D V P - E S 3 S e r i e s O p e r a t i o n Ma n u a l
1 0 - 2 8
_10
Code
Indication
How to correct
E0
ASSeries PLC master module
receives the emergency message
sent from slave.
Read the relevant message with the PLC program
E1
PDO data length returned from the
slave is not consistent with the
length set in the node list.
Set the PDO data length of the slave and
re-download.
E2
PDO of slave is not received.
Check and ensure the setting is correct.
E3
Downloading auto SDO fails.
Check and ensure auto SDO is correct.
E4
Configuration of PDO parameter
fails.
Ensure that the PDO parameter setting is legal.
E5
Error in key parameter setting.
Ensure that the connected slave device is
consistent with the configured slave in the
software.
E6
The slave does not exist in the
network
Ensure that the power supply of slave is normal
and slave is correctly connected to the network.
E7
Slave error control is timed-out.
E8
The node IDs of master and slave
repeat.
Set the node ID of the master and slave again and
ensure their node IDs are unique.
5.
Codes displayed in SR825 when the DVP-ES3 Series PLC is the master:
Code
Indication
How to correct
0
In CANopen DS301 mode: the PLC
works as master and is working
normally.
Not in CANopen DS301 mode: the
master mode function is not
activated.
N/A
F1
No slave in the list
Add slave into the node list and then re-download
the configuration data.
F2
The data are being downloaded to
the PLC
Wait to finish downloading the configuration data.
F3
The configuration receiving error in
the PLC
Download parameter configuration again.
F4
Bus-OFF is detected.
Check that the CANopen bus cables are properly
connected and ensure that all the node devices run
at the same baud rate before you reboot.
F5
The PLC setting error such as
incorrect node address
The node address in the DVP-ES3 Series PLC
should be between: 1–127.
F8
Internal error; the error is detected in
the internal memory
If the same error occurs after cycling the power,
replace it with a new DVP-ES3 Series PLC.
FB
The sending buffer in the PLC is full.
Check that the CANopen bus cable is properly
connected and then reboot.
FC
The receiving buffer in the PLC is
full.
Check that the CANopen bus cable is properly
connected and then reboot.
Содержание DVP-ES3 Series
Страница 26: ...DVP ES3 Series Operation Manual 1 14 _1 MEMO ...
Страница 59: ...Chapter 3 Installing Software 3 5 3_ 9 Check the installation information and then click Install ...
Страница 232: ...DVP ES3 Series Operation Manual 8 28 _8 MEMO ...
Страница 385: ...DVP ES3 Series Operation Manual 13 8 _13 MEMO ...
Страница 399: ...DVP ES3 Series Operation Manual B 4 _ B MEMO ...
Страница 405: ...DVP ES3 Series Hardware Manual C 6 _C MEMO ...