Digital/analog module
Voltage output
Current output
Isolation
An analog circuit is isolated from a digital circuit by a digital integrated
circuit/an optocoupler, but the analog channels are not isolated from one
another.
Isolation between a digital circuit and a ground: 500 VDC
Isolation between an analog circuit and a ground: 500 VDC
Isolation between an analog circuit and a digital circuit: 500 VDC
Isolation between the 24 VDC and a ground: 500 VDC
DVP06XA-E2
Electrical specifications
Module name
DVP06XA-E2
Number of inputs/outputs
Inputs: four; Outputs: two
Analog-to-digital
conversion
Voltage input/Current input; Voltage output/Current output;
Supply voltage
24 VDC (20.4 VDC–28.8 VDC) (-15% to +20%)
Connector type
Removable terminal block (distance to the terminal is 5 mm)
Conversion time
400
μs
/channel
Weight
213 g
Things to note when connecting the module to a CPU PLC module:
1. Up to 8 modules can be connected to a CPU PLC module.
2. The connected module is numbered automatically from 0 (nearest to the CPU PLC module) to 7
(furthest away from the CPU PLC module).
3. The connected modules do NOT take up any digital I/O points.
A/D Functional specifications
Voltage input
Current input
Analog input channel
4 channels
Rated input range
±10V
±5V
±20 mA
0 ~ 20 mA
4 ~ 20 mA
Digital conversion range
±32,000
±32,000
±32,000
0 ~ 32,000
0 ~ 32,000
Hardware input limit*
1
±10.12V
±5.06V
±20.24 mA
-0.24~20.24 mA 3.81 ~ 20.19 mA
Digital conversion limit*
2
±32,384
±32,384
±32,384
-384 ~+32,384
-384 ~ +32,384
Hardware resolution
14-bit
14-bit
14-bit
13-bit
13-bit
Input impedance
≧
1M
Ω
250
Ω
Absolute input range*
3
±15 V
±32 mA
Digital data format
16-bit two’s complement number
Average function
Yes, CR#8 ~ CR#11, setting range: K1 ~ K100
Self-diagnosis function
Detecting if exceeding upper and lower limts or channel disconnection
Overall Accuracy
25° C/77° F: The allowed error range is ±0.5% of full scale.
0° C to 55° C/-32° F to 131° F: The allowed error range is ±1% of full scale.
Содержание DVP-ES3 Series
Страница 26: ...DVP ES3 Series Operation Manual 1 14 _1 MEMO ...
Страница 59: ...Chapter 3 Installing Software 3 5 3_ 9 Check the installation information and then click Install ...
Страница 232: ...DVP ES3 Series Operation Manual 8 28 _8 MEMO ...
Страница 385: ...DVP ES3 Series Operation Manual 13 8 _13 MEMO ...
Страница 399: ...DVP ES3 Series Operation Manual B 4 _ B MEMO ...
Страница 405: ...DVP ES3 Series Hardware Manual C 6 _C MEMO ...