Chapter 5 Parameters and Functions
5-15
_5
A2
40163
demand value below
this value clears
alarm)
A3
40164
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Over Apparent Power Demand
A4
40165 Alarm enable
0: Disable
1: Enable
word
2
R/W
A5
40166
Pickup setpoint
(apparent power
demand value
exceeding this value
triggers alarm)
0.000 – 99999.999
float
kW
4
R/W
A6
40167
A7
40168
Pickup time delay
(alarm–trigger delay) 0 – 99
word
s
2
R/W
A8
40169
Dropout setpoint
(apparent power
demand value below
this value clears
alarm)
0.000 – 99999.999
float
kW
4
R/W
A9
40170
AA
40171
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Over Frequency
AB
40172 Alarm enable
0: Disable
1: Enable
word
2
R/W
AC
40173 Pickup setpoint
(frequency value
0.0000 – 99.9999
float
Hz
4
R/W
Содержание DPM-D520I
Страница 3: ......
Страница 9: ...Delta Din rail Power Meter DPM D520I User Manual 1 4 _1 _1 MEMO...
Страница 15: ...Delta Din rail Power Meter DPM D520I User Manual 2 6 _2 MEMO...
Страница 31: ...Delta Din rail Power Meter DPM D520I User Manual 4 10 _4 MEMO...
Страница 116: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...
Страница 119: ...Delta Din rail Power Meter DPM D520I User Manual 6 4 _6 Memo...
Страница 120: ...A 1 Appendix A Accessories Table of Contents A 1 DCT1000 Series A 2 A 2 DCT2000 Series A 4 12 A...
Страница 125: ...Delta Din rail Power Meter DPM D520I User Manual A 6 _A _1 _1 MEMO...