A p p e n d i x C E M C St a n d a r d s
3
C_
Conducted immunity test
Environmental phenomenon
Fast transient
burst
High energy surge
Radio frequency
interference
Reference standard
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
Interface/Port
Specific
interface/port
Test level
Test level
Test level
Data
communication
Shielded cable
1 kV
1 kV line-to-earth
10 V
Unshielded cable
1 kV
1 kV line-to-earth
10 V
Digital and analog
I/O
AC I/O
(unshielded)
2 kV
2 kV line-to-earth
1 kV line-to-line
10 V
Analog or DC
I/O(unshielded)
1 kV
1 kV line-to-earth
10 V
All shielded lines
(to the earth)
1 kV
1 kV line-to-earth
10 V
Equipment power
AC power
2 kV
2 kV line-to-earth
1 kV line-to-line
10 V
DC power
2 kV
0.5 kV line-to-earth
0.5 kV line-to-line
10 V
I/O power and
auxiliary power
output
AC I/O and AC
auxiliary power
2 kV
2 kV line-to-earth
1 kV line-to-line
10 V
DC I/O and DC
auxiliary power
2 kV
0.5 kV line-to-earth
0.5 kV line-to-line
10 V
Содержание DVP-ES3 Series