7. Installation

30

31

7. Installation

EN

Solar inverter

Max. open circuit voltage of the 

PV array

SOLIVIA 3.0 EU T4 TL

630 V

SOLIVIA 5.0 EU T4 TL

1000 V

Table 8.3.: 

Max. open circuit voltage of the PV array

Solar inverter

Max. DC 

input current 

rating

Wire size Recommended 

PV power

SOLIVIA 3.0 EU 

T4 TL

10 A

2-3 mm

2

 / 

14 AWG

3360 W

SOLIVIA 5.0 EU 

T4 TL

17.5 A

2-3 mm

2

 / 

14 AWG

5950 W

Table 8.4.: 

DC input wire size

 

● The DC-MINUS connection is a socket. A connection 

plug is required for the DC-cable. 

 

● The DC-PLUS connection is a plug. A connection 

socket is required for the DC-cable. 

Tools and devices required.

Not supplied in the scope of delivery:

Single-core cable

Connection Socket and Connection Plug

DC Connection Type on Solar 

Inverter

Counterpiece Required for 

Cable

The DC-MINUS connection is 

a socket.

A connection plug is required 

for the DC cable.

The DC-PLUS connection is a 

plug.

A connection socket is required 

for the DC cable.

Connection sockets and connection plugs can be ordered 

from Multi-Contact at www.multi-contact.de. The required 

size depends on the wire cross-section and thickness of the 

cable used. 
You can also download the manual from the Multi-Contact 

website. This manual will also tell you which tools are 

required.

DC Connection of 

Power Inverter 

Connection T

ype 

for Cable

W

ire Cross-Section

Diameter Range for 

Cable Sheath

Multi-Contact 

Order 

No.

mm

2

AWG mm

DC+ Socket

1.5 / 2.5 14

3-6

32.0010P0001-UR

5.5-9

32.0012P0001-UR

4 / 6

10

3–6

32.0014P0001-UR

5.5-9

32.0016P0001-UR

DC-

Plug

1.5 / 2.5 14

3-6

32.0011P0001-UR

5.5-9

32.0013P0001-UR

4 / 6

10

3-6

32.0015P0001-UR

5.5-9

32.0017P0001-UR

Multi-Contact UTE kit (for France)

The Multi-Contact UTE Kit is designed to conform to the lat-

est French standard UTE C 15-712-1. It contains eight cou-

plings, an installation and removal key and a signal sticker. 

This kit allow you to meet the DC protection and signal 

requirements specified in UTE C 15-712-1.

Multi-Contact UTE Kit

Delta Part Num-

ber

Multi-Contact UTE kit for SOLIVIA EU G4 TR EOE90000341

7.3.3  Establishing Connection

1.  Check the polarity of the DC voltage at the DC connec-

tions before connecting the PV system.

2.  Install the connection plug/socket on the DC cable. Fol-

low the connection plug manual when doing this.

3.  Insert the DC cable into the DC connections for the 

solar inverter.

4.  Check the installation.

 

þ

The PV module is now connected.

 

► Insert the wires of the AC cable into the pin insert con-

nections. Observe the correct phase sequence when 

doing this.

 

► Tighten the screws of the pin insert to fix the wires in 

place.

N
PE

L

N

L

 

► Screw the cable housing 

 onto the socket insert 

 

and then screw the nut 

 onto the cable housing.

1.

2.

 

► Insert the AC plug into the AC socket 

 on the solar 

inverter until the AC plug locks into place.

4.  Ground the inverter if required.

 

Grounding screw

5.  Check the installation.

 

þ

The grid connection has been established.

7.3.2  Connection of the PV modules

DANGER

Danger of death or severe injuries from 

dangerous voltage

Dangerous voltages can be present at the 

DC connections of the solar power inverter. 

 

► Never disconnect the PV modules when 

the solar power inverter is under load. 

First switch off the grid connection so 

that the solar power inverter cannot 

feed energy into the grid. Then open the 

DC switch.

 

► Secure the DC connections against be-

ing touched.

NOTE

 

► To ensure protection conforming to IP65 

all unused connections and interfaces 

must be closed using the covers on the 

solar power inverter.

General instructions

The strings of the PV modules are connected to the DC 

connections, see 

Fig. 7.8, p. 30

Fig. 7.8.: 

Location of DC connections

The negative DC pole of the string is connected to the DC-

MINUS connection; the positive DC pole to the DC-PLUS 

connection, see 

Fig. 7.9, p. 30.  

