Chapter 5 Parameters and Functions
5-5
_5
7: Clear all
8: Reset time of use value and
accumulated energy value from
auto recording
9: Reset accumulated energy
value from energy saving mode
of the measured equipment
1D
40030 Demand
0: block
word
2
R
1E
40031 Demand time interval 0–60
word Minute
2
R/W
Alarm – Over Current
1F
40032 Alarm enable
0: Disable
1: Enable
word
2
R/W
20
40033 Pickup setpoint
(current value
exceeding this value
triggers alarm)
0.000 – 99999.999
float
A
4
R/W
21
40034
22
40035
Pickup time delay
(alarm–trigger delay)
0 – 99
word
s
2
R/W
23
40036
Dropout setpoint
(current value below
this value clears
alarm)
0.000 – 99999.999
float
A
4
R/W
24
40037
25
4038
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Under Current
26
4039 Alarm enable
0: Disable
1: Enable
word
2
R/W
27
40040
Pickup setpoint
(current value below
0.000 – 99999.999
float
A
4
R/W
Содержание DPM-D520I
Страница 3: ......
Страница 9: ...Delta Din rail Power Meter DPM D520I User Manual 1 4 _1 _1 MEMO...
Страница 15: ...Delta Din rail Power Meter DPM D520I User Manual 2 6 _2 MEMO...
Страница 31: ...Delta Din rail Power Meter DPM D520I User Manual 4 10 _4 MEMO...
Страница 116: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...
Страница 119: ...Delta Din rail Power Meter DPM D520I User Manual 6 4 _6 Memo...
Страница 120: ...A 1 Appendix A Accessories Table of Contents A 1 DCT1000 Series A 2 A 2 DCT2000 Series A 4 12 A...
Страница 125: ...Delta Din rail Power Meter DPM D520I User Manual A 6 _A _1 _1 MEMO...