D V P - E S 3 S e r i e s O p e r a t i o n Ma n u a l
4 - 4 0
_4
*4. Connect FE of the shielded cable to ground when the noise it too loud.
*5. Connect the terminal
to ground.
*6. CHX: Every channel can work with the input wiring shown above.
Note 1: use cables with the same length (less than 200 m) and use terminal resistors of less than 200 ohm.
4.9.2
Wiring DVP04TC-E2
+
-
I4 +
I4-
C ol d conjunction
compensation
MU X
+
-
J,K,R,S,T,E,N
- 80mV ~80 mV
I 1+
I 1-
FE
FE
Shielded c abl e*1
2 4V D C
D C /D C
Conv er ter
5V
AG
0V
24V
* 2
CH X
* 3
C HX
*3
S hielded cable*1
*1. The cable connected to the input terminal should be the cable or the shielded twisted pair cable connected
to a type J, K, R, S, T, E, N thermocouple. It should be kept separate from other power cables and cables
that generate noise.
*2. Connect the terminal
to ground.
*3. CHX: Every channel can work with the input wiring shown above.
Note 1: only use copper conducting wires with a temperature rating of 60/75°C and the length must be less
than 50 m.
Note2: TC modules must run for 30 minutes before they start to take any temperature measurement.