two people...

Страница 12: ...d in the following table SOLIVIA 3 0 TL and 5 0 TL inverter packing list Object Qty Description PV Inverter 1 3 kVA or 5 kVA solar inverter User Manual 1 The Instruction to provide the information of...

Страница 13: ...on Module Communication modules are available in three configurations depending on which inverter is ordered Type 1 is the stan dard default module that has the RS485 communication only Type 2 is a mo...

Страница 14: ...tion Hazardous voltage is still present 5 minutes after all power sources have been disconnected Never open the solar power inverter The solar power inverter contains no components that are to be main...

Страница 15: ...terface ETHERNET interface and WiFi module depends on the communications module type See the following section for further details 5 7 4 1 RS485 interface EIA485 The two RS485 interfaces are used to c...

Страница 16: ...s comes in multiple languages Accessible by Ethernet or WiFi connection IP address Ethernet 169 254 1 100 or WiFi 169 254 2 100 3 level of users are available Guest pwd guest Owner pwd owner Installer...

Страница 17: ...assumed temperature More exact information on tempera ture dependency is provided in the PV module data sheet The feed in voltage range of the solar power inverter defines the range of input voltages...

Страница 18: ...inte grated internal web interface Production information ETHERNET Production information is available for the actual day week month etc The production information is saved each month Warning and fai...

Страница 19: ...degree of pro tection and can be installed indoors and in protected outdoor areas Note the Operating temperature range at full power without derating and the maximum operating tem perature range When...

Страница 20: ...Mounting plate WARNING Danger of injury due to heavy weight The solar power inverter is heavy Incorrect handling can lead to injuries The solar power inverter must always be lifted by at least two peo...

Страница 21: ...ting nuts and washers for fastening the solar power inverter to the mounting plate The following items are also required Screws 5 mm dowels for fastening the mount ing plate to the wall 12 pcs M5 scre...

Страница 22: ...s kit allow you to meet the DC protection and signal requirements specified in UTE C 15 712 1 Multi Contact UTE Kit Delta Part Num ber Multi Contact UTE kit for SOLIVIA EU G4 TR EOE90000341 7 3 3 Esta...

Страница 23: ...dule kit is supplied in the scope of delivery Ethernet RS485 1 RS485 2 Antenna Rubber Seal Plug Claw Nut Fig 7 10 Assembly of the communications module The three openings for the cable feed through ar...

Страница 24: ...VDE 126A1 Germany VDE 0126 1 1 A1 x FR UTE France UTE 15 712 1 x NL Netherlands x PL Poland SPAIN RD 1699 Spain RD 1699 2011 x SPAIN Spain RD 1663 2000 x UK G83 1 United Kingdom UK G59 2 United Kingdo...

Страница 25: ...Guest Owner Installer Each level will have varied functions with Guest hav ing access to basic information and Installer with more advanced user rights For more info please see Chapter 9 Production I...

Страница 26: ...x xx Hz xxxx W DC xxx V xx x A xxxx W Today DC xxxxx Wh Today AC xxxxx Wh DC Life Energy xxxxxx KWh AC Life Energy xxxxxx KWh cos phi x xx PR xxx ENT or After 2 sec Measurement Information Section Sys...

Страница 27: ...r is master of Guest and Installer is the master of Owner and Guest User Levels Guest Owner Installer Example of the log in page Three user levels are avail able Guest Owner or Installer The user leve...

Страница 28: ...responds to a power gradient of 83 3 Hz User can set all necessary settings to meet the require ments from network operator P 0 Gradient 40 Pm Hz Pm Fstart 50 2Hz Power vs frequency curve for VDE AR N...

Страница 29: ...EC62109 2 Minimum Value R VMAX PV 30 mA 33K VDE0126 The array insulation resistance to ground shall be not less than 1 k V with respect to the maximum dc input voltage as specified by the manufacturer...

Страница 30: ...n AC plug and make sure it connects to inverter 3 Replace fuses and check all switching devices in boost inverter stages Grid Volt Under Rating 1 Actual utility voltage is under the UVR setting 2 Inco...

Страница 31: ...ace the defective relay s 2 Check the driver circuit inside the inverter 3 Check the Vgrid and Vout voltage detection accuracy Message Possible cause Action Bus Unbalance 1 Not totally inde pendent or...

Страница 32: ...Incorrect han dling can lead to injuries The solar power inverter must be lifted and carried by at least two people Or use an appropriate lifting device such as a crane 12 1 Decommissioning 1 Switch...

Страница 33: ...ass I Configurable trip parameters Yes 3 Isolation monitoring Yes Overload behavior Current limiting power limiting ENS Grid connection guidelines DIN VDE 0126 1 1 RD 1699 2011 RD1633 2000 UTE C15 712...

Страница 34: ...ating elevation 2 000 m above sea level 1 Cos Phi 1 VA W 2 AC voltage and frequency range will be programmed according to the individual country requirements 3 Ethernet communication module required t...

Страница 35: ...UR 4 6 10 3 6 32 0014P0001 UR 5 5 9 32 0016P0001 UR DC Plug 1 5 2 5 14 3 6 32 0011P0001 UR 5 5 9 32 0013P0001 UR 4 6 10 3 6 32 0015P0001 UR 5 5 9 32 0017P0001 UR MultiContact UTE kit The Multi Contact...

Страница 36: ...r Rating R Phase F42 CT current sensor Fail A F45 HW OOCP Circuit F50 Zero Cross Circuit Fail F56 Hardware Incompatibility F60 PV1 Current Over Rating F70 PV1 Current Transient Over Rating Error E01 O...

Страница 37: ...55 Certificates EN 15 Certificates Please visit the web site at www solar inverter com to find all applicable certificates for the SOLIVIA 3 0 TL 5 0 TL solar inverters...

Страница 38: ...upport greece solar inverter com 49 7641 455 549 Israel support israel solar inverter com 49 7641 455 549 Italy supporto italia solar inverter com 800 787 920 Free Call The Netherlands ondersteuning n...