Chapter 5 Parameters and Functions
5-13
_5
88
40137 Alarm enable
0: Disable
1: Enable
word
2
R/W
89
40138
Pickup setpoint (total
displacement power
factor value below this
value triggers alarm)
0.00000 – 1.00000
float
4
R/W
8A
40139
8B
40140
Pickup time delay
(alarm–trigger delay) 0 – 99
word
s
2
R/W
8C
40141
Dropout setpoint (total
displacement power
factor value
exceeding this value
clears alarm)
0.00000 – 1.00000
float
4
R/W
8D
40142
8E
40143
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Alarm – Over Current Demand
8F
40144 Alarm enable
0: Disable
1: Enable
word
2
R/W
90
40145
Pickup setpoint
(current demand
value exceeding this
value triggers alarm)
0.000 – 99999.999
float
A
4
R/W
91
40146
92
40147
Pickup time delay
(alarm–trigger delay)
0 – 99
word
s
2
R/W
93
40148
Dropout setpoint
(current demand
value below this value
clears alarm)
0.000 – 99999.999
float
A
4
R/W
94
40149
95
40150
Dropout time delay
(alarm–clear delay)
0 – 99
word
s
2
R/W
Содержание DPM-D520I
Страница 3: ......
Страница 9: ...Delta Din rail Power Meter DPM D520I User Manual 1 4 _1 _1 MEMO...
Страница 15: ...Delta Din rail Power Meter DPM D520I User Manual 2 6 _2 MEMO...
Страница 31: ...Delta Din rail Power Meter DPM D520I User Manual 4 10 _4 MEMO...
Страница 116: ...6 1 Chapter 6 Error Codes Table of Contents 6 1 Error Codes 6 2 6 2 Alarm Types 6 2 6...
Страница 119: ...Delta Din rail Power Meter DPM D520I User Manual 6 4 _6 Memo...
Страница 120: ...A 1 Appendix A Accessories Table of Contents A 1 DCT1000 Series A 2 A 2 DCT2000 Series A 4 12 A...
Страница 125: ...Delta Din rail Power Meter DPM D520I User Manual A 6 _A _1 _1 MEMO...