7. Installation
30
31
7. Installation
EN
Solar inverter
Max. open circuit voltage of the
PV array
SOLIVIA 3.0 EU T4 TL
630 V
SOLIVIA 5.0 EU T4 TL
1000 V
Table 8.3.:
Max. open circuit voltage of the PV array
Solar inverter
Max. DC
input current
rating
Wire size Recommended
PV power
SOLIVIA 3.0 EU
T4 TL
10 A
2-3 mm
2
/
14 AWG
3360 W
SOLIVIA 5.0 EU
T4 TL
17.5 A
2-3 mm
2
/
14 AWG
5950 W
Table 8.4.:
DC input wire size
● The DC-MINUS connection is a socket. A connection
plug is required for the DC-cable.
● The DC-PLUS connection is a plug. A connection
socket is required for the DC-cable.
Tools and devices required.
Not supplied in the scope of delivery:
Single-core cable
Connection Socket and Connection Plug
DC Connection Type on Solar
Inverter
Counterpiece Required for
Cable
The DC-MINUS connection is
a socket.
A connection plug is required
for the DC cable.
The DC-PLUS connection is a
plug.
A connection socket is required
for the DC cable.
Connection sockets and connection plugs can be ordered
from Multi-Contact at www.multi-contact.de. The required
size depends on the wire cross-section and thickness of the
cable used.
You can also download the manual from the Multi-Contact
website. This manual will also tell you which tools are
required.
DC Connection of
Power Inverter
Connection T
ype
for Cable
W
ire Cross-Section
Diameter Range for
Cable Sheath
Multi-Contact
Order
No.
mm
2
AWG mm
DC+ Socket
1.5 / 2.5 14
3-6
32.0010P0001-UR
5.5-9
32.0012P0001-UR
4 / 6
10
3–6
32.0014P0001-UR
5.5-9
32.0016P0001-UR
DC-
Plug
1.5 / 2.5 14
3-6
32.0011P0001-UR
5.5-9
32.0013P0001-UR
4 / 6
10
3-6
32.0015P0001-UR
5.5-9
32.0017P0001-UR
Multi-Contact UTE kit (for France)
The Multi-Contact UTE Kit is designed to conform to the lat-
est French standard UTE C 15-712-1. It contains eight cou-
plings, an installation and removal key and a signal sticker.
This kit allow you to meet the DC protection and signal
requirements specified in UTE C 15-712-1.
Multi-Contact UTE Kit
Delta Part Num-
ber
Multi-Contact UTE kit for SOLIVIA EU G4 TR EOE90000341
7.3.3 Establishing Connection
1. Check the polarity of the DC voltage at the DC connec-
tions before connecting the PV system.
2. Install the connection plug/socket on the DC cable. Fol-
low the connection plug manual when doing this.
3. Insert the DC cable into the DC connections for the
solar inverter.
4. Check the installation.
þ
The PV module is now connected.
► Insert the wires of the AC cable into the pin insert con-
nections. Observe the correct phase sequence when
doing this.
► Tighten the screws of the pin insert to fix the wires in
place.
N
PE
L
N
L
► Screw the cable housing
➁
onto the socket insert
➂
and then screw the nut
➀
onto the cable housing.
➁
➀
➂
1.
2.
► Insert the AC plug into the AC socket
➃
on the solar
inverter until the AC plug locks into place.
➃
4. Ground the inverter if required.
Grounding screw
5. Check the installation.
þ
The grid connection has been established.
7.3.2 Connection of the PV modules
DANGER
Danger of death or severe injuries from
dangerous voltage
Dangerous voltages can be present at the
DC connections of the solar power inverter.
► Never disconnect the PV modules when
the solar power inverter is under load.
First switch off the grid connection so
that the solar power inverter cannot
feed energy into the grid. Then open the
DC switch.
► Secure the DC connections against be-
ing touched.
NOTE
► To ensure protection conforming to IP65
all unused connections and interfaces
must be closed using the covers on the
solar power inverter.
General instructions
The strings of the PV modules are connected to the DC
connections, see
Fig. 7.8, p. 30
Fig. 7.8.:
Location of DC connections
The negative DC pole of the string is connected to the DC-
MINUS connection; the positive DC pole to the DC-PLUS
connection, see
Fig. 7.9, p. 30.
The connections are
coded to prevent incorrect polarity.
–
+
Fig. 7.9.:
Connecting PV modules to DC connections