The connections are 

coded to prevent incorrect polarity.

+

Fig. 7.9.: 

Connecting PV modules to DC connections

Содержание SOLIVIA 30 EU T4 TL

Страница 1: ...Operation and installation manual SOLIVIA 3 0 EU T4 TL SOLIVIA 5 0 EU T4 TL preliminary...

Страница 2: ...the device All information and specifications can be modified without prior notice Within this manual there may be symbols used that indicate that ETHERNET or WIRELESS function is required to utilize...

Страница 3: ...n features ETHERNET 19 5 7 Electrical connections 20 5 7 1 Overview 20 5 7 2 DC connections and DC switch 21 5 7 3 AC connection 21 5 7 4 Communications Module RS485 ETHERNET WiFi 21 5 7 4 1 RS485 int...

Страница 4: ...unication module ETHERNET WIRELESS 36 8 4 Next steps 37 9 Production information 38 9 1 Overview Menu Structure Display Interface 38 9 1 1 Startup Menu 38 9 1 2 Main Menu Loop 38 9 1 3 Measurement Loo...

Страница 5: ...ionality must be present to access the web interface 1 3 Warnings and symbols The following section explains the warnings and symbols used in this manual DANGER Indicates a dangerous situation An acci...

Страница 6: ...lar inverter during operation This potentially fatal voltage is still present for five minutes after all power sources have been discon nected Never open the solar inverter Always disconnect the solar...

Страница 7: ...sse ausreichend abgedichtet werden Nicht genutzte Anschl sse m ssen mit den am Solar Wech selrichter angebrachten Abdeckkappen verschlossen werden Italiano Indicazioni di sicurezza generali PERICOLO P...

Страница 8: ...este manual Antes de realizar trabajos en el inversor solar se debe separar el inversor solar de la red y de los m dulos FV El inversor solar presenta un valor de corriente de fuga elevado El conducto...

Страница 9: ...en m Najprv odpojte sie aby sol rny invertor nemohol dod va iadnu al iu energiu Potom rozpojte odpojova DC Zabezpe te DC pr pojky pred dotykmi Sol rny invertor mo no bezpe ne a norm lne prev dzkova i...

Страница 10: ...st te prevenci proti z sahu bleskem a to dodr ov n m ustanoven platn ch ve va zemi Povrch sol rn ho st da e m e b t velmi hork Sol rn st da je t k Sol rn st da je nutno zvedat a p en et v dy ve dvou K...

Страница 11: ...njury due to heavy weight The solar power inverter is heavy see Chapter 13 Technical Data Incorrect han dling can lead to injuries The solar power inverter must always be lifted by at least two people...

Страница 12: ...d in the following table SOLIVIA 3 0 TL and 5 0 TL inverter packing list Object Qty Description PV Inverter 1 3 kVA or 5 kVA solar inverter User Manual 1 The Instruction to provide the information of...

Страница 13: ...on Module Communication modules are available in three configurations depending on which inverter is ordered Type 1 is the stan dard default module that has the RS485 communication only Type 2 is a mo...

Страница 14: ...tion Hazardous voltage is still present 5 minutes after all power sources have been disconnected Never open the solar power inverter The solar power inverter contains no components that are to be main...

Страница 15: ...terface ETHERNET interface and WiFi module depends on the communications module type See the following section for further details 5 7 4 1 RS485 interface EIA485 The two RS485 interfaces are used to c...

Страница 16: ...s comes in multiple languages Accessible by Ethernet or WiFi connection IP address Ethernet 169 254 1 100 or WiFi 169 254 2 100 3 level of users are available Guest pwd guest Owner pwd owner Installer...

Страница 17: ...assumed temperature More exact information on tempera ture dependency is provided in the PV module data sheet The feed in voltage range of the solar power inverter defines the range of input voltages...

Страница 18: ...inte grated internal web interface Production information ETHERNET Production information is available for the actual day week month etc The production information is saved each month Warning and fai...

Страница 19: ...degree of pro tection and can be installed indoors and in protected outdoor areas Note the Operating temperature range at full power without derating and the maximum operating tem perature range When...

Страница 20: ...Mounting plate WARNING Danger of injury due to heavy weight The solar power inverter is heavy Incorrect handling can lead to injuries The solar power inverter must always be lifted by at least two peo...

Страница 21: ...ting nuts and washers for fastening the solar power inverter to the mounting plate The following items are also required Screws 5 mm dowels for fastening the mount ing plate to the wall 12 pcs M5 scre...

Страница 22: ...s kit allow you to meet the DC protection and signal requirements specified in UTE C 15 712 1 Multi Contact UTE Kit Delta Part Num ber Multi Contact UTE kit for SOLIVIA EU G4 TR EOE90000341 7 3 3 Esta...

Страница 23: ...dule kit is supplied in the scope of delivery Ethernet RS485 1 RS485 2 Antenna Rubber Seal Plug Claw Nut Fig 7 10 Assembly of the communications module The three openings for the cable feed through ar...

Страница 24: ...VDE 126A1 Germany VDE 0126 1 1 A1 x FR UTE France UTE 15 712 1 x NL Netherlands x PL Poland SPAIN RD 1699 Spain RD 1699 2011 x SPAIN Spain RD 1663 2000 x UK G83 1 United Kingdom UK G59 2 United Kingdo...

Страница 25: ...Guest Owner Installer Each level will have varied functions with Guest hav ing access to basic information and Installer with more advanced user rights For more info please see Chapter 9 Production I...

Страница 26: ...x xx Hz xxxx W DC xxx V xx x A xxxx W Today DC xxxxx Wh Today AC xxxxx Wh DC Life Energy xxxxxx KWh AC Life Energy xxxxxx KWh cos phi x xx PR xxx ENT or After 2 sec Measurement Information Section Sys...

Страница 27: ...r is master of Guest and Installer is the master of Owner and Guest User Levels Guest Owner Installer Example of the log in page Three user levels are avail able Guest Owner or Installer The user leve...

Страница 28: ...responds to a power gradient of 83 3 Hz User can set all necessary settings to meet the require ments from network operator P 0 Gradient 40 Pm Hz Pm Fstart 50 2Hz Power vs frequency curve for VDE AR N...

Страница 29: ...EC62109 2 Minimum Value R VMAX PV 30 mA 33K VDE0126 The array insulation resistance to ground shall be not less than 1 k V with respect to the maximum dc input voltage as specified by the manufacturer...

Страница 30: ...n AC plug and make sure it connects to inverter 3 Replace fuses and check all switching devices in boost inverter stages Grid Volt Under Rating 1 Actual utility voltage is under the UVR setting 2 Inco...

Страница 31: ...ace the defective relay s 2 Check the driver circuit inside the inverter 3 Check the Vgrid and Vout voltage detection accuracy Message Possible cause Action Bus Unbalance 1 Not totally inde pendent or...

Страница 32: ...Incorrect han dling can lead to injuries The solar power inverter must be lifted and carried by at least two people Or use an appropriate lifting device such as a crane 12 1 Decommissioning 1 Switch...

Страница 33: ...ass I Configurable trip parameters Yes 3 Isolation monitoring Yes Overload behavior Current limiting power limiting ENS Grid connection guidelines DIN VDE 0126 1 1 RD 1699 2011 RD1633 2000 UTE C15 712...

Страница 34: ...ating elevation 2 000 m above sea level 1 Cos Phi 1 VA W 2 AC voltage and frequency range will be programmed according to the individual country requirements 3 Ethernet communication module required t...

Страница 35: ...UR 4 6 10 3 6 32 0014P0001 UR 5 5 9 32 0016P0001 UR DC Plug 1 5 2 5 14 3 6 32 0011P0001 UR 5 5 9 32 0013P0001 UR 4 6 10 3 6 32 0015P0001 UR 5 5 9 32 0017P0001 UR MultiContact UTE kit The Multi Contact...

Страница 36: ...r Rating R Phase F42 CT current sensor Fail A F45 HW OOCP Circuit F50 Zero Cross Circuit Fail F56 Hardware Incompatibility F60 PV1 Current Over Rating F70 PV1 Current Transient Over Rating Error E01 O...

Страница 37: ...55 Certificates EN 15 Certificates Please visit the web site at www solar inverter com to find all applicable certificates for the SOLIVIA 3 0 TL 5 0 TL solar inverters...

Страница 38: ...upport greece solar inverter com 49 7641 455 549 Israel support israel solar inverter com 49 7641 455 549 Italy supporto italia solar inverter com 800 787 920 Free Call The Netherlands ondersteuning n...

Отзывы: