46
Installation Instructions for the Hybrid E5 Battery Storage System EU V1 EN 2018-09-17
Connecting the inverter to the mains (AC)
Wiring the AC plug
Depending on how the Hybrid E5 System is used, the AC
plug must be wired differently.
Wiring variants
Use
1 = L (Grid)
4 = N (Grid)
PE
3 = N’ (Load)
2 = L’ (Load)
1
The Hybrid E5 System is connected to the mains.
If mains power fails, standalone mode (isolated oper-
ation) is used for emergency power supply.
1 = L (Grid)
4 = N (Grid)
PE
3 = N’ (Load)
2 = L’ (Load)
2
The Hybrid E5 System is connected to the mains.
Standalone mode (isolated operation) is NOT used
for emergency power supply.
#
1 = L (Grid)
4 = N (Grid)
PE
3 = N’ (Load)
2 = L’ (Load)
3
The Hybrid E5 System is only used in standalone
mode (isolated operation).
The Hybrid E5 System is NOT connected to the
mains.
This connection variant must be used if no public
mains connection is available at the installation site.
Wiring variants for the AC plug of the inverter
Readying AC cable for use and connecting